Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.6 LAccepted-Finance 139 3 A AMAR CHAKRABORTY ROAD PO KHAGRA DIST MURSHIDABAD PIN 742103 | MURSHIDABAD | WEST BENGAL | 742103 | L1 | Accepted-Finance L1 | |
| 2 | L2₹13.6 L+₹5,413 (0.40%)Rejected-Finance 139 3 A PO KHAGRA DIST MURSHIDABAD PIN 742103 | KHAGRA | MURSHIDABAD | WEST BENGAL | 742103 | L2 | Rejected-Finance L2 | |
| 3 | L3₹14.3 L+₹71,303 (5.24%)Rejected-Finance VILL ADHARMANIK P O BASUDEVKHALI P S BERHAMPORE DIST MURSHIDABAD | BERHAMPORE | MURSHIDABAD | WEST BENGAL | 742101 | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | SRIDAM MONDAL L3 | SUBRATA GHOSH L2 | SUBHAM ELECTRICAL L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply and Installation of Cubical panel suitable for 415V, 50 HZ, AC , 3 Phase and neutral system,made from CRCA MS sheet metal (14 SWG) incorporated the following main switches with IP-42/43 protection. The panel should have necessary interconection with incoming and outgoing main switch with busbar by suitable size of conductor and proper earthing attachment.The panel should be powder coated painted and all necessary Shrouds,Cable terminals, Nut-bolts and required accessories. (Make: Approved make of P.W.D.)
Incoming : 250A, 415V TPN SFU with propet HRC fuse (open execution type) --- 1 no.
Change Over Switch: 320 A, 415V TPN On-Load Front operated (open execution type)--- 1 no.
Busbar Chamber with 4 nos. 415 A capacity Al. Bus.
Outgoing : i) 160 A, 415V TPN SFU with propet HRC fuse(open execution type)----3 nos.
ii) 32A, 415V TPN SFU with propet HRC fuse(open execution type)---- 1 nos.
Digital Multifunction Meter with selector switch --- 1 no.
R,Y,B indicating lamp --- 6 nos.
C.T. coil 400A/5A (0.5s class) --- 3 nos.
Danger Board --- 1 no. Make: L&T,ABB,C&S,HPL (NS) | 1 | Nos | 1,25,000 ₹1,25,000 | 1,20,000 ₹1,20,000 | 1,19,000 ₹1,19,000 Lowest |
| 2.00 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment(upto 250A-8way)Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDRR | 2 | No | 22,500 ₹45,000 | 22,460 ₹44,920 | 22,458 ₹44,916 Lowest |
| 3.00 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (8way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER. | 2 | Nos | 5,500 ₹11,000 | 5,450 ₹10,900 | 5,448 ₹10,896 Lowest |
| 4.00 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, on wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (2+12Way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 4 | Nos | 2,750 ₹11,000 | 2,702 ₹10,808 | 2,700 ₹10,800 Lowest |
| 5.00 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment (8 way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 4 | Nos | 1,350 ₹5,400 | 1,345 ₹5,380 | 1,344 ₹5,376 Lowest |
| 6.00 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (160 A-FP) Make :- LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 2 | Nos | 12,500 ₹25,000 | 12,215 ₹24,430 | 12,212 ₹24,424 Lowest |
| 7.00Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionMake:Legrand,Schneider,ABB,Crabtree | ||||||
| 7.01 | TP(63A) For VTPN outgoing | 4 | Nos | 200 ₹800 | 195 ₹780 | 192 ₹768 Lowest |
| 7.02 | TP(32 A) For VTPN to ( Motor incoming) | 12 | Nos | 1,600 ₹19,200 | 1,500 ₹18,000 | 1,497 ₹17,964 Lowest |
| 7.03 | SP(6-32A) For Outgoing | 96 | Nos | 300 ₹28,800 | 240 ₹23,040 | 238 ₹22,848 Lowest |
Tender Value
Refer Docs
EMD Value
₹27,200
Closing Date
14 Mar 2026, 12:00 pmClosed
Executive Engineer,PWD
O/o The Executive Engineer Murshidabad Electrical Division P.W.Dte. 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Estimate for Electrical Installations of Laboratories for EI work New godown to converted Laboratories at Govt. College of Engineeering and Textile Technology , Berhampore, Murshidabad.
2026_WBPWD_1016488_1
WBPWD/EE/MsdED/83/e-Q of 25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
20 days
Murshidabad
Please refer Tender documents.
5 documents required · 5 mandatory
₹27,200
13 Jun 2026
28 Feb 2026
16 Mar 2026
28 Feb 2026
14 Mar 2026
28 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and Installation of Cubical panel suitable for 415V, 50 HZ, AC , 3 Phase and neutral system,made from CRCA MS sheet metal (14 SWG) incorporated the following main switches with IP-42/43 protection. The panel should have necessary interconection with incoming and outgoing main switch with busbar by suitable size of conductor and proper earthing attachment.The panel should be powder coated painted and all necessary Shrouds,Cable terminals, Nut-bolts and required accessories. (Make: Approved make of P.W.D.)
Incoming : 250A, 415V TPN SFU with propet HRC fuse (open execution type) --- 1 no.
Change Over Switch: 320 A, 415V TPN On-Load Front operated (open execution type)--- 1 no.
Busbar Chamber with 4 nos. 415 A capacity Al. Bus.
Outgoing : i) 160 A, 415V TPN SFU with propet HRC fuse(open execution type)----3 nos.
ii) 32A, 415V TPN SFU with propet HRC fuse(open execution type)---- 1 nos.
Digital Multifunction Meter with selector switch --- 1 no.
R,Y,B indicating lamp --- 6 nos.
C.T. coil 400A/5A (0.5s class) --- 3 nos.
Danger Board --- 1 no. Make: L&T,ABB,C&S,HPL (NS) | 1 | Nos | - | - |
| 2 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment(upto 250A-8way)Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDRR | 2 | No | - | - |
| 3 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (8way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER. | 2 | Nos | - | - |
| 4 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, on wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (2+12Way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 4 | Nos | - | - |
| 5 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment (8 way), Make: LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 4 | Nos | - | - |
| 6 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (160 A-FP) Make :- LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER | 2 | Nos | - | - |
| 7Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionMake:Legrand,Schneider,ABB,Crabtree | |||||
| 7.01 | TP(63A) For VTPN outgoing | 4 | Nos | - | - |
| 7.02 | TP(32 A) For VTPN to ( Motor incoming) | 12 | Nos | - | - |
| 7.03 | SP(6-32A) For Outgoing | 96 | Nos | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.42 MB
Tendernotice_2.pdf
PDF • 0.55 MB
BOQ_2497081.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .