Loading…
Loading…
Tender ID
Tender Value
₹1.7 Cr
EMD Value
₹1.7 L
Closing Date
18 Apr 2026, 6:00 pmClosed
Additional City Engineer (I/C)
Supply, Installation, Testing and Commissioning SITC of Electro Mech machineries at Katariya Kalawad Road and 2nd Ring Road Junction UB Pumping Station with 05 Years Comprehensive Operation & Maintenance
292833
RMC/Katariya(KUB)-EM/26-27/01
Open
Supply,erection and Commissioning
Works
Rajkot
14 documents required · 13 mandatory · 1 optional
₹4,500
Rajkot Municipal Corporation
₹1.7 L
2 Apr 2026
2 Apr 2026
2 Apr 2026
18 Apr 2026
2 Apr 2026
physical submission of required documents. Technical bid must be submitted by
RPAD/Speed post only.
Office of the Dy Executive Engineer (Mech)
Rajkot Municipal Corporation,
Dr. Ambedkar Bhavan,
Central Zone Office,
Water Works, Room No.6,
Dhebar Road, Near ST bus stand,
Pre-Qualification Criteria:
Financial Criteria:
1. The bidder must have achieved a minimum annual turnover in any one year over the last
seven financial years (i.e. 2024-25 to 2018-19) of the annual value of contract applied for.
(i.e.,Rs.1,71,01,550/-)(Rajkot Municipal Corporation’s Enhancement Factor can be
2. The bidder has liquid assets (aggregate of Working capital, cash in hand and uncommitted
bank guarantees) and/or credit facility equal to 25% of the contract value. (i.e.
3. Available Bid Capacity-ABC must be more than the tender amount.
Note:- The estimated cost of the work is Rs. 1,71,01,550/- for one year for the purpose of
calculation of Annual turnover and Working capital.
B) Experience Criteria:
1. The bidder has successfully completing or substantially completing at least one contract of
similar nature of work at least 40% of the value of proposed contract within the last seven
years. (i.e. Rs.68,40,620/-)
2. Substantially completed works means those works which are at least 90% completed as on the
date of submission (i.e. gross value of done up to the last date of submission is 90% or more of
the original contract price.) and continuing satisfactorily. Experience certificate of competent
authorities required to be submitted Only 3(A) CERTIFICATE will be considered as
experience certificate and sign not belongs to executive engineer.
Note:- Experience as a contractor of similar nature of work
The physical submission must be accompanied by a EMD of Rs. 1,71,020/- as well as e-
tender fee (non-refundable) of amount of Rs.4500/- in terms of Demand draft in favor of
Municipal Commissioner, Rajkot Municipal Corporation, Rajkot, from any Nationalized Bank or
as per Finance Department, GR No.-FD/MSM/e-file/4/2024/2859/DMO, Dt.01/05/2025 and
must be delivered within seven days from the last day of submission of bid. The bid security
and tender fee must be included with the physical submission on address below by RPAD only:
Addi. City Engineer
Water Management Unit (Hand Pump)
Room No.06, Dr. Ambedkar Bhavan,
Central Zone Office, Dhebarbhai Road,
Rajkot Municipal Corporation
The bidder also can pay EMD and Tender fee by NEFT/RTGS or Online Transfer.
RMC BANK ACCOUNT DETAILS
A/C No.: 015305010638 Bank Name: ICICI Bank
IFS Code: ICIC0000153 Branch: Jay Hind Press
Following documents shall be submitted in original at above Address by RPAD only:
Following documents shall be submitted in electronic format through online by scanning And In Hard
copy Only Tender Fee, EMD and Tender Document(Technical Bid, Price Bid and Corrigendumm) also
with duly sign and stamp of Agency at above Address by RPAD.
: The required documents to be submitting online on website https://rmctender.nprocure.com
3. Tender Documents (Technical bid, Price Bid and Corrigendum)
4. GST No. Details
5. PAN No. Details
6. PF and ESIC Details
7. Professional Tax Details -Enrollment certificate(Firm) and Registration certificate (Employee)
8. Class Registration Certificate
9. Work Experience Certificate- Only 3(A) CERTIFICATE will be considered as experience
certificate and sign not belongs to executive engineer
10. Power of Attorney (if Applicable)
11. Current Electrical Contractor License
12. Turnover Details of last seven years
13. Working Capital Details
14. No Blacklist Affidavit on Rs. 300/- Stamp Paper with notarized as per tender format.
15. Sites visit & fully aware with nature of work confirmation letter
Terms & Conditions:
1. Tenderer has to submit tender documents online at https://rmctender.nprocure.comand Submit
Hard copy of tender fee, EMD, signed tender copy only on address given above by RPAD only:
2. Conditional tender are liable to be rejected.
3. Joint venture or MOU is not permitted.
4. The bidder should provide accurate information on any litigation history or arbitration resulting
from contracts completed or under execution by him over the last ten years. This should also
include such cases, which are in process/progress. A consistent history of awards against the
bidder may result in failure of the bid. In case the bidder has not provided such information and
has come to the notice of the authority, the tender will be rejected at what so ever stage and in
such case all the losses that will arise out of this issue will be recovered from the
tenderer/bidder and he will not have any defense for the same.
5. Enhancement factor at 10% per year for last seven years will be applicable to arrive average
annual turnover and finalize the magnitude of work done in last seven years.
6. The Bidder / firm must have current Registration in E1-Class or Above(R & B) with of any State
Government / Central Government authority.
7. The agency should not be Black Listed/Debar/Terminated anywhere in India, for which, agency
will have to submit fresh Notarized Affidavit on Rs.300/- judicial stamp paper.
8. Sites visit & fully aware with nature of work confirmation letter
9. Power of Attorney authorizing the person for signing the Tender and give any clarification
asked by department.
10. The agency shall also have to submit the documentary evidence for possessing the Current
Electrical Contractor License in Electrical Department of Government.
11. The contractor shall have to purchase the material required for this tender work, only from the
supplier having registered GST Number. RMC will not be responsible to pay any amount
towards GST if the material is purchased from the unregistered supplier / not having GST
12. Also, the details of works on hand and works completed shall have to be mentioned in the
Annexure-II of Technical Bid (Volume-I)
13. The successful bidder shall have to pay security deposit amounting to 5% of Contract Value in
favour of "Rajkot Municipal Corporation" in terms of Fixed Deposit Receipt of Nationalized
Bank or as per Finance Department, GR No.-FD/MSM/e-file/4/2024/2859/DMO,Dt.01/05/2025
valid for the period of 30 Months.
If the contract price offered by the selected bidder is lower than 10% but up to 20% of
the Estimated project Cost than the additional performance security shall be calculated @20%
of the difference in the Estimated Project Cost minus 10% of the Estimated Project Cost and
Contract Price offered by the selected Bidder.
If the contract price offered by the selected bidder is lower than 20% of the Estimated
project Cost than the additional performance security shall be calculated @30% of the
difference in the Estimated Project Cost minus 10% of the Estimated Project Cost and Contract
Price offered by the selected Bidder.
The Additional Performance Security shall be treated as part of the Performance
Security. The Performance Security shall be valid beyond 60 days of the defect liability period
and the additional Performance Security shall be valid beyond 28 days of Project completion
14. The Tender of those bidder(s) those who fails to submit the required documents physically
within the stipulated date and time, will be treated as non responsive and their Price Bid will
15. After opening of Technical Bid, the procedure for the pre-qualification shall be adopted and the
Price Bid of only successful qualified bidder shall be opened for final evaluation of the contract.
The decision of Municipal Commissioner regarding the pre-qualification shall be final and
binding to all the bidders.
16. After opening of the Technical Bid, if the agency is disqualified for this work and under such
circumstances if the agency tries to pressurize the Evaluation Committee through any means
then the offer of such bidder will be treated non-responsive and liable to be rejected out rightly
without assigning any reason thereof.
17. Enter into an agreement on stamp paper as per prevailing norms. It shall be incumbent on the
Contractor to pay the stamp duty and the legal charges for the preparation of the contract
18. The Jurisdiction will be Rajkot City only.
19. Commissioner, Rajkot Municipal Corporation, Rajkot, reserves the right to accept / reject any or
all e-Tender(s) without assigning any reasons thereof.
Add. City Engineer
Water Management Unit
Rajkot Municipal Corporation
Supply, Installation, Testing and Commissioning (SITC) of Electro‐Mech
machineries at Katariya under bridge with 05 Years comprehensive
Operation and Maintenance.
1 Bill of Quantities (General)
2 Information to Tenderer
3 Commercial Conditions
1.0 BILL OF QUANTITIES (GENERAL):
The Bill of quantities consists of following section:
1.2 Supply items (Mechanical , electrical)
Erection Items ( Including storage , installation testing and
commissioning of pumping machinaries with accessorieses)
The bill of quantities forms the most important part of the tender
documents. The supply, installation and Commissioning of various
equipments which form a part of total work are indicated in the schedules
separated included in this documents. The tendering contractors shall price
each of the item of this document separately.
Each item in the bill of quantities is to be individually priced in in k and the
same should be added up to the tender sum. No column in the bill of
quantities shall be left blank. The description of the works given here is only
for guidance and all relevant clause must be consulted. The contractor's price
must allow for all works as per the detailed specifications and for all
contractual obligations whether separately specified or not.
1.1 SUPPLY ITEMS:
The supply items (Mechanical-Electrical)
As mentioned in the tender document.
1.2 ERECTION ITEMS: -
Erection testing and Commissioning :
The bill of quantities for storage, installation, testing and commissioning of
the pumping machineries, It also includes provisions of contractors
equipments/machinery, power cabling etc., complete.
This shall also include:
I Performance testing and maintenance.
II Ten days trial running and maintenance.
In case the tendering contractor given alternative design, a separate bill of
quantities on exactly similar lines as in this tender shall be acceptable.
Tenderer may modify description of the items to suit his alternative offer
without changing the format.
1.4 The bill of quantities, general conditions of contract and the specifications
which from an integral part of this contract shall be read in conduction.
1,5 The rates and prices in the bill of quantities shall except in case separately
provided for, be deemed to cover all the contractual obligations including GST
under this and above quoted documents which require the setting of the works
for satisfactory performance.
BILL OF QUANTITY
NAME OF WORK: Supply, Installation, Testing and Commissioning (SITC) of Electro‐Mech machineries at
Katariya under bridge with 05 Years comprehensive Operation and Maintenance.
PART – A (SITC)
Item Decription Qty. Unit Rate in Rs. Amount in Rs.
MECHANICAL WORK
1 SEWAGE SUBMERSIBLE NON CLOG PUMP-MOTOR SET 5 Ea. 533453.00
Supply, installation, testing and commissioning of non clog sewage
submersible pumnp with SS CF8M Impeller, CI Casing to Gr 260,SS
410 shaft suitable for 3 Phase, 415 V, 50 Hz., AC supply submersible
motor having Class 'F' insulation with temperature rise limit to
Class "B" and IP-68 protection.
The scope shall include all required accessories pump viz. If req. SS-
304 heavy duty & of suitable size double guide pipes of length to
suit the sump height with required supports, SS-304 or suitable
stainless steel grade Chain with shackles (shall be with dual hook /
shackles of 150 mm or suitable higher size at app. every 1.5m C-C
distance) & of length as per sump height + min. 3m, Check valves,
sluice valves, pressure gauge, automatic coupling device, delivery
bend suitable to install pump set in new sump, thrust block, .
Submersible Power & control cable upto starter panel through
suitable size GI pipe (copper flexible & stranded type conductor of
reqd. cores & size for each pump motor set) & of length sump
height + min. 15 m long each run with necessary electrical
termination connection at junction box / starter panel.
The pump set shall be provided along with automatic shut down
arrangement when water level in sump go down to the minimum
water level (MWL)
The scope also includes providing civil foundation for duck foot
bend for auto coupling etc & any other required minor civil
modification /rectification /thrust blocks/finish work to complete
Pump Capacity : Discharge 360 m3/hr, Head: 16 m, ( 4W + 1S ),
Overall Efficiency at Duty : 70 %, delivery pipe size 200mm dia
Motor Rating: 30 HP / 22.5 kW (or higher rating as reco. by pump
Make: KIRLOSKAR, KSB, JASCO, KISHOR, PULLEN, AQUA.
2 MOTOR CONTROL PANEL OR STARTER 5 Ea. 23809.00
Supplying & erecting approved make motor control cubical panel
[Star delta] made from 16G CRCA sheet duly epoxy powder painted
inside and outside with hinged doors and locking with suitable size
of ON - OFF isolator (AC 3 / 23 duty) main fuses. Digital volt and
current meter (in a single unit) with micro controller based control
unit and current sensing single phasing preventer electronic
overload protection, PMJ, Capacitors, over voltage (Programmable)
protection and under voltage (Programmable) protection, prod less
dry run protection programming facility for setting of all parameter
like overload current, high voltage limit, low voltage limit, dry run
limit with digital indication on seven segment LED display for any
fault like over load, high voltage, low voltage, dry running single
crimped, electronic star delta timer, feather touch start / stop push
buttons to be erected on angle iron frame. Grouted on wall the
contactors will be of L& T, Siemens , BCH make only).. The starter
shall matcch GWSSB standard specification for 30 HP non- clog
pump notor set.
Make :L&T,Siemens, ABB. schniders, switchgears.
3 SEWAGE SUBMERSIBLE NON CLOG PUMP-MOTOR SET 3 Ea. 302528.00
Supply, installation, testing and commissioning of non clog sewage
submersible pumnp with SS CF8M Impeller, CI Casing to Gr 260,SS
410 shaft suitable for 3 Phase, 415 V, 50 Hz., AC supply submersible
motor having Class 'F' insulation with temperature rise limit to
Class "B" and IP-68 protection.
The scope shall include all required accessories pump viz. If req. SS-
304 heavy duty & of suitable size double guide pipes of length to
suit the sump height with required supports, SS-304 or suitable
stainless steel grade Chain with shackles (shall be with dual hook /
shackles of 150 mm or suitable higher size at app. every 1.5m C-C
distance) & of length as per sump height + min. 3m, Check valves,
sluice valves, pressure gauge, automatic coupling device, delivery
bend suitable to install pump set in new sump, thrust block, .
Submersible Power & control cable upto starter panel through
suitable size GI pipe (copper flexible & stranded type conductor of
reqd. cores & size for each pump motor set) & of length sump
height + min. 15 m long each run with necessary electrical
termination connection at junction box / starter panel.
The pump set shall be provided along with automatic shut down
arrangement when water level in sump go down to the minimum
water level (MWL)
The scope also includes providing civil foundation for duck foot
bend for auto coupling etc & any other required minor civil
modification /rectification /thrust blocks/finish work to complete
Pump Capacity : Discharge 100 m3/hr, Head: 16 m, ( 1W + 1S ),
Overall Efficiency at Duty : 70 %, delivery pipe size 150mm dia
Motor Rating: 12.5 HP / 9.63 kW (or higher rating as reco. by pump
Make: KIRLOSKAR, KSB, JASCO, KISHOR, PULLEN, AQUA.
4 MOTOR CONTROL PANEL OR STARTER 3 Ea. 13658.00
Motor control panel or fully automatic star-delta starter with
necessary electrical connections and electrical control panel with
starter overload relay range 13-21 ampere including individual
MCB, analog volt meter with selector switch, analog ampere meter
with selector switch, SPP, PMU, capacitors, phase indicators, as
well as digital meters as per GWSSB standard specification for
HP non- clog pump notor set.
Make :L&T,Siemens, ABB. schniders, switchgears.
5 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Ea. 440250.00
Supply, installation, testing, commissioning of Electrically operated
Chain Hoist & Electically operated geared trolley suitable to
operate on Mono Rail Girder having motorized motion in vertical
liftingg & for cross travel, manufactured as per IS:6547-1972-Class
II & IS-3177- Class-II, complete with electrically operated chain
hoist & Electically operated geared trolley, brake, chain-gear,
motors, safety device, pendant push button, starter panel, cables
from motor to starter panel and all other required accessories like
limit switches, panel, power supply system (Fastoon cable
type),fasteners, epoxy painting, etc. tested to 50% over load,
complete and as per specifications.
Note: Capacity of Electric CPB hoist shall be minimum as specified
or min.1.5 times the weight of single heaviest component to be
lifted at Pump location whichever is higher.
Capacity: min. 1 Ton. As required
Lift: 15 m. (min) , Span 9 m to 12 m or as requried, Long Traves
Mtr or as requried, Make:- Morris / Indef/ Safex / WH Brady
/Anker/ Max/ Japs
6 Manufacture supply and delivery, lowering & laying of submerged 8000 Kg 137.00
arc welded M.S pipe out side coated with best quality Bituminus
Paint with Epoxy coating to inside pipeline with two parts of
Solvent free high build liquid epoxy lining as per AWWA C210-07
suitable for portable water application & shall be approved by
CFTRI India/BS 6920-UK/international standard/NSF/ANSI/-61
to be fit for contact with portable water for consumption with
micron thickness, having a beveled ends plate and coil conferming
to is 3589-2001 or its latest revision /ammendment for following
thickness including all taxes, transportation, freight charges, octroi,
inspection charges, loading, unloading, conveyance to
Departmental stores/ site, stacking, etc. including specials and
wastage etc.; complete Tender
Specifications: Make:- Essar / Tata / Jindal / SAIL/ Zenith / Asian
7 M.S. specials plain/ Flanged ended 1150 Kg 137.00
Erection, Installation, Testing & Commissioning of M.S. Specials for
Delivery, By Pass & Header Piping with Flanges, eccentric Nozzles,
Nut-Bolts, Y -tee connection, puddle flanges etc. Complete. Up to
8 Providing , erecting , fabricating the M.S. structure as per 5250 Kg 137.00
requirement on site incorporating proper size of M.S. angles, flats,
bars, channels, sections complete with cutting, welding, grinding &
finishing duly painted with one coat of red oxide with erection on
site as per direction of engineer in charge with necessary grouting,
cementing, plastering & finishing complete. (For Covering Cutout
9 Providing , erecting , fabricating the M.S. structure as per 5000 Kg 137.00
requirement on site incorporating proper size of M.S. angles, flats,
bars, channels, sections complete with cutting, welding, grinding &
finishing duly painted with one coat of red oxide with erection on
site as per direction of engineer in charge with necessary grouting,
cementing, plastering & finishing complete. (For Making Stair
D Electrical Panel
10 Supply, Installation, Testing and Commissioning of Electrical Panel 1 Ea 300211.00
manufactured as per IEC 61439 as per Following
Construction 14 SWG MS CRC Sheet Type 2B construction
Incoming Changeover -400A FP Auto changeover Switch
MCCB - 400A FP, Micro Processor Type With E/F protection, SPD
Outgoing MCCB - 8 Nos 80A FP, Variable TM type MCCB-2Nos, 63A
FP, Variable TM type MCB - 4 Nos 32A C Curve Busbar : 400A AL
PVC Sleeved with 0.8A Current Density Digital Ammeter Digital
Voltmerer Indicating Lamps-12 Nos.
Capacitor Bank:
Outgoing 160A MCCB, from
Ougoing : (5+10+20+20+20) KVAR 550V APP Capacitors with
Detuned reactors
8 Stage APFC relay, timer contactor, Indicating Lamp A/M Switch
etc as required Switchgear Make : L&T, Siemens, Schneider
11 Design, Supplying, installing, testing of factoryfabricated ready 1 Ea. 216103.00
made Three phase APFC Panel Cubical Panel fabrication should be
type tested as per IEC 61921, 61439:1&2 Capacitor Duty Contactor
for switching as per following Steps Incomer Switch of MCCB type
Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth fault
protection Incomer Switch of MCCB type Icu=Ics=50KA at 400/440
Volts, with OC, SC, internal earth fault protection, Copper tinned
insulated Busbar, Cubical panel should be indoor type with IP
and IK 10,Metalized polypropylene film tye3-phase 550Volt
Capacitor, De tuning Reactor for each capacitor, Panel having Short
Circuit and Overload protection, Each step Capacitor having
suitable MCB with Sc, OL, internal earth fault relay, Each stage
having Stage Contactor (Capacitor load rating), A/M switch, PF
regulator master controller having suitable steps with LCD
display, Rs 485 Communication port, Indication LED Lamps for main
incomer and ON-OFF for each capacitor bank, MS Chanel for
Floor mounting, Cable entry as per site situation,Cooling fans for
12 Supplying rubber matting of 12mm thickness as per IS:15652/IEC 20 Sqmt 3051.00
13 Follow Up with supply co. for getting supply . The scope also covers 1 Ea 15000.00
laying of L.T. cable from Meter to MCCB. This also covers to obtain
any permission required for road crossing from any authority (if
required), Filling the necessary application to supply co., following
up and getting the supply filling the necessary test report to the
supply co. All official fees shall be paid by client on presentation of
documentary proof and all other out of pocket expenses shall be of
14 CHANGEOVER SWITCH 1 Ea. 26231.00
Supply of Approved make Iron Clad or metal clad four pole change
over switch 415V. confirming to IS in sheet steel enclosure of
following capacity and Erection on New angle iron frame duly
painted with red oxide .
Rating: 400 A Cat-lll
Providing and erecting Approved make Four pole moulded case
circuit breaker having breaking capacity ICU of 50 KA and above at
415 V having Normal current rating 400A. with micro processor
based release suitable to work on A.C.supply 50 c/s. With all
internal connections, spreader tinned copper & complete erected
with supply of 16 G.M.S. housing.
ICS=100% of ICU only Cat III
Make :L&T,Siemens, ABB. schniders, switchgears.
16 Supplying and erecting, commissioning and testing of Diesel
Generating set confirming to IS: 4722:1968 & BS:5514 having
continuous rating, 3 phase, 415 volts, 50 cycles A.C. supply
comprising of a totally enclosed air/water cooled diesel engine
with multi-cylinders developing suitable BHP not less than
following capacity at 1500 RPM with 10% overload for one hour in
24 hours with standard accessories like fly wheel, lubricating oil
cooler, "A" class governor, heavy duty fuel wheel and lubricating oil
filter, oil bath air filler, lubricating oil pressure gauge, end exhaust
manifold, standard set of tools with adjustable spanners, screw
drivers, cylinder head to cover, joint cylinder head to exhaust,
element lube oil filter, 12 / 24 volts electric starting equipment
complete with standard heavy duty battery, dynamo, cut-outs,
ammeter, necessary wiring, pressure gauge, starter etc and heavy
duty Residential type exhaust silencer (With DEF System) and
vertical hot air duct both
logged with asbestos rope, save oil trays, exhaust piping of
required length, standard wall/floor mounted fuel with level
indicator and piping and drip proof alternator, self excited, self
regulated, screen protected, with excitation system, capable of
delivering the rated system output at 415 volts, 3 phase, 0.8 PF,
Hz, 4 wire, running at 1500 RPM, conforming to IS-4722- 1968 with
voltage regulation +/- 5% of rated voltage from no load to full
load. Both the engine and alternator fitted on a common
fabricated steel base plate with antivibration mounting engine
and alternator both connected to each other by flexible flange
coupling and with floor/wall mounted control panel box
comprising of voltmeter ammeter, selector switches, ACB / MCCB
/ MCB of adequate capacity,
indicator lamps duly wired with HRC fuses. The alternator & 1 Ea. 1574322.00
control panel shall be connected with provided suitable capacity
armoured cable and complete with Acoustic enclosure (canopy)
made out of 16 SWG CRCA Sheet, sound absorbing material
Rockwool of 64 density & 100 mm thick conforming to IS:8183 / PU
Foam of 40 Density - at least 40 mm. The resin bonded rockwool
covered from inside the canopy by perforated sheet with 3/4 mm
holes, sound level not more than 75 dB at a distance of 1 mtr, as
per PVCT norms.DG set should have in built fuel tank capacity of
minimum 8 hrs of continous running capacity on full load .
Erection, commissioning and satisfactory testing as per
requirement with first filling of fuel (minimum up to the 80% of
fuel tank capacity), oil, etc. with guarantee / Warrantee of
complete system for Two years. & with obtaining all necessary
certificate from Electrical Inspector. The Capacity and Ratings of DG
sets are as below. (As per new CPCB4+ Emission norms Engine
With - Turbo Charger, EGR (Exhaust Gas Recirculation), CRS
(Common Rail Fuel System), DOC (Diesel Oxidation Catalyst), SCR
(Selective Catalytic Reduction), Integrated wiring harness
connected to ECU .)
Continuous rating of 200 KVA ,BHP not less than 254 BHP
17 Providing & erecting approved make AMF control panel suitable 1 Ea. 220509.00
for following size of 3 phase, 415 V., 50 cycles, A.C. diesel
generating set complete of scope as detailed below:
1) Power module: A pair of electromechanically interlocked
contactors (for mains & generator) Overload relay for generator
contactor Neutral contactor for mains and generator Power socket
for connections.
2) Control and metering module: Line voltage monitor. Generator
voltage monitor Ammeter 3 items attempt start facility. Air circuit
breakers/MCB/MCCB of suitable rating for auto/manual operation.
Auto/manual switch. Emergency stop push buttons. Manual start
push button. frequency meter. Engine hour meter. Two earthing
3) Protection module: The engine shutdown in the unlikely event of
Low lube oil pressure High cylinder head temperature. V belt
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency stop
battery charger.
The AMF Panel of following capacity
AMF Control Panel for200 KVA/250 KVA3 phase DG Set
18 Providing & erecting approved make ATS panel suitable for 1 Ea. 90679.00
following size of 3 phase, 415 V., 50 cycles, A.C. diesel generating
set complete of scope as detailed below:
1) Power module: Motorised Changeover switch with ATS
controller, Auxiliary contactor with NO & NC contacts with
Automatic Battery Charger, indicating lamps for Generator ON,
Mains ON, Load and suitable control terminals and power
terminals with neutral earthing studs.
ATS Panel for 180 / 250 KVA 3 phase DG Set
19 Supplying and erecting Acoustic enclosure (canopy) made out of 1 Ea. 262205.00
18 SWG, CRCA Sheet, sound absorbing material Rockwool of
density & 100 mm thick conforming to IS:8183 The resin bonded
Rockwool / PU FOAM covered from inside level not more than
dB at a distance of 1 mtr, as PVCT norms , on provided foundation
suitable for following size of DG Set. The enclosures for
following capacity of DG sets.
For for 160/180/200/250 KVA
D CABLES & TERMINATION
20 Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable 100 Ea. 891.00
multistrand Aluminium conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench / pipe of following size
3 1/2 core 185 Sq. mm ( 95 Sq. mm 1/2 core)
21 Providing and erecting 18 G. M.S. termination box outdoor type 1 Ea. 899.00
suitable for- 1.1 KV PVC insulated armoured cable complete
erected with clamp, bolts, nuts etc. suitable of following size of
22 Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper 500 Mtr. 733.00
cable 1.1 KV grade to be erected as directed of following size.
23 Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper 100 Mtr. 236.00
cable 1.1 KV grade to be erected as directed of following size.
(K) 4 core 4 Sq. mm
24 (L) 4 core 6 Sq. mm 50 Mtr. 359.00
25 (M) 4 core 10 Sq. mm 300 Mtr. 565.00
26 (N) 4 core 16 Sq. mm 300 Mtr. 717.00
27 Providing & laying approved make Double walled corrugated 100 Mtr. 95.00
pipes (DWC) of polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same material at required
depth for laying of cable. below ground / road surface for
enclosing cable and back filling the same to make ground as per
28 Providing & laying approved make Double walled corrugated 100 Mtr. 136.00
pipes (DWC) of polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same material at required
depth for laying of cable. below ground / road surface for
enclosing cable and back filling the same to make ground as per
29 Making trench in soft soil of suitable width of 90 cms deep for 100 Mtr. 55.00
laying cable or locating the fault all over the run and backfilling the
same and making the surface as normal ground.
30 Providing and, fixing heavy duty flange type brass cable gland with 10 Ea 33.00
rubber ring for PVC insulated armoured cable complete with out
going tails, insulating tape etc for following size of cables.
(a) 2 to 4 core 2.5 Sq. mm
31 (b) 2 to 4 core 6 Sq. mm 4 Ea 38.00
32 (c) 2 to 4 core 10 Sq. mm 10 Ea 38.00
33 (d) 2 to 4 core 16 Sq. mm 10 Ea 47.00
34 Providing and, fixing heavy duty flange type brass cable gland with 8 Ea 236.00
rubber ring for PVC insulated armoured cable complete with out
going tails, insulating tape etc for following size of cables.
3 & 1/2 core 185 Sq. mm
35 Solder less crimping type Aluminium lugs conforming to IS suitable 24 Ea 80.00
for cable of following size evenly crimped with high pressure tool &
connected to switchgear terminals with brass/cadmium plated nut
bolts in an approved manner.
36 Solder less crimping type Aluminium lugs conforming to IS suitable 8 Ea 40.00
for cable of following size evenly crimped with high pressure tool &
connected to switchgear terminals with brass/cadmium plated nut
bolts in an approved manner.
37 Solder less crimping type Copper lugs conforming to IS suitable for 56 Ea 8.00
cable of following size evenly crimped with high pressure tool &
connected to switchgear terminals with brass/cadmium plated nut
bolts in an approved manner.
40 Providing and Fixing Cable connection Junction Box for cable 7 Ea 10340.00
connection for Sub-mersible cable, made from CRC sheet with
input and output connector as requried of requried capacity havnig
size of approximate 600 x 600 x 150 duly painted with one coat of
red oxide and two coat of epoxy paint
D EARTHING WORK
41 Maintenance Free Chemical Earthing 10 Ea. 8551.00
Supplying & erecting earth pit of minimum bore dia.150mm size
approved make Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of corrosion free hot dipped
G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron
galvanising, Inner pipe dia of 25 mm having 200-250 Micron
galvanising, connection terminal dia of 12mm with constant ohmic
value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications with chamber
and heavy duty cover. (A)(approved make OEM has to submit test
certificate including value of earth resistance of installation duly
stamped and signed by agency and officer Incharge has to ensure
the value of earthing resistane mentioned in test Certificate) &
having back filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-
2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar
content:- <2%(C) Back fill Compound :- Earthing compound should
be capable to retain moisture for long time ecessary test report
must be submitted by Agency.
(c) For Electrical Installation covering Transformer Neutrals,
Lightning arrester Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e independent Earthing in
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of 25 Kg.
42 Providing and erecting required size HOT deep Galvanised iron 600 Kg 77.00
strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board,
Motors etc. using proper clamp.
43 Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 50 Kg 77.00
44 Providing one bag of 25 Kg. Additional Back Filling Compound (BFC) 10 Ea. 700.00
suitable for safe earthing device.
45 Mains with ISI marked, 1.5KV grade electrolyte multi stranded, 50 Mtr. 56.00
annealed copper conductor with heat resistant PVC insulated
conforms to IS 694, IEC - 227 erected in existing pipe of following
size with required size of copper lugs, nuts and bolts if required.
(e) One wire 6.00 sq. mm
(f) One wire 10.00 sq. mm 100 Mtr. 91.00
(g) One wire 16.00 sq. mm 20 Mtr. 141.00
46 Point wiring for Light / Bell with 2-1.5 sq.mm & earthwire of 1.5 6 Pt 415.00
sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC
insulated multistrand copper wires, in following type of pipe to be
erected concealed in/ on surface on wall/ceiling complete with 6A
Modular type switch / bell push & accessories and earth continuity
of following type, erected on PVC / Metallic box, single mounting
base frame covered with textured/metallic front plate modules
erected on / in wall / ceiling as per pipe erected, with necessary
Lamp holder/ceiling rose / H.D.Connector as directed.
(a) with medium class Rigid PVC pipe and accessories Cat- III
47 Point wiring for FAN with 2-1.5 sq.mm & earthwire of 1.5 sq.mm 10 Pt 593.00
(Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated
multistrand copper wires, in following type of pipe to be erected
concealed in / flushed on wall/ceiling complete with 6A Modular
type switch and hum free EME four or more step type electronic
fan regulator with separately mounted and accessories with earth
continuity of following type erected on PVC / Metallic box, single
mounting base frame covered with textured/metallic front plate
modules erected on / in wall / ceiling as per pipe erected. with
necessary ceiling rose / H.D.Connector as directed.
(a) with medium class Rigid PVC pipe and accessories Cat- III
48 Point wiring for Individual Plug with & earthwire of 1.5 sq.mm 2 Pt 441.00
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires, in following type of to be erected
concealed in / on surface of wall / ceiling complete with Modular
type switch & 5 pin Plug erected on PVC / Metallic box covered
with appropriate front plate modules erected on / in wall / ceiling
as per pipe erected with following type of accessories.
[I] For 6A Plug with 2-1.5 sq.mm Cu. Wire
(a) with medium class Rigid PVC pipe and accessories Cat- III
49 Point wiring for Individual Plug with & earthwire of 1.5 sq.mm 4 Pt 782.00
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires, in following type of to be erected
concealed in / on surface of wall / ceiling complete with Modular
type switch & 5 pin Plug erected on PVC / Metallic box covered
with appropriate front plate modules erected on / in wall / ceiling
as per pipe erected with following type of accessories.
[III] For 16A Plug with 2-4 sq.mm Cu. Wire
(a) with medium class Rigid PVC pipe and accessories Cat- III
50 Point wiring for on board Looped Plug with 6A Modular type 2 Pt 239.00
switch & 5 pin socket erected on PVC / Metallic box, single
mounting base frame covered with textured / metallic front plate
modules erected on / in wall / ceiling with following type
accessories Cat. III
51 Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm 1 Pt 525.00
& earthwire of 1.5 sq.mm (green) both are of .ISI marked 1.1 KV
grade FRLS PVC insulated multistrand copper wires, in following
type of pipe to be erected concealed in / flushed on wall/ceiling
,complete with 6A Modular type switches and following type of
accessories erected on PVC / Metallic box, single mounting base
frame covered with textured / metallic front plate modules erected
on / in wall / ceiling as per pipe erected. with necessary
batten/angle holder or ceiling rose or H.D.Connector as directed.
(a) with medium class Rigid PVC pipe and accessories Cat- III
52 Providing following type of Modular Type Accessories mounted 4 Ea 24.00
with pvc / metallic box, single mounting base frame covered with
textured / metallic front plate , modules erected with necessary
connection. As desired by Engineer In charge
(7) Blank Plate Single Cat III
53 Point wiring for secondary light point with 2-1.5 sq.mm & 12 Pt 131.00
earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade
FRLS PVC insulated multistrand copper wires, in following type of
pipe to be erected concealed in / flushed on wall/ceiling, complete
with earth continuity and necessary connection with primary light
with accessories erected on Metal / PVC box covered with 3 mm
thick PC(Polycarbonet) / Acrylic sheet for open / concealed wiring.
with necessary Lamp holder / ceiling rose / H.D.Connector as
Note:- Maximum up to 6 mtrs length, excess will be considered as
Mains for Secondary Point.
(a) with medium class Rigid PVC pipe and accessories
54 Providing and erecting ISI mark Medium class RIGID PVC PIPES of 100 Mtr 33.00
following size complete to be erected on/in wall or ceiling erected
with necessary PVC fittings & Junction boxes fixed with adhesive
solution & Clamps with following dia of pipes, in approved manner
57 Providing & erecting PVC Corrugated Flexible Conduit with 10 Mtr 21.00
required nos. of coupling, PVC bushes, Check-nuts etc. complete of
following sizes.
60 Supplying & erecting UPVC Mini trunking (PVC Casing-n-Capping) 20 Mtr 31.00
having double-locking arrangement with grooves, trunking of size
not below 12.5 mm in height as per IS with accessories of
PVC/Resin polypropylene not below 1.8 mm thick duly sealed in
joint & erected on wall / ceiling of following size .
61 Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded 10 Mtr 82.00
Copper conductor wire in following type of pipe to be erected
concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper
conductor FRLS PVC insulated stranded wire of green colour for
earth continuity of following size
(a) with medium class Rigid PVC pipe and accessories
(a) 3 wire 1.5 sq. mm
62 (b) 3 wire 2.5 sq. mm 200 Mtr 101.00
63 Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded 50 Mtr 139.00
Copper conductor wire in following type of pipe to be erected in /
on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC
insulated stranded wire of green colour for earth continuity of
(d) 3 wire 4 sq. mm
64 Supplying and erecting Flexible PVC insulated multistrand 25 Mtr 106.00
multicore 1.1 kv grade ISI marked copper wires of following size to
be erected as directed.
i) 2.50 Sq.mm 4 core round PVC sheathed
65 k) 4.0 Sq.mm 4 core round PVC sheathed 25 Mtr 175.00
LAMPS AND FITTINGS
66 Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 16 Ea 370.00
Watt to 0.5 Watt assembled on single MCPCB, with housing used
as a heat sink shall be made of thick sheet Steel conforming to IS:
513/CRCA/ aluminium die cast powder coated and high U.V. &
corrosion resistance with diffuser with company mark/name 160V
to 270V, Power Factor more than 0.95, THD < 15%,CCT 3000 K to
6500K, Luminaire efficacy> 85 lumens/watt ,LED LED driver
efficiency > 85 %( fitting required LM-79 & LM-80
Certificates)(NOTE: Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select
any wattage capacity between the ranges shown.)
(A) Tube Light with integral driver
(iv) 22-24 Watts, Surge - 2KV,IP-20, conventional 4 feet
67 Providing and erecting decorative wall bracket fittings complete 2 Ea 1696.00
with LED lamp and rust free fittings components mounted in
chrome finish housing with holder ,clear/opaque glass diffuser
complete erected with lead wires with minimum 15 wattage
capacity as per instruction engineer incharge/architect/authority
SWITCHGEARS AND DISTRIBUTION BOARDS
68 Miniature circuit breaker single pole 6A to 32A suitable to operate 18 Ea 111.00
on 240 V A.C. system and having breaking capacity 10 KA to be
erected in existing box. confirming to IS 8828/1996 with ISI Mark
69 Providing & erecting 240 V MCB double pole switch for lighting 1 Ea 276.00
Load (B Curve) having 10 KA breaking capacity & confirms to IS :
8828 in existing box having following capacity
(A) 6 to 32 Amp. Cat. III
70 Providing & erecting 415V MCB Four Pole Switch for Lighting Load 1 Ea 573.00
(B curve) having 10KA breaking capacity & confirms to IS :8828 in
existing box having following capacity
(a) 6 to 32 Amp. Cat. III
71 (b)40 Amp. Cat. III 1 Ea 632.00
72 Providing & erecting 415 V MCB Four Pole for Motor & Inductive 1 Ea 730.00
Load (C Curve) having 10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
(c)63 Amp. Cat. III
73 Providing and erecting Sheet Steel powder coated MCB distribution 1 Ea 3379.00
board - flush / surface mounted fitted with busbar, neutral link,
earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 &
without MCB to house appropriate nos. of MCBs.(The DBs should
be used of same company of MCB to be used) suitable for
(B) three phase incoming and single phase horizontal type outgoing
Per phase isolation type (PPI)
(b) sheet steel double door
74 Supplying & erecting Sheet Steel powder coated Cable end 1 Ea. 683.00
termination Box to be mounted on Top or Bottom of the MCB
Distribution Box for housing/covering Extra wires & Cables, suitable
for following size of MCB DB Box. (G) Three Phase 8 Way
75 The Above all items of MCB, DB the cost of erection on New angle 1 Ea 246.00
iron frame add following.
[B] above single phase 8 way and all three phase DBs.
76 Approved make ELCBs / RCCBs conforming to IS: 12640 and having 3 Ea 1950.00
sensitivity of 30 mA and Short Circuit withstand capacity of 6 KA
and suitable for operation on single phase 240 V. having
characteristic of quick action & tripping with all advance feature &
do not incorporate any electronic component. for following Max.
rating erected as directed
(i) 25Amps. DP Cat III
77 (ii) 40Amps. DP Cat III 1 Ea 2213.00
78 Providing & erecting Medium Voltage Danger Notice Board sticker 2 Ea 26.00
of standard size
FANS & ACCESSORIES
79 Providing & erecting Approved make Power Saving 50 Watt Ceiling 10 Ea 1929.00
Fan with double ball bearing ISI mark with Condenser 230 volt A.C.
50 Hz 1200 mm sweep complete having 3blades with aluminium
blades with , canopy & 30 cms. down rod erected with 24/ 0.2,
core flexible wire with earthing.(Make shall be approved by
Engineer in charge))
80 Supplying and erecting 19 / 20 mm. nominal bore Medium Class 10 Ea 107.00
M.S. Pipe down rod erected duly painted for fan complete with
necessary 24/ O.20, 3 core flexible wire with earthing.
81 Supplying & erecting Fan Hook of 10 mm M.S. Round bar grouted 10 Ea 43.00
in RCC slab with Making the site as original.
82 Supplying & erecting fan hook box of 10 mm M.S. round bar 10 Ea. 107.00
bounded to the RCC bars up to 50mm length each side and pierced
through a 16 Gauge M.S. box / Heavy Duty PVC box complete
erected concealed in Ceiling with necessary finishing.
83 Providing Fan clamp of 30 x 5 mm flat of required length & 10 mm 10 Ea. 98.00
M.S. Bolt & Nuts erected with necessary hook of 10 mm M.S.
84 Providing 2.5mm.thick laminated acrylic sheet to cover the fan 10 Ea 18.00
hook or Fan box.
85 Supplying & erecting approved make low noise decorative exhaust 1 Ea 1687.00
fan having size 200mm with 1350 RPM with square frame ABS
body with inbuilt lowers & square frame.
86 Supplying & erecting single phase approved make industrial 6 Ea 3306.00
exhaust fan suitable for medium duty ring mounted low noise
operation suitable for medium duty having following dia size and
maximum speed in RPM
[D] 450 mm dia 900 RPM Cat.II
87 Providing suitable M.S. louver shutter of the Exhaust fan. 6 Ea 365.00
88 Supplying & erecting electro galvanised G.I. wire micro mesh jali 4 Sq.Mtr 628.00
cover of grade 304 required size with suitable wooden frame duly
fitted in wall outside of exhaust fan for insect protection.
89 Providing recess in wall or window frame suitable for erection of 6 Ea 188.00
Exhaust fan complete with plastering and colour washing to match
the colour of the wall or window complete with expanded metal in
order to render the fitting in accessible and the room water-proof.
90 Providing window frame suitable for erection of Exhaust fan 6 Ea 171.00
complete covering the remaining portion of window with 15 mm.
thick plywood and colour washing to match the colour of the wall.
91 Supplying and erecting approved make oscillating type bracket fan 1 Ea 2509.00
A.C. 23OV. 50cy/s 400/450 mm sweep wall mounted with height
adjustment and rotary tilting device complete with guard, flexible
Core plug top complete erected with lead wires as directed. Cat II
COMPREHENSIVE MAINTENANCE FOR 5 YRS
COMPREHENSIVE MAINTENANCE FOR 5 YRS AS
PER ATTACHED SHEET
TOTAL WITH O & M
Amount Put to Tender
PART – B COPREHENSIVE OPERATION AND MAINTENANCE
Sr. Total Daily Total Total Amt in
Desription KUB Power Day
No. Shift Rate Rate Rs.
Plant / Pump Operator
Semi Skilled person.
( 1 person x 3 Shift = 3 Person per
day) (June-November)
Plant / Pump Operator
Semi Skilled person.
( 1 person x 1 Shift = 1 Person per
day) (December-May)
Total Manpower cost for 01 Year of
A Total cost for 01 Year - A
B Insurance / P.F Approx @13% of - A
C E.S.I Approx @3.25% of - A
D Bonus @ 8.33% of -A
E Employee RC @ RC Rs.200/-
F Total Manpower cost for per Year
Contractor Profit approx @ 3.85% for 1st year(minimum service charges in the procurement of
Manpower As per GeM)
Total amount for 1st Year(A+B+C+D+E+F+G+H)
Total amount for 1st Year(A+B+C+D+E+F+G+H)
Pumping Station Name Total Amt in Rs.
I Capital Cost of pumping station
As Per Technical Sanction of 02 pumping station, machinery Cost
Grand capital cost of Two pumping station
Cost for Comprehansive work As per GWSSB @ 5 % of Capital cost - I
Contractor profit As per CPWD @ 15 % of - J
Section - B Total Cost for Comprehansive work (I+J)
Grand total of section-A and section-B(I+J)
Grand total of section-A and section-B(I+J)
Total Base amount for 2nd year
Price escalation in min wages & O&M cost approx @ 10% for 2nd year
Total amount for 2nd Year
Total amount for 2nd Year
Price escalation in min wages & O&M cost approx @ 10% for 3rd year
Total amount for 3rd Year
Total amount for 3rd Year
Price escalation in min wages & O&M cost approx @ 10% for 4th year
Total amount for 4th Year
Total amount for 4th Year
Price escalation in min wages & O&M cost approx @ 10% for 5th year
Total amount for 5th Year
Total amount for 5th Year
Total Amount of 5 Year
Total Amount of 5 Year
Total Amount of 5 Year Say
Total Amount of 5 Year Say
Amount In words :- Sixtyone lakh Eightythree Thousand One Hundred Only/-
1. The bid is percentage rate bid for Supply, Installation, Testing and
Commissioning of Pumping Machinery with allied Electro-Mechanical works with
Operation & Comprehensive Maintenance, and Defect Liability Period for 2 Years
2. The rates and prices shall be submitted in the formats given in the online
and the Bids will be disqualified.
3. It will be entirely at the discretion of the Employer to accept or reject the
bidder’s proposal, without giving any reasons whatsoever.
for items listed in the online schedule. Prices quoted in online Schedule only will
be considered for price evaluation & shall form a part of the Contract Agreement.
the successful bidder.
6. The bidder shall be deemed to have allowed in his price for provision,
maintenance and final removal of all temporary works of whatsoever nature
required for construction including temporary bunds, dewatering, diverting
water, pumping, providing civil foundation, required civil modification,
rectification, finishing work etc. to complete the Electro-Mechanical works. The
rates shall also be deemed to include any works and setting out that may be
required to be carried out for the same.
7. Where there is a discrepancy between the unit rates and the amount
Contract, the Specifications and other sections of these bid documents and
these documents are to be taken as mutually explanatory of one another.
9. Prices quoted by the bidder shall be firm for the entire period of Contract without
any escalation.
10. The bidder shall interpret the data furnished and carry out any additional study,
investigation or planning required to execute the work shall be at his own cost.
11. The prices quoted shall also include the cost of testing and materials utilized
12. The bidder should acquaint himself with the site conditions including the access
to Worksite. The successful bidder shall have to make suitable access to
worksites at his own cost. These accesses will be used by the other contractors
working for RMC.
13. The contractor shall have to avail P.F & E.S.I as per the applicable laws of
Government. The required documents shall have to be submitted by the contractor
to the competent authority.
14. The quoted rates should be inclusive of all taxes and duties.
15. The prices shall have to be quoted firm & fix including all the taxes & duties
without any statutory variation. RMC will not consider any statutory variation as
well as the price rise in the market and if any, those shall be on account of
16. The work contract tax will be borne by the agency.
17. Bidder shall note that RMC shall appoint PMC/TPI agency for supervision of this
work and fees pertaining to same shall be borne by RMC.
The Electro-Mechanical equipment and pipes shall be inspected by Third Party
Inspection Agency or RMC engineers, the costs of inspection procedure which
are to be borne by contractor. The Third Party Inspection Agency will be
from any Government undertaking agency like RITES, EIL, CEIL, MACON,
WAPCOS, SGS, etc. approved by RMC / Gujarat Water Supply & Sewerage Board
or such authorities.
Signature of Contractor ADDITIONAL CITY ENGINEER
Rajkot Municipal Corporation
Rajkot Municipal Corporation
Supply, Installation, Testing and Commissioning (SITC) of Pumping Machinery with
allied Electro-Mechanical works with 5 Years Operation & Comprehensive
Maintenance, and Defect Liability Period for 5 Years for Katariya Underbridge.
:: SCHEDULE - A ::
SUMMARY OF COST ESTIMATE FOR Katariya
UB (SITC / CAPITAL COST + O&M COST FOR
(BOQ & RATES FOR EACH AS PER SCHEDULE - B,)
Sr. Location of Estimated Cost of Project, in Rs.
Capital COMPREHENSIV Total
Cost E O&M Cost Amount
Katariya Underbridge,
at Kalawad Road ,Rajkot
GRAND TOTAL, RS.
GRAND TOTAL, RS.
I/We agree to carry out the above work at _ % (In Fig)
( (In words) Equal/Above/Below the
estimated cost.
Contractor shall have to quote their rates in the given online Price
Bid only. Please do not mention percentage quote in physical
AAE/AE Dy.Ex.Engineer Addi. CITY ENGINEER
Rajkot Muni. Corporation Rajkot Muni. Corporation Rajkot Muni. Corporation
Signature of Contractor:
Schedule of Payment % Break-up of payment for each component of the
Pumping Machinery during Supply, Installation, Trial Run & Commissioning.
Sr. No. Break-Up quoted
1. On supply of equipment at site 65%
2. On erection of equipment 15%
3. On testing and commissioning and successful trial run 20%
Any other items not specified above but considered necessary for completion of work to
the satisfaction of Engineer-in-charge and efficient operation of the plant / SPS.
After commissioning the pumping station O & M shall be the responsibility of the
Contractor to run Pumping station / pumping station for 5-years (60 months)
period and after that plant / pumping station should be handed over to the Client
Contractor’s Signature Addi. City Engineer
Rajkot Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Price Bid KUB 1.pdf
Technical Bid KUB 1.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .