Executive Engineer, GAP-I, EM, KMDA
Office of the Executive Engineer, GAP-I, EM, KMDA, 83 1A Vivekananda Road, 3rd floor, Kolkata-700006
Servicing, overhauling and commissioning of old existing 11 KV Switch Gear along with servicing, dehydration and topping up of insulation oil in 315 KVA,11/0.433 KV Transformer at Natagarh Main Pumping Station under Panihati Municipality.
2024_KMDA_687457_2
18/EE(E/M)/GAP-I/EM/ KMDA/2023-24
Open Tender
Electrical Work/ Equipment
Item Rate
15 days
Panihati Municipality.
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹4,190
Office of the Executive Engineer, GAP-I, EM, KMDA
29 Aug 2024
22 Mar 2024
4 Apr 2024
22 Mar 2024
2 Apr 2024
22 Mar 2024
27 Mar 2024
Amount
Supply & Delivery of Transformer oil grade as per ISI rule.
Dehydration and topping up 315 KVA Transformer oil with dislodging by centrifugation method.
Opening the transformer breather and refitting the same after changing the silica gel including the supply of necessary gasket and silica gel
Repairing ,rectification ,installation & commissioning of Buccholz relay of the Transformer.
Complete Dismantling of all the Mechanical Parts of the HT Switchgear after removing to a workable position in side the substation after dismantling of all the components like rollers, main latch, trip latch, guide rollers main drive, shaft, S.S pin, self spring, ratchet assembly etc, has been properly Overhauling by petrol & grease with replacement of old transformer oil with new one of required BDV after overhauling re-fixed as per existing way for interlocking arrangement, bush, spring etc. replace.
Supply , delivery at site nut bolt, washer, 1.5 sqmm cable and socket as per direction of the EIC.
Supply,replacement of spare parts of HT Switchgear including porcelin spout
Servicing, cleaning and testing, calibration of following relay (for 6 KV Panel/11 KV Panel)For Incomer Feeder: Each relay set consists of following relays MICOM P110 /122/127/ 1 NO. CGL 14N/C- 1 NO VAX31 - 1 NO, VAA-33-1NO VAMP-31 - 1 NO, VAJH-13- 1NO
Supply & fixing of 230/240V, LED indicating lamp (make :AE/KAPPA/IMP) Blue/ white color.
Supply,delivery and Fixing of shunt trip coil.
Complete Panel Wiring by supply & installation of 1.1 KV grade unsheathed copper PVC insulation wire 7/0.029 or 2.5 sq. mm (make : Finolex) laying inside control circuit panel through PVC front cover cable tray with all necessary including numbering, ferules, socketing, crimping joints for measuring instrument relay, power pack from C.T. & P.T. including supply & fixing of 2 nos. push button, 16 nos. 6-10Amps HRC fuse cartridge, binding tape, numbering ferules, flexible PVC pipe etc. The C.T.’s secondary connection should be short circuited & proper ground earth reconnection of H.T. cable terminal joint.
High pressure Testing including Earth measuring.
Necessary checking , Testing & commissioning of Switch Gear along with P.T. circuit including tripping test through all relays, Primary injection through CT & measured secondary current of relays are to be made at site in presence of Electrical Engineer.
D.C.Eng.Co
PASS TREAT
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .