Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.6 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹36.0 L+₹2.3 L (6.97%)Rejected-Finance | L2 | Rejected-Finance Being No L1 | |
| 3 | L3₹36.4 L+₹2.8 L (8.37%)Rejected-Finance | L3 | Rejected-Finance Being No L1 | |
| 4 | L4₹38.2 L+₹4.5 L (13.5%)Rejected-Finance D NO 4 96 40 27 FLAT NO 307 GREEN CASTLE APARTMENT GOPALAKRISHNA NAGAR SUJATHANAGAR VISAKHAPATNAM 530 051 | VISAKHAPATANAM | ANDHRA PRADESH | 530051 | L4 | Rejected-Finance Being No L1 | |
| 5 | L5₹40.4 L+₹6.8 L (20.2%)Rejected-Finance D NO 58 22 34 9 PYDIMAMBA NILAYAM BUTCHIRAJUPALEM VISAKHAPATNAM 530 027 | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | L5 | Rejected-Finance Being No L1 |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
24 Nov 2022, 6:00 pmClosed
GARRISON ENGINEER I DOCKYARD MAINT NAVAL DOCKYARD
GARRISON ENGINEER I DOCKYARD MAINT NAVAL DOCKYARD VISAKHAPATNAM
REPAIR REPLACEMENT OF UNSV SPARES OF 11KV VCBS AND ALLIED WORK AT DRY DOCK AREA SUBSTATIONS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM
2022_MES_561229_1
SSGE/8754/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAVAL DOCKYARD VISAKHAPATNAM
As per tender documents
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER I DOCKYARD MAINT NAVAL DOCKYARD
₹94,000
Yes
27 Dec 2022
3 Nov 2022
1 Dec 2022
3 Nov 2022
24 Nov 2022
17 Nov 2022
Amount
Maintenance, servicing, cleaning of vacuum circuit breaker unit of 11 KV VCB panel of capacity 400 Amps to 2500 Amps, taking out from panel, cleaning of all parts with CTC and clean cloth, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the VCB, checking of complete operating mechanism for proper functioning, reporting for any defective parts, complete all as specified and as directed. (Note: Replacement of defective parts of the VCB shall be measured and paid separately)
Supply and fix including dismantling taking out unserviceable 11KV Buffer (For Opening Spring ) For 800A to 1600A, 11 KV VCB complete all as specified and as directed. Make-Schneider, Part No- MVIJ00098-01 or equivalent.
Supply and fix including dismantling taking out unserviceable Buffer (For Closing Spring ) For 800A to 1600A, 11 KV VCB complete all as specified and as directed. Make-Schneider only, Part No- MVIJ00056-01 or equivalent.
Supply and fix including dismantling taking out unserviceable single (Read-Blue) phase busbar spout suitable for 800 Amps to 1250 Amps VCB complete all as specified and as directed. make Schneider Part No MEP-39-32185 or equivalent.
Supply and fix including dismantling taking out unserviceable single (Y) phase busbar spout for 800 Amps to 1250 Amps VCB complete all as specified and as directed. make Schneider Part No MEP-39-32186 or equivalent.
Supply and fix including dismantling taking out unserviceable CT Spout suitable for VCB 800 to 2500 Amps complete all as specified and as directed. make Schneider Part No MEP-39-32186 or equivalent.
Supply & fixing closing coil assembly 110 V DC to Schneider make 11KV VCB incl necessary connection testing complete incl dismantling taking down unsv one complete all as specified and as directed.. Make- Schneider, Part No- ECO39SN134900FN
Supply and fixing tripping coil 110 V DC to Schneider make 11KV VCB incl necessary connection testing complete incl dismantling taking down unsv one complete all as specified and as directed.. Make- Schneider, Part No- ECO39SN134100FN or equivalent.
Supply and fix including dismantling taking out unserviceable Breaker Wheel - CAST IRON, For 800A to 2500A,11 KV VCB complete all as specified and as directed.. Make-Schneider only, Part No-MVIA00025-01 or equivalent.
Supply and fix including dismantling taking out unserviceable spring charging Universal motor with gear box 220V AC For 800A to 2500A 11 KV VCB complete all as specified and as directed. Make-Schneider only, Part No-MVIJOO157-02 or equivalent.
Supply and fix including dismantling taking out unserviceable busbar supporting insulator For 800A to 1600A 11 KV VCB complete all as specified and as directed. Make-Schneider only , Part No- MEP-39-A0147901 or equivalent.
Supply and fix including dismantling taking out unserviceable Rectifier unit (Monoblock) for spring charging motor For 800A to 1600A, 11 KV VCB complete all as specified and as directed. Make-Schneider, Part No- ERC-A-A00DC-001or equivalent.
Supply and fix including dismantling taking out unserviceable Drive Beam suitable for 11 KV VCB 800 to 2000 Amps complete all as specified and as directed. Make-Schneider Model No MSM3950118600FN or equivalent.
Supply and fix including dismantling taking out unserviceable Epoxy Body suitable for 11 KV VCB up to 1250 Amps complete all as specified and as directed. Make-Schneider Model No MEP3953022000FN-22 or equivalent.
Supply and fix including dismantling taking out unserviceable Shutter assembly for busbar / circuit spout suitable for 11 KV VCB up to 800A -1250 Amps complete all as specified and as directed. Make Schneider only Model No SPP0009-04 or equivalent
Supply and fix including dismantling taking out unserviceable space heater, 230V, 100 watt inside cable chamber including necessary connection, testing complete all as specified and as directed. Make- Schneider, Part No-EHT-A-AA 000-001or equivalent
Supply and fix including dismantling taking out unserviceable thermostat for space heater For 800A to 1600A Schneider make 11 KV VCB complete all as specified and as directed. Make-Schneider only, Part No- ETH-E-B000-001 or equivalent
Supply and fix including dismantling taking out unserviceable resin cast CT dual core of ratio 100-50/5A-5A/15VA core 1 metering, core 2 protection of breaking capacity 31.5KA with dimension 220x110x230 mm and hole to hole 110 mm for 800 to 1250 A Schneider make 11 KV VCB complete all as specified and as directed. Make : Kappa/Esun/ Pragati/AE/Schneider complete all as specified and as directed. Note : Contractor should visit the site for brackets size to mounting the CTs in 11 KV VCBs.
All as per item No 18.00 above but 400-200/5A-5A/15VA 5P10
All as per item No 18.00 above but 600-300/5A-5A/15VA 5P10
M&L for THERMOGRAPHIC TESTING of 11kV switch Boards with IMAGE INFRARED CAMERA to detect Hot spots, to avoid electrical failures and increase safety for all current-carrying devices. Visual and Mechanical Inspection to be done when load is applied to the system. Use & follow appropriate caution, safety devices, and personal protective equipment. Provide a report which includes the following: 1. Description of equipment tested. 2. Discrepancies if any.(HOT Spots). 3. Identify load conditions at time of inspection. 4. Provide photographs and/or thermo grams.
M&L for painting of outer surface of multiple section of complete VCB panel 11 KV size upto 2m x 1.8 x 0.8 in one substation using one coat of synthetic zinc paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gears all as specified and directed.
Decarburizing/Buffering of copper Busbar complete from 11kV HT Bus bar chamber of each VCB panel including connecting Busbar from CT to main Busbar & spout. Servicing of support insulator by clean cloth and hot air blower/ vacuum cleaner, applying Backtol Red solution to the bus bar insulator , checking for any loose contact, refixing of all nuts & bolts by Stainless steel , refixing all covers ,replacement of defective parts, busbar sleeve and ensure proper decarburizing up to proper megger value , checking all the connections all as specified and directed.
Supply and applying Si-COAT 570 RTV Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Cable chamber (4.5 Kg coating materials per panel) , testing complete all as specified and directed. Make:- CSL Silicones Inc. Canada
Supply and applying Si-COAT 570 RTV Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Bus bar chamber (4 Kg coating materials per panel) , testing complete all as specified and directed. Make:- CSL Silicones Inc. Canada
Note: (for item no 24,25) 1.Surface preparation: All insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating. 2.All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope
aswitha engineering works
B5BUILDING SOLUTIONS
MSN ENGINEERING WORKS
P VENKATA RAO
SANTOSH CONSTRUCTIONS
SATYAM ENGINEERS
LEO ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .