Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹35.9 LAccepted-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L-1 | Accepted-Finance LOWEST TENDERER | |
| 2 | L-2₹37.5 L+₹1.7 L (4.62%)Rejected-Finance FLAT NO 401 TULSANI HEIGHTS 4TH FLOOR GREEN PARK SOCIETY AKURDI GURUDWARA TO WALHEKAR WADI ROAD CHINCHWAD PUNE 411033 | PUNE | MAHARASHTRA | 411033 | L-2 | Rejected-Finance GREATER THAN L1 |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
18 Jul 2020, 6:00 pmClosed
Maj Komal Parihar
GE (I) (NAVY), INS SHIVAJI - POST, LONAVLA -410402
SPECIAL REPAIR S TO EXTERNAL ELECTRIC SUPPLY AND AREA LIGHTING NEAR NBCD BLDG AND INTERNAL LIGHTING OF GOMATI BLOCK AND IMPROVEMENT TO INTERNAL LIGHTING OF STEAM WING BLDG NO.P203 SMW, FLAMEPROOF LIGHT FITTING ALONG WITH ALL REQUISITE FLAMEPROOF WIRI
2020_MES_356671_1
GE/LONAVLA/8921/E8
Open Tender
Civil Works
Item Rate
270 days
GE (I) (NAVY) LONAVLA
As per NIT /Tender documents
4 documents required · 4 mandatory
₹500
Yes
GEINDEPNAVYLONAVLA
₹86,000
Yes
21 Jul 2020
29 Jun 2020
20 Jul 2020
29 Jun 2020
18 Jul 2020
6 Jul 2020
30 Jun 2020 - 5 Jul 2020
Amount
Excavatioin in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and taking out hard/dense soil for laying of cable /erection of pole/stay pit excavation
M&L for dry river sand for cable cushoining laid in trenches for protection of cable
M&L for bricks sub class 'B' old size well burnt for cable protection all as specified and directed
Returning and filling including spreading levelling watering and well ramming in layers not exceeding 25 cm
Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point
Supply laying and testing cable XLPE insulated screened PVC beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade wiyh stranded aluminium conductor of size 16 sq mm 4 core. Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade wiyh stranded aluminium conductor of size 25 sq mm 3,1/2 core. Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade wiyh stranded aluminium conductor of size 35 sq mm 3,1/2 core. Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 50 sq mm 3,1/2 core.Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 95 sq mm 3,1/2 core.Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 120 sq mm 3,1/2 core.Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
Supply laying and testing cable XLPE insulated screened beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 240 sq mm 3,1/2 core.Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted.
M & L for tubes light grade of size100 mm dia for UG cable protection with all fittings laid in trenches, on poles to crossing the roads/Nalah etc .
Cutting bituminus road as per direction of Engr in Charge for laying of UG cable and match the existing road to the existing system.
Taking down existing RCC/Steel tubular LT street light pole by using gas cutter or by using welding machine or by diging foundation of any size by disconnecting of electrical Connection of street light, taking down street light and refixing the same on new octogonal poles as per direction directed by Engr- In-charge.
Supply and installation of BAJAJ make Hot dip galavanised iron pole 7 mtr long sheet thickness 3 mm. C/s A/F - top = 70mm, bottom =130 mm, base plate 200x200x12 mm, 500 mm long weatherproof reinforced door opening with junction box mounting arrangement but including of junction box, single arm bracket 1 m, 20 dia threaded made to J shape M20x600mm long steel grade EN8 foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing Approved Equivalent Make - PHILIPS Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing including formwork. This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Excavation, PCC, RCC formwork and reinforcement shall deemed to be included in quoted rates.
Supply & fixing 90W pressure die cast aluminium housing LED street light, including connection with two core twisted copper flexible cable. Including taking down old street light fitting and diposited to MES store Yard for reused. Make - Bajaj, Cat No - BRTGF90W LED or equivalent make of wipro/philips
Supply & fixing 100W LED Turbo flood light luminaire with secondary optics made in pressure die cast housing with heat sink & aluminium extrusion with IP66 , including connection with two core twisted copper flexible cable. Including taking down old street light fitting and diposited to MES store Yard for reused. Make - Bajaj, Cat No - BARFEG 100W LED or equivalent make of wipro/philips
S&F 90W LED square projector with RGB LED ; surface finishing, powder coated, outdoor grade, Anti-UV ; LED etc complete all as specified and as directed. Make: CREE/Osram; Housing; aluminium alloy, tempered glass; Single LED power: 2W; Control Method: Standard DMX 512 ; Option for Different beam angle ;IP 65
M&L for earthing complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to GI strip using 32x6mm galvanised iron strip, means of volts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 5 of SSR part1991,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 185 to 240 sqmm, Indoor/Outdoor type
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm, Indoor/Outdoor type
M&L for Shifting of existing panel board of any size/capacity including removing all the electrical connections and refixing the same and reconnecting the electrical connections and making the suitable size of platform all as specified and directed
Supply and fix LED bollard in rectangular shaped victorian design with ipal acrylic diffuser and IP 65 protection mounting on masonarypost/piller complete with and including standard accessories all as per cat No BOS 600 9W LED of Bajaj or equivalent in Philips/Wipro
Supply & installation of post top mounting decorative street light pole of height 3m of dia 140 mm bottom and 76mm at top made out of GI Pipe as per IS 1239. inbuilt junction box weather proof flush type door & locking arrangement for housing at bottom of pole to accomodate 6 amps MCB and bakelite terminal plate / sheet, base plate shall be 250 x 250 x 10 mm thick, top pipe of the pole shall be provided with cast iron embalishment (black colour with goldedn cast iron rings) to add aesthetic on the pole with the help of gurv screw. the body of decorative pole shall be machined and polished properly to give it a smooth surface. the decorative pole shall be duly pretreated and painted in u.v. ray resistant PU coating of approved colour shade. fitting should have housing in die cast aluminum with polycarbonate diffuser,IP 65 protection with LED bulb 18 watt, etc complete all as specified and as directed. Make Cat No darrant pole ( with 18 watt LED bulb fitting of antiqua fitting) of Bajaj or equivalent in Philips / Wipro. Note: Rates deemed to include necessary foundation bolts, grouting, bracket arrangement for satisfactory installation.
Supply and fix LED post top made in die cast aluminium housing with decorative clear opal acrylic diffuser and IP65 protection mounting on masonarypost/piller with suitable MS/GI pipe complete with and including standard accessories all as per cat No BGCT W4 LED WWof Bajaj or equivalent in Philips/Wipro
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete,(fittings such as switches, ceiling roses, pendants, regulators sockets etc. to be measured separately), removing materials to store for keeping in safe custody for issue under Schedule of credit and making good disturbed surfaces of walls, floors, etc.
Taking down MCB DBs / SFUs
M & L for point wiring with 1.5 sq mm single core PVC insulated cable 1100 V grade with multistranded copper conductor drawn through PVC casing and capping with all accessories fixed to wall /roofs ceiling etc and incl provision of 1.5 sq mm PVC insulated and unsheathed copper conductor as earth continuity conductor and connected to common earth dolly incl fabricated steel terminal box made out of 1.6 mm thick MS sheet concealed in the wall with 3 mm thick laminated sheet top cover / PVC Switch Board mounted on wall for mounting the switches , socket outlets , fan regulators etc all as s specified and directed for One light/Fan point controlled by one switch.
All as per item No.29 above but for one socket 3 pin outlet 5 amp on independent board.
All as per item No.29 above but for one 3 pin socket outlet 5 amp on the same board board with other switches.
All as per item No.29 above but for one bell/buzzer point controlled by one push button on the same board with other switches or independent with cable 1.5 sq mm size.
All as per item no 29 above but with copper conductor cable for one 3 pin socket outlet 15 amp independent board with cable 2.5 sq mm.
S&F in repairs switch piano flush type single pole one way 5 amp.
S&F in repairs ceiling rose three terminal/PVC polycarbonate, isolated body complete all as specified.
S&F in repairs switch socket combination 2 in 1, 3 pin 5/15 amp flush type. .
S&F in repairs switch socket combination 2 in 1,5 amp flush type.
S&F in repairs socket outlet 2 in 1, 3/5 pin 5 amp multi purpose, flush type.
S&F in repairs switch bell push, flush type 5 Amp.
S&F in repairs bell, electronic type AC, 230 Volts single pole.
S&F in repairs fan regulator flush type complete all as directed by EIC at site
M&L for replacement of lamp holder, insulated body with back plate batten/angle type for batten fitting complete all as specified & directed.
Supply and fix new adore LED lamp 15 Watt confirming to Cat No LHLDERUEMD8X015 of Havell's or euivalent in Philips / Bajaj
S&F in repairs LED Tube light 18 Watt LED complete set prewireed upto terminal block complete with all accessories and connecting up with twin core / .0076 flexible copper wire with and including LED tube light fixed on two nos PVC round / square mounting blocks complete all as required at site and as directed by Engineer -in-Charge. Make : Cat No for Batten-BLRB DB 118, and for LED Tube Rod Cat No BLRB 18W CW LED of Bajaj or equivalent of Havell's/Philips / Wipro
Supply & fix in repairs 45 W pressure die cast aluminium housing LED Building light secondary optics IP 66 protection including connection with two core twisted copper flexible cable, Make - Bajaj, Cat No - BRTFG 45W LED WW or equivalent make of Havells /Philips/CG
Supply and fix in replacement of LED Tube light of 10 watt (2") with batten integrated channel complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed.Make:Bajaj CAT Part No BCLSB 10 NW (2ft) or equivalent to CG/Philips/Wipro complete all as specified and directed .
S&F in replacement vertical type DB , (VTPN) suitable for and including MCCB 4 pole, 125 amps, 16KA as incoming (compact) Earth and neutral bus bar of capacity upto 200 amp 4 ways,IP 43 protection , shrouded neutral bar & pan assembly with flexible connecting link in the wall with suitable nut and bolt including matching the existing surface all as specified and directed ,
S&F in replacemen MCB DB SPN 4 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
S&F in replacemen MCB DB SPN 8 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
S&F in repairs MCB DB SPN 12 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
S&F in repairs MCB SPN 35-63 amps, 240 Volts, Complete all as specified and directed.
S&F in repairs MCB SP 6 to 32 amps single pole 240 Volts, Complete all as specified and directed.
S&F in repairs Isolator FP 63 Amps 415 V , with adjustable thermal and adjustable magnetic release,Make- Indoasian,Cat No-811561 or equivalent to Havells/Legrand Complete all as specified and as directed.
S&F in repairs MCB/MCCB Enclosure 3/4 (Way)Mod Metal. Make- Indoasian Cat Part No- 811981/811982, or equivalent to Havells/Legrand Complete all as specified and as directed.
Taking down sub main wiring of any size from the ceiling, walls etc and incl making good to disturb surface of wall and match with the existing surface.
M&L for sub main wiring drawing through PVC casing and capping with two single core 4 sq mm and one run of 4 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade all as directed. Note:- Three run of 4 sqmm wire and One run of PVC casing caping will be measured as one running meter.
M&L for sub main wiring drawing through PVC casing and capping with four runs of single core 6 sq mm and two runs of 4.0 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade all as directed.Note:- Four run of 6 sqmm wire and Two run of 4 sqmm wire and One run of PVC casing caping will be measured as one running meter.
Supply and fix in repairs Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of rating upto 06 -32 Apms
M&L for earthling complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized earth lead wire 4.0 mm dia by means of volts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR Part I 2009,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover , including testing on complition.
M&L for making hole in wall of size 300 mm dia to 450 mm dia for mounting of exhaust fan, making good the disturbed surfaces to match the existing complete all as directed by Engineer-in-Charge at site
Dismantling the existing energy Meters, MCCB / MCB Distribution boards by disconnecting the eletric supply connection and refixing at new or same location after carrying out repairs / replacement , reconnecting complete all as directed by EIC at site.
Supply & fix fans ceiling complete with accessories 230 V,1200 mm sweep. BEE 5 star rated including taking down old u/s ceiling fan and deposited to MES store complete all as specified and as directed.
Supply & fix exhaust fans metal body complete with and accessories 230 V,300 mm sweep including taking down old u/s exhaust fan and deposited to MES store complete all as specified and as directed.
M&L for taking down Opening of body cleaning of slots of Ceiling fan 1200 / 1400 mm Sweep. Rewinding of fan by super ennameled copper insulated wire as per existing gauge, varnishing, heating assembling and testing for following complete all as directed by Engineer-in-Charge.
Labour only for taking down repairs to Ceiling Fan, Exhaust Fan, any Make & any Sweep Oiling, Greasing , removing all dust with painting and replacement of unserviceable spares, complete all as directed by EIC at site. NOTE : Spares shall be measured & paid resperative item of this sch.
Renewal/ Repairs to LT Panel Board of any size complete as mentioned below:- (I) Repair/ replacement of damaged hinges of each compartment (ii) Taking down existing bus bars cleaning with CTC applying with becktol red solution, providing bus bar insulation and refixing with new nuts, bolts, washers etc., (iii) Replacement of damaged copper flexible cable and fixing new copper flexible cable of suitable size for incoming and out going connections of each MCCB terminals to bus bars (iv) Replacement of damaged/ worn out/ loose connections/ cable lugs for incoming & outgoing cables (v) Replacement of u/s CT's, ammeters, Volt meters, Indication Lamps (01 Set each) including provision of new wiring for the same. Note : Ammeters and CT's shall be wired with 2.5 sqmm copper wire . (vi) Replacement of neoprene gasket for all doors of panel board. Note : i) Cost for replacement of spares are deemed to be included in the quoted rates. ii) The rate shall be deemed to be included for replacement of worn out rusted, Channels, hinges, bolts, split pins and cable lugs, cable glands and neoprene gasket with painting to all doors including raising of foundation to 0.3 M height etc., iii) Cost of replacement of MCCB's, Repairs to ACB's not included in the scope of work.
Taking down copper/Aluminium pt wiring (light, Fan, socket or power) including fitting such as switch , socket C/roses , lamp holders, tube light fitting wooden boards, bell ., call bell, MCBs & regulators etc & making good to distrubed surfaces & maching with the existing colour of wall/Floor etc.
M & L for point wiring with 1.5 sq mm single core PVC insulated cable 1100 V grade with multistranded copper conductor drawn through PVC casing and capping with all accessories fixed to wall /roofs ceiling etc and incl provision of 1.5 sq mm PVC insulated and unsheathed copper conductor as earth continuity conductor and connected to common earth dolly incl fabricated steel terminal box made out of 1.6 mm thick MS sheat concealed in the wall with 3 mm thick laminated sheet top cover/PVC fiber board of suitable size for mounting the switches , socket outlets , fan regulators etc all as specified and directed for One fan/exhaust fan/Air ciculator point controlled by one way switch.
All as per item No. 68 above but with 2.5sqmm cable and 2.5sqmm earth continiuty wire for power point.
Supply and fix switch piano, flush type single pole, one way, 5 Amps, 240 volts all as specified and directed at site.
Supply and fix switch piano, flush type single pole, one way, 15 Amps, 240 volts all as specified and directed at site.
Supply and fixing socket outlet 2 in 1, 3 pin, 5 and 15 amp flush flush type all as specified and directed at site.
S&F in replacement of fan regulator electronic step , flush type on the existing phenolic laminated sheet .
Dismantling and taking down fluorescent tube light/Recess mounted single/double of any wattage or size street/garden light fittings for repair or replacement .
S&F sheet metal enclosure single pole and neutral with a two pin and earth plug and socket complete with one single pole MCB SP 20 Amps complete all as specified and as directed.
Supply & fix in replacement of LED tube light fitting 18 watt alongwith fixtures complete all as specified and directed .Make:Bajaj Model No BCLSB 18 NW/phi lips/Wipro
S&F 2x2 recess mounting LED luminaire 36 W white powder coated CRCA housing with LEDs plane front frame with translucent cover fixed to housing incl provision of necessary connection with twin twisted copper cable Make:Bajaj model NoBZRSQL36W Gzi WH or equalant in Philips/Wipro
Supply & fix in replacement of LED pendent luminaire 2x40 Watts range alongwith fixtures complete all as specified and directed .Make:Bajaj Model No BPTX 2-40 W LED 8F WH or equalent in ph lips/Wipro Note: Cost of MS conduit and all fixing arrangements are deemed to be included in quoted rates.
Supply & fix in replacement of LED HIGHBAY Luminaire 80 watt alongwith fixtures complete all as specified and directed .Make:Bajaj Model No BGHBM 80 LED XE/ph lips/Wipro
Supply & fix in replacement of LED pendent luminaire 40 Watts range alongwith fixtures complete all as specified and directed .Make:Bajaj Model No BPTX 40 W LED 4F WH or equalent in ph lips/Wipro Note: Cost of MS conduit and all fixing arrangements are deemed to be included in quoted rates.
Supply and fix ceiling roses, 3 phase, PVC/Polycarbonate, isolated body all as specified and directed at site.
Taking down exhaust fan and re-connecting up including provision of cable from ceiling rose to exhaust fan after cleaning all dust complete all as specified and as directed. Note :- (i) The spares like nuts & bolts,Fashners etc if found defective/damage deemed to be replaced and make the fans functional. The rates quoted for the same deemed to be included for the above job.
Supply and fix Exhaust fan 300 mm sweep AC 230 Volts 50hz single phase complete with all accesorries. Including taking down Unserviceable ceiling fan from the ceiling/roofs by disconnecting electric connection and diposited to MES store Yard.
Taking down ceiling fan (C/F of any size/make), cleaning its dust properly oiling and hanging the same back to its original position including connecting the wire to ceiling rose etc complete after completing the wiring all as specified and as directed by Engr-in-Charge. Note :- (i) The spares like condensor, ball bearing, cotter pin, nuts & bolts, connecting rods & hooks etc if found defective/damage deemed to be replaced and make the ceiling fans functional. No extra payments will be done on this account. (ii) In case any winding burnt cases may please be brought out to knowledege concern JE E/M for rewinding and making functional.
Taking out the defective winding for fan starter and cleaning the slots properly providing insulating sheets and supply and rewinding the fans with supper enameled copper winding and existing gauge and class varnishing the winding the winding wire and testing it for proper working for size of fan 1200/1400mm sweep.Including taking down ceiling fan1200/1400 mm sweep from the ceiling/roofs by disconnecting electric connection all as directed.
Supply and fix ceiling fan 1200 mm sweep AC 230 Volts 50hz single phase complete with all accesorries. Including taking down Unserviceable ceiling fan from the ceiling/roofs by disconnecting electric connection and diposited to MES store Yard.
M & L MCCB 100 Amps 4 pole 16 KA including enclosure with all accessories and connection complete
M & L for point wiring with 1.5 sq mm single core PVC insulated FRLS cable 1100 V grade with multistranded copper conductor drawn through stove enamelled steel conduit with all accessories concealed in the wall etc and incl provision of 1.5 sq mm PVC insulated FRLS cable1100 V grade multistranded unsheathed copper conductor as earth continuity conductor and connected to common earth dolly incl provn of fabricated steel terminal box made out of 1.6 mm thick MS sheat concealed in the wall with 3 mm thick laminated sheet top cover mounting the switches , socket outlets , fan regulators for one light point controled by one switches etc all as specified and directed for following.
S & F switch flame proof rotary type with termination box in LM6,LM16, single pole 250V
S&F Fluorewscent tube light fitting 1x36 Watt flameproof type FLP-WP made of aluminium alloy LM6,with electronic ballast , bipin holders, connectors blocks, etc complet with all accessories prewired and including connecting up with twin core twisted flexible copper conductor with suitable size as directed.
S&F in replacement of MCB single pole and neutral 32 amps, 240 Volts, Complete all as specified and directed.
S&F in replacement of MCB 6 to 32 amps single pole 240 Volts, Complete all as specified and directed.
S&F in replacement sub main wiring drawing through steel conduit of suitable size with two single core 4sq mm and one run of 2.5 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed FRLS cable of 1100 volts grade all as directed
M&L for earthling complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized earth lead wire 4.0 mm dia by means of volts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR part1991,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover , including testing on complition.
Supply and fix switch piano,flush type single pole,one way 5 Amps,240 volts all as specified and as directed at site.
Supply & fix exhaust fans AC single phase 230/ 240 V of size 300 mm sweep with louver complete all as specified and directed.Note:- Cost of making hole for Exhaust fan of required size at site is deemed to be included in qoted rates.
SHAILENDRA B TULSANI
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .