Executive_Engineer_NTKMD_PHED
Utility_Bldg__Beside_Delhi_Public_School_AA_ID_New_Town_Kol_700156
Overhauling of 11KV Breaker and LT panel with allied works at Sub-station of PS-VIII at AA-IIG under NTK Project.
2025_PHED_855141_15
PHE/NTKMD/e-04 of 2025-26
Open Tender
Project Work
Item Wise
30 days
WORK
Please refer Tender documents.
5 documents required · 5 mandatory
₹4,500
26 Nov 2025
30 May 2025
11 Jun 2025
30 May 2025
9 Jun 2025
30 May 2025
Amount
For HT panel : Thorough testing and calibration of 11KV VCB 3 Panel distribution board at site : A) Disconnection of 11KV HT cables. B) Cleaning of entire panel by carbon cleaner to remove all carbon particles. C) Cleaning of all dismantled components to remove all carbon particles and sulphation to improve insulation resistor (IR). D) 11KV Breaker completely servicing, cleaning by CRC & checking of all parts and make it in proper condition. E) Cable and termination to be cleaned by carbon cleaner. F) After servicing of all switch gear & checking its IR with respect to earth and phase to phase, they are racked in service position & kept at ON condition. At this condition High Voltage testing. G) All over current and earthfall relays tested by secondary injection. H) IR value checking of PT & CT. I) Tripping test of Breaker by primary injection. J) After testing all the HT cables (11KV) reconnected for successfully charging of 11KV supply on put on load condition. For LT PDB panel : A) Thorough cleaning of entire PDB panel & lighting. B) Testing & servicing of Air Circuit Breaker C) Testing of all MCCB, SFU, CT etc. D) All tightness checking. For LT MCC panel : A) Thorough cleaning of entire MCC panel & lighting. B) Motor Protection Relay Setting Checking C) Testing of all MCCB, MCB, Contactor, SFU, CT etc. D) Water Level Sensor And Interlocking With Motor Checking E) All tightness checking. For Transformer : IR/PI Value, Ratio checking, Oil lekage, Relay setting and others as per Annexure, changing of gasket to arrest to leakage of oil. For Battery Charger : Thorough Overhauling of battery charger, De-sulpheriztion & maintenance of battery (Report should be submitted as per Annexure I, II, III & IV)
Dehydration & filtration of 2 nos. 11/0.433KV 500 KVA transformer oil of the existing transformer (2 nos. x 550 lt.) =1100 ltrs.
Dielectric strength test as per specification of the IE rules (2 nos. 500 KVA transformer)
Transportation charges of filtration machine (to & fro).
Supply & reflling of Silica gel
N.B. : Within one year after the overhauling if any breakdown will occur, the agency should attend the site within two hours and complete the work within six hours in emergency basis.
GST @18% of Total Value in Amount
CESS @1% of Total Value in Amount
WEST BENGAL ENGINEERING CO. (BID ID -6502844)
ORIENTAL ENGINEERING CO. (BID ID -6504633)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .