Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-AOC SIMURALI NADIA | PURBA BARDHAMAN | WEST BENGAL | 713502 | L1 | Accepted-AOC AOC | |
| 2 | L2₹12.6 L+₹63,598 (5.33%)Rejected-Finance | L2 | Rejected-Finance Rejected as L2 | |
| 3 | L3₹12.9 L+₹1.0 L (8.45%)Rejected-Finance 30 2 RAJKUMAR MUKHERJEE ROAD KOL 700035 | KOLKATA | KOLKATA | WEST BENGAL | 700035 | L3 | Rejected-Finance Rejected as L3 |
Tender Value
Refer Docs
EMD Value
₹23,500
Closing Date
24 Jul 2024, 1:00 pmClosed
Executive Engineer
District Hospital Campus Shaktinagar Krishnanagar Nadia
EI at DSF Fulia between WBSEDCL Meter room to newly constructed multipurpose building at Dist Seed Farm Fulia Nadia
2024_WBPWD_710908_1
WBPWD/EE/NED/ NIQ/e-T/04/ (2nd Call)24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
District Hospital Campus Shaktinagar Krishnanagar
Please refer Tender documents.
5 documents required · 5 mandatory
₹23,500
3 Apr 2025
10 Jul 2024
26 Jul 2024
10 Jul 2024
24 Jul 2024
10 Jul 2024
Amount
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] Average Run -- 8 Mtr. [ 5(c)/E-15 ]
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 5A 3 pin plug point incl. S&F 240 V 5A 3 pin flush type plug socket & piano key type switch (Anchor make) incl. S&F earth continuity wire, fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish. On Board [ 4(a)/(i)/E-10 ]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [ For 6A S.P. ] [ 1(a)/(i)/E-14 ] As per choice of EIC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [ For 16A D.P.P. & Outdoor LED ] [ 1(a)/(ii)/E-14 ] As per choice of EIC
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC [ For SPNDB ] [ 1(a)/(iv)/E-14 ] As per choice of EIC
Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick as per GS. [ 21/E-6 ] [ 6 A S.P. ]
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick as per GS. [ 22/E-6 ] [ 16 A D.P.P. ]
Supply & Fixing 240 V, 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board incl. S & F 100x100x65mm MS (16SWG) switch board and bakelite/ perspex top cover of 3mm thick as per GS. [ 17(b)/E-6 ]
Supplying and fixing 415V, 400A TPN SFU on angle iron frame TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.( Make - L & T ) [ 4(a )/D-3 ] [ For Meter Room ]
Supplying and fixing 415V, 415 A TPN on load front operated Changeover switch open execution type in SS enclosure/ cubical with nuts bolts etc
Supplying and fixing 415 A cable end Box sheet steel (16SWG) cable end box on TPN SFU enclosure with nuts bolts etc incl. powder coated painting.[ 5/D-5 ]
Supplying and fixing (2+6) Way Enclosure (607711) double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall as per GS. (2+6) Way Enclosure (607711) [ Make - Legrand ] [ 13/D-9 ]
(2+10) Way Enclosure (607712) [ Make - Legrand ] [ 13/D-9 ]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages as per GS. 4 Way Enclosure ( 607715 ) [ Make - Legrand ] [ 14/D-10 ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs as per GS. -- 6-32 A SP MCB [ Make - Legrand ] [ 7/D-6 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs as per GS. -- 40 A DP Isolator [ Make- Legrand ] [ 6/D-5 ]
63 A FP [ Make - Legrand] [ 6/D-5 ]
Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works. 19 mm dia 3 mm thick polythene pipe without earth continuity wire. [ 3(a)/ E-2 ]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required as per GS -- 25 mm. size [ 7(b)/E-16 ]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required. 3 x 22/0.3 (1.5 sqmm) [ For 6A S.P. ] [ 1(b)/E-9 ]
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) as ECC [ For 16A D.P.P. & Outdoor LED ] [ 1(s)/E-9 ]
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) as ECC [ For SPNDB ] [ 1(y)/E-9 ]
4 x 126/0.4 ( 16 sq mm ) + 2 x 80/0.4 ( 10 sq mm ) ECC. [ 1(g1)/E-9 ] [ For TPNDB ]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes as per GS. 2.5 Sq mm [ 9(i)/ F-5 ]
4 Sq mm [ 9(ii)/ F-5 ]
6 Sq mm [ 9(iii)/ F-5 ]
10 Sq mm [ 9(iv)/ F-5 ]
16 Sq mm [ 9(v)/ F-5 ]
Supply & Delivery of 2 Core PVC/XLPE Insulated & Sheathed Armoured Aluminium Conductor Cables for Working Voltage up to 1100 Volts of following sizes. [ Make Polycab/Gloster /Havells] Testing Certificate from manufructural authority and as per derection of EIC. 2 core 10 Sq mm. cable. [ NS ]
Supply of 4 Core PVC/XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes. [ Make - Polycab/Gloster/ Havells ] Testing Certificatefrom manufructural authority and as per derection of EIC. 4 core 16 Sq. mm Cable. [ NS ] [ For 2 Nos. Pump House ]
4 core 95 Sq. mm Cable. [ NS ] [ From Meter Room LT Panel to I/N of LT Panel of Multipurpose Seed Godown) ]
4 core 120 Sq. mm Cable. [ NS ] [ From Meter Room LT Panel to I/N of LT Panel of Main office Green building ]
4 core185 Sq. mm Cable. [ NS ] [ From Meter Room to I/N of Main LT Panel of Panel Room ]
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as per GS. -- [ 2(a)/F-1 ] [ For 2 core 10 Sq mm. ]
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. [ 2(b)/F-1 ] [ For 4 Core 16 Sq mm. ]
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. [ 2(e)/F-1 ] [ For 4 core 120 Sq mm. ]
Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as per GS. From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. [ 5(i)/F-3 ] [ For 2 core 10 Sq mm. & 4 Core 16 Sq mm. ]
Above 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc. [ 5(iii)/F-3 ] [ For 4 Core 95 Sq mm. 4 Core 120 Sqmm & 4 Core 185 Sq mm. ]
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space as per GS. [ 1(a)/F-2 ] [ For 2 core 10 Sq mm. & 4 Core 16 Sq mm. ]
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space as per GS. [ 1(b)/F-2 ] [ For 4 Core 120 Sq mm. , 4 Core 95 Sqmm & 4 Core 185 Sq mm. ]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry as per GS. 2 core 10 Sq mm. cable gland. [ 7(a)/F-4 ]
For 4 core 10 Sq. mm. [ 7(c) /F- 4 ]
For 4 core 150 Sq. mm. [ 7(c) /F- 4 ]
For 4 core 185 Sq. mm. [ 7(c) /F- 4 ]
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make) as per GS. 2 core 10 Sq mm. cable [ 8(b)/(iii)/F-5 ]
4 core 10 Sq mm. cable [ 8(b)/(xi)/F-5 ]
3.5 core 150 Sq mm Cable. [ 8(b)/(xx)/ F-5 ]
3.5 core 185 Sq mm Cable. [ 8(b)/(xxi)/ F-5 ]
Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. as required. [ 14(d)/C-2 ]
Fixing only lamp. [ 11/C-2 ]
Supply of 4ft LED T-8 box type single batten with end cap complete with all accessories -- Single fiittings [ Make - Phillips, Cat. No - TMC 501 P1XT LED ] [ NS ]
Supply and Delivery of 18W LED T-8 lamp [ Make - Phillips, ( Cat. No - 18W P3241 ) 1200 mm, 2100 Lumen MAS LED tube ] on fittings. [ NS ]
Supply of 9W LED lamp to the lamp point. [ Make - PHILLIPS ] [ NS ]
Supply & Delivery of 240 volt, 25 W ASTRA NEO LED outdoor luminaire on arm bracket. ( Make - Crompton, Cat No - LSTS-25-CDL-M ) /Philips [ NS ] [ For Wall Bracket lights ]
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991) [ 29/D-14 ]
Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc. [ 18/(a)/E-6 ]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. [ 21/(a)/C-3 ]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible as per GS. -- 30 cm. ( 12 '') [ 28(b)/C-4 ]
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) For Aluminum, 30 cm. Exhaust Fan ( 12 '') [ 32(a)/D-14 ]
Supply of ceiling fans complete with all accessories having the following Model / Cat No. [ Make - Crompton Greaves ] 1200 mm Sweep AC Ceiling Fan ( HIGH SPEED ), Colour - White/Dark Brown/ Chocklate [ NS ]
Supply & delivery of Exhaust Fans complete with all accessories having the following Model/ Cat No. [ Make - EPC Heavy Duty ] 12 '' ( 300 mm ), Speed - 920 RPM [ NS ]
Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as per GS. -- [ 18/ C-3 ] [ For Wall Bracket lights ]
Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. where necy. incl. painting. -- 200 x 150 x 100 mm. [ 16(a)/I-2 ]
S & F of Compound Light Timer Control Box with Double door ( 2 + 10 ) Way SPNDB enclosure as per -- ( Make - L&T, Cat no - LTSD12N ) with IP - 42/43 protection, concealed in wall after cutting the wall & mending good the damages incl. interconnection with suitable size of PVC insulated copper wire and neutral link & proviosion for earthing attachment. incl. proper socketting with required size of copper lugs and following accessories -- i) 240/415 V, 16 A DP MCB of Breaking Capacity 10 KA & ''C'' Charecteristics ( Make - L&T ) - 1 nos. ii) 32 A, 3 Pole Power Contactor with 220 coil voltage ( Make - L&T, Cat no - MNX 32 - 3P, CS94111) - 1 nos. iii) Digital Time Switch ( Make - L&T, Cat No - Crono 67DDTO ) -1 nos. iv) One no. Red and One no. Green 240 V LED indicator lamp for indicating purpose of Auto & Bypass indication ( Make -- L&T ) v) Auto/Manuual Toggle Switch -- 1 nos. vi) S & F 4 way terminal lead on existing enclosure over the pvc insulated chairs with necy. nuts, bolts & washers. -- 1 nos. [ NS ]
Dismentling of the existing old wiring incl. existing fittings - fixtures etc. [ NS ]
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling. [ 22/D-13 ]
Supply & Fixing Meter Board on wall by MS angle frame ( 50 mm x 50 mm ) incl. provision for fixing the meter with supply & fixing 250 Volt, 3 Nos. 415 Amp Fuse Base and Bridge incl. Neutra link incl. painting the wooden board as per direction of E.I.C. [ NS ]
Supply & Laing of Meter Loop connection incl. Supply & fixing 4 x 80/ 0.20 ( 70 Sq mm. ) PVC single core stranded copper wire through PVC flexible pipe ( 3 meter. of Length of each Phase wire & Neutral wire i.e. 3 x 4 = 12 Mtr. of total length ) from Meter to Cut - Out and Cut - Out to Incoming of Main Switch with proper socketting by Pin/Ring type copper lugs of required size. [ NS ]
Additional charges for cutting the RCC Road and mending good the damages as to original finish after laying the cable through GI Pipe protection as per size given below -- 40 mm dia GI Pipe [ NS ]
50 mm dia GI Pipe [ NS ]
80 mm dia GI Pipe [ NS ]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. -- 40 mm dia GI Pipe [ 11(c)/F-6 ]
50 mm dia GI Pipe [ 11(d)/F-6 ]
80 mm dia GI Pipe [ 11(f)/F-6 ]
Supply, Installation , Testing & Commissioning of floor-cum-wall mounted CPRI approved Cubical type LT Distribution Panel Board of Self Supporting Compartmentalized with Separate bus & Cable alleys made of 2mm thick CRCA MS (14 SWG)sheet & angle iron frame supported incl. necy. interconnection by suitable size & grade Copper Cable / Solid link/ flat bar incl. making cable end terminal box float boxes after making drill holes ect. as required as per direction of E.I.C. The panel board consisting of the following accessories -- ( MAIN LT PANEL ) -- (A) INCOMING: (i) 415Volt ,630 Amp. FN type TPN Main switch incl. S & F 3 nos. HRC fuses as per rating. ( Make- L&T ) -- 01 Set (B) Bus Bar Chamber:- 415 Volts, 4 Bars Copper B.B.C incl. 4 Nos 1000 Amp capacity Copper Bars of size 4 x ( 2 x 80 x 5 ) mm. on DMC/ porcelain insulator of requisite length incl. drill hole etc. as required and as approved by E.I.C .
( C ) OUTGOING :- (i) 415 Volt, 400 Amp FN type TPN Main switch incl. S & F 3 nos. HRC fuses as per rating. ( Make -- L&T ) -- 01 Set ( ii ) 415 Volt, 160 Amp FN type TPN main switch incl. S & F 3 nos. HRC fuses as per rating ( Make -- L&T ) -- 01 Set ( iii ) 415 Volt, 63 Amp FN type TPN main switch incl. S & F 3 nos. HRC fuses as per rating ( Make -- L&T ) -- 04 Set iv) 415 Volt, 100 Amp FN type TPN main switch (Spare) incl. S & F 3 nos. HRC fuses as per rating ( Make -- L&T ) --01Nos.
( D ) Metering Panel :- (i) S & F Current Transformer of size 600/5A ( Kappa make )- 3 Nos. (ii) LED Multifunction Meters [ ABB make DMTMEI-48596] -- 1 Nos. (iii) LED Indicator [ R,Y,B ] -- 3 Nos. (iv) 3P MCB C6 -- 1 Nos. (v) S & F Danger Notice Board -- 1 Set (vi) Connection with suitable size of Copper wire.
( E ) Painting :- The complete Panel board should be painted by 2 coats of powder coated synthetic enamel Paint over two coats of R.O. primer of Approved make & brand & color as per Direction of E.I.C. ( F ) Constructural Details :- All incoming & outgoing panel mounted cubical Switch disconnector fuse should be housed in Respective compartment with hinged & gasketted Door at front. All doors shall have Panel lock Arrangement. The panel shall be properly Gasketted to prevent ingress of dust & moisture & Remain. Busbar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts On angle /flat iron frame base as per direction of E.I.C.
Cable trenching work should be done for installation of the Panel. The Panel should be installed on the supporting structure made of 10" brick pedestal of required dimension as per the size of the Panel of 600 mm. above the Ground level incl. Sand Cement Plastering and neat cement finishing. Inside the brick pedestal, there will be filled up by loose sand where the incoming & outgoing cable will be in rest for trenching of cable.
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil [ 1(a)/G-1 ]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long)as per GS. By ISI - Medium GI Pipe [ 2(a)/ G-1 ]
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as per GS. -- [ 5(e)/G-3 ]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as per GS. Solid G.I. wire -- No. 4 SWG GI wire. [ 5(a)/(i)/G-2 ]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall as per GS. [ 4(c)/G-2 ]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall as per GS. [ 4(b)/G-2 ]
GEM ENGINEERS CO-OP SOCIETY LTD
M/S. GHOSH ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .