Tender Value
₹7.6 L
EMD Value
₹14,500
Closing Date
27 Nov 2023, 12:00 pmClosed
Executive Engineer EDD Kargil
Baroo Kargil
Creation of 63 KVA Sub- Station along with HT/ LT Line at Chonmo Mohallah Zanaskar
2023_PDNRE_11899_1
E-NIT NO 78 of 2023-24
Open Tender
Electrical Works
Turn-key
30 days
ZANASKAR KARGIL
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
Account No 0096010200000064 IFSC Code JAKA0KARGIL
₹14,500
29 Nov 2023
21 Nov 2023
28 Nov 2023
21 Nov 2023
27 Nov 2023
25 Nov 2023
Amount
Creation of Sub-Stations Supply,Installation,Testing & Commissioning of
11/0.433kV, 3-phase 63 kva Distribution Transformerswith Bimetallic Terminal Connectors Energy Level-2,
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
95Sqmm (or 70Sqmm (2Ckt)/150Sqmm (or 95Sqmm (2Ckt)/300Sqmm (or 185Sqmm (2Ckt) Cable,1.1KV Grade,XLPE Insulated stranded conductor FRLS type.
9 Mtr. Long Pole,ST-410 SP56)
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative,creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,GO Set & Lightening arrestors as per IS 2629/85,GI nuts & bolts,refilled with earth enhancement materials & earth chamber made of bricks masonary with RCC Slab Cover.
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
LT Distribution box for 250KVA DTR with MCCB for incomer and SFU's for outgoing circuits
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards .5cum/pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Sundry items like aluminium lugs, Jumpers,binding Tape,
Construction of HT Line Supply,Installation,Testing & Commissioning of
SITC of 9 Mtr. Long Pole( ST-410 SP33)
SITC of GI V cross-arm/Channel with top Bracket including clamp suitable for 33KV Pin & Disc insulators(as per drawing & sample available with Divisional stores)
SITC of 30 mm² ACSR Conductor
SITC of PG Clamps for 30 mm² ACSR Conductor
SITC of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
SITC of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative,creepage distance 900mm
SITC of Galvanized Nuts and Bolts
SITC of Danger Plates with Clamps
SITC of Anti-Climbing Device with Clamps
SITC of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
SITC of Red Oxide
SITC of Aluminium Paint
SITC of Cement bottoming 1:2:4 mix as per REC standards .5cum /pole
Construction of LT Line Supply,Installation,Testing & Commissioning of
SITC of 8 Mtr. Long Pole( ST-410 SP33)
16 KN Polymer Shackle/Pin Insulator
M/S KHADIM HUSSAIN
M/S TASLA ENGINEERING WORK
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .