Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹16.0 L+₹52,070 (3.37%)Rejected-Finance | L2 | Rejected-Finance HIGHER QUOTED BIDDER | |
| 3 | L3₹16.7 L+₹1.2 L (7.98%)Rejected-Finance | L3 | Rejected-Finance HIGHER QUOTED BIDDER | |
| 4 | L4₹18.2 L+₹2.8 L (18.0%)Rejected-Finance | L4 | Rejected-Finance HIGHER QUOTED BIDDER | |
| 5 | L5₹18.6 L+₹3.1 L (20.3%)Rejected-Finance 77 KAILASH PURI BIKANER RAJ C 15 SWC JAIPUR | BIKANER | RAJASTHAN | 331801 | L5 | Rejected-Finance HIGHER QUOTED BIDDER |
Tender Value
₹23.8 L
EMD Value
₹21,600
Closing Date
13 Jun 2020, 6:00 pmClosed
CWE (AF) JAISALMER
HQ CWE (AF) JAISALMER
REPAIR/MAINT OF TRANSFORMER AND CONNECTED WORK AT AF STN PHALODI.
2020_MES_345170_1
80098/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) PHALODI
Class E Cat b(ii)
7 documents required · 7 mandatory
₹500
GE (AF) PHALODI
₹21,600
Yes
30 Jul 2020
15 May 2020
15 Jun 2020
15 May 2020
13 Jun 2020
30 May 2020
Amount
Servicing maint and repair of functional transformers comprising as under:- (a) Disconnecting of transformers from electrical circuit /pole/plinth mounted out door /indoor type of any make of capacity upto 63 KVA.Opening the top cover for carry out repair at site and replacement of defective parts. (b) Draining out transformer oil complete removing sludge/carbon particles from bottom core & coils, washing core using drained transformer oil. (c) Reassembling of top cover and reconnecting to electrical system, testing and commissioning of transformer complete all as specified and directed. Note :- (i) Refiling, Dehydration and filtration of oil, replacement of parts, gasket will be measured and paid separately under relevant items.
All as per item Ser No.1 above but of capacity exceeding 63 KVA but not exceeding 100 KVA complete all as specified and directed.
All as per item Ser No.1 above but of capacity exceeding 100 KVA but not exceeding 160 KVA complete all as specified and directed.
All as per item Ser No.1 above but of capacity exceeding 160 KVA but not exceeding 300 KVA complete all as specified and directed.
All as per item Ser No.1 above but of capcity exceeding 300 KVA but not exceeding 500 KVA complete all as specified and directed.
All as per item Ser No.1 above but Isolation transformer of capcity exceeding 63 KVA but not exceeding 300 KVA complete all as specified and directed.
Dehydration, filtration, heating and refilling of old transformers oil after testing the same for dielectric strenghth not less than 45 KV (RMS) complete all as specified and directed. Note:- (i) Dehydration and filtration can be carried out at site by brining filtration machine at site otherwise the same shall be got done from the manufacturing workshop of transformers/stablizer.
Supply and top up of transformer oil HV grade having electric stength not less than 45 KV (RMS) at 4mm gap. High viscosity in transformer conforming to IS-335 of 1983 as amended complete all as specified and directed . Make: HP, BPL, IOC
Supply and replacing and testing of externally operated tap changing gear off load type on HV winding to vary the LV voltage upto 7.5 % variation limit in steps on 2.5% suitable upto 250 KVA transformer complete all as specified and directed.
All as per item No: 09 above but capacity 300 KVA to 500 KVA complete all as specified and directed.
Supply and replacing of Ceramic Bush insulators with brass spindle complete with washers, nuts and check nuts on HT side as per existing size, shape and specification for 11/0.433 KV transformer (outdoor/indoor) type transformers of capcity not exceeding 250 KVA complete all as specified and directed.
All as per Item Ser No.11 here in before but capcity 300 to 500 KVA complete all as specified and directed.
Supply and replacing of Ceramic Bush insulators with brass spindle complete with washers, nuts and check nuts on LV side as per existing size, shape and specification for 11/0.433 KV transformer (outdoor/indoor) type transformers of capcity not exceeding 250 KVA complete all as specified and directed.
All as per item Ser No. 13 here in before but capacity 300 KVA to 500 KVA complete all as specified and directed.
Supply and replacing cork sheet gasket (set of four) for ceramic bushing on LT side as per existing size, shape and specification complete for capcity not exceeding 250 KVA 11/0.433 Volts transformers complete all as specified and directed.
All as per item Ser No.15 here in before but capacity 300 KVA to 500 KVA complete all as specified and directed.
Supply and replacing of cork sheet gasket of 6 mm thick out to size/shape for top cover of transformer upto capacity 250 KVA complete all as specified and directed.
All as per item Ser No: 17 above but transformer of capcity exc 300 KVA and upto 500 KVA complete all as specified and directed.
Supply and replacing of silicagel breather assembly of metallic body including silicagel for distribution transformer of capcity not exceeding 250 KVA complete all as specified and directed.
All as per item Ser No. 19 here in before but capacity 300 KVA to 500 KVA complete all as specified and directed.
Supply and replacing of temperature gauge 0 to 150 degree celsius as per existing dia at site suitable for 11/0.433 KV transformer complete all as specified and directed.
M&L painting of transformers externally spray painting with synthetic enameled paint of gray color after cleaning surfaces thoroughly with thinner and scrapper and preparing the surface to required standard including writing and marking such as MES No on the body of transformer capacity upto 200 KVA including colour wash of transformer plate and replace oil level indicator of same type complete all as specified and directed.
All as per item Ser No 22 above but capacity 250 KVA to 500 KVA complete all as specified and directed.
M&L for rewinding of HV coil of transformer of any capacity using proper size DPC super enameled copper winding wire of appropriate guage and grade,with insulation material suitable for HT 11 KV transformer including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. Make: Emco/Milan
Re-insulation of HT coil of transformer of any capacity using proper size paper insulation material to form DPC Copper wire and HT insulation material suitable for 11/0.433 KV transformer complete all as specified and directed. (Note : Item shall be measured only where re-insulation of copper wire is required.)
M&L for rewinding of LV coil of transformer of any capacity using proper size DPC super enameled copper winding wire of appropriate guage and grade, and insulation material suitable for 11/0.433 KV transformer including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. Make: Emco/Milan
Re-insulation of LV coil of transformer of any capacity using proper size paper insulation material to form DPC Copper wire and LT insulation material suitable for 11/0.433 KV transformer complete all as specified and directed. (Note : Item shall be measured only where re-insulation of copper wire is required.) Note for Item No 24 to 27 :- (a) Rewinding of transformer HV/LV Coils shall be carried out from ISO certified 2008 Coy. (b) Dehyderation and filteration of transformer oil, and replacement of unserviceable spares shall be measured and paid seperately under appropriate Item of schedule however cost of renewal of Nut, bolts & washers shall deemed to be included in UNIT RATE QUOATED.
M&L in replacement for Earthing complete with galvanised steel earth plate electrode 60 X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and inclduing GI Strip 32x6 mm as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 3 of MES SSR Part I and testing on completion inclduing excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, and cover 6 mm thick in cement concrete (1:2:4) type B1, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed with earth resistance not more than 1.0 OHMS. Note:- (i) In case earth resistance valve is more than 5.0 ohms while initial testing, the contractor wiil re-execute the earthing at no extra cost. (ii) The earthig lead i.e 32x6 mm GI strip from electrode onwords shall be suitably protected by 40 mm GI pipe light grade of 7 meter length and suitable GI testing clamp of size 32x6 mm in to be fixed on wall for regular testing of earthing valve.
M&L in replacement for Earth continuity conductor or main earthing lead fixed to walls on batten or recess or chases or burried in ground or drawn in conduit/pipes or fixed to poles or any other indicated situation for loop earthing etc as required 32X6mm galvanised iron strip complete all as specified and directed.
S&F in replcement of vertical type air break switch gang operated, tripple pole, mechnically operated, outdoor type, with all fittings and accessories mounted on and including HT 11 KV porcelain insulators and steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements , suitable for 11000 volts, 400 Amps current rating complete including dismantling existing one complete all as specified and directed. Make :-MEI/Pactil/Atlas/Jaipuria
S&F in replcement of drop out fuse unit, explusion type for out door air break gang oprated switch, single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts and washer etc synthetic bounded fuse tube complete with line capcity suitable for current carrying capacity upto 100 Amps all as directed including taking down old one all as specified and as directed. Make:- MEI/Pactil/Atlas/Jaipuria
S & F in replacement lightning arresters suitable for 11000 Volts, non-linear type complete with all fittings, transmission class, discharge capacity 65 KA complete all as directed. Make :- Bhel/Areva/Oblum/Jaipuria
M&L in replacement for cross arms bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint.
Supply and replace Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable . Including cutting and removing existing unserviceable joint, excavation near 2/4 pole structure / HT Panel board / Transformer and taking out loop cable from trench and excavation refilling the trench shall deemed to be included in quoted rate with excavated material complete all as specified and directed. Make :- M-Seal/Y-Denson/Raychem RPG
Supply and replace Cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2/4 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material complete all as specified and directed. Make :- M-Seal/Y-Denson/Raychem RPG
Supply and replace Cable end jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2/4 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material complete all as specified and directed. Make :- M-Seal/Y-Denson/Raychem RPG
Disconnecting / dismantling primary & secondary (HT/LT) connection carefully of unservicable / serviceable out door / indoor type Transformer complete of any capacity from its foundation and safely shifting one sub station to another sub station where as directed by Engr-in-charge and reconnection of cabling ,earthing ,install testing and commissoning of the transformer complete all as specified and directed. Note:- Cost of Necessary tools and plants such as Vehicle, hydra/Crane etc should be deemed to be included in the unit rate quoted.
MORESHWAR ELECTRICALS CORPORATION
star electricals
Nvimal Engineer and Contractor
M/S SOLANKI GENERAL SUPPLIERS
Hariom Construction Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .