Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Disqualified |
Tender Value
₹26.6 L
EMD Value
₹39,000
Closing Date
17 May 2021, 3:00 pmClosed
Deputy Vice President (HCD)
HLL Lifecare Limited, HCD Projects, HLL Bhavan, 6th Floor, Golden Jubilee Block, Poojapura, Thiruvananthapuram - 695012, Kerala, Ph 0471-2775651
Civil and Electrical Works for Setting up of ICU at Taluk Hospital, Sasthacotta, Kollam, Kerala as per Schedule of Work enclosed.
2021_HLL_421623_1
HLL/CHO/HCD/CE/ICU-STA/21-22
Open Tender
Civil Works - Buildings
Item Rate
45 days
Taluk Hospital, Sasthacotta
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,800
Yes
₹39,000
Yes
28 May 2021
21 Apr 2021
18 May 2021
21 Apr 2021
17 May 2021
21 Apr 2021
Amount
Civil Work
CEMENT CONCRETE
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
RCC WORK
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 150 landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
DISMANTLING AND DEMOLISHING
Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area 3 sq. metres and below
Dismantling of flushing cistern of all types (C.I. / PVC/ Vitrous China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge
MASONRY WORK
Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
Solid masonry using pre cast solid blocks (factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete
PLASTERING
12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
CURTAIN AND FALSE CEILING
Supplying and laying polyester, washable and stain free cloth(Bio-Active fabric washable germ free suitable for sterile area) curtain system with maximum curtain cloth height 230 cm(top 30 cm white colour net and 200cm light blue color as per approval) stitching with stifiner tape, pleats, ironing and laying around each bed using PVC runner with hooks & stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceiling with powder coated MS cup, all leads and lifts including all labour charges etc. complete. (unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will not be considered in cloth measurement)/ supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer in charge including conveyance.
Providing and fixing GI Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing 'C' wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter ofthe room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of sixe38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring 'T' with :GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/sqm(both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
TILE WORK
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer) of Ist quality conforming to IS: 15622 of approved make in all colours, shades, except white, Ivory, Grey Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete.
Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
Providing and fixing first quality Vitrified wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, ncluding pointing in white cement mixed with pigment of matching shade complete.
DOORS
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing to existing door frames.30 mm thick Fiberglass Reinforced Plastic (F.R.P) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF) / Polystyrene foam to be used all filler material throughout the hollow panel, casted monoolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS : 14856, complete as per direction of Engineer-in-charge.
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Veneered flat pressed three layer or graded wood particle board with commercial veneering on both sides conforming to IS : 3097, grade I
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:5.5mm thick glass pane
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete:150x10 mm
Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete
Providing and fixing ISI marked, IS : 1341, M.S. heavy weight butt hinges with necessary screws etc. complete:125x90x40.00 mm
PAINTING
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
WATER SUPPLY AND SANITARY WORKS
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Surgeon type wash basin of size 660x460 mm with a pair of 15 mm C.P. brass pillar taps with elbow operated levers
Providing and fixing P.V.C. waste pipe for sink or wash basin including PVC.waste fittings complete.Semi rigid pipe32 mm dia
Providing and fixing PVC pipes includings of pipes with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 20 mm dia 10 Kgf/cm2
Providing and fixing PVC pipes includings joints of pipes with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 32 mm dia 6 Kgf/cm2
Providing and fixing PVC pipes includings of pipes with one step PVC solvent cement, trenching refilling & testing of joints complete as per direction of Engineer in Charge. 63 mm dia 6Kgf/cm2
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
Providing and fixing shower rose with shower arm (reputed make approved brand) including stop cockand other necessary fittings
Providing and fixing PTMT grating of approved quality and colour.Rectangular type with openable circular lid150 mm nominal size square 100 mm diameter of the inner hinged round grating
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
NURSE STATION AND SIGNAGE
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Ply wood 7 ply, 9 mm thickDecorative plywood one side decorative veneer and commercial veneer on other face (Type I) conforming to IS 1328 BWR Type
Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete.50 mm
Providing and fixing magnetic catcher of approved quality in cupboard/ward robe shutters, including fixing with necessary screws etc. complete.Triple strip vertical type
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-Charge.Powder coated minimum thickness 50 micron aluminium
Providing and fixing special quality chromium plated brass cupboard locks with six levers of approved quality including necessary screws etc. complete.Size 50 mm
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge ( Door handle, lock and stopper etc to be paid separately)
Providing and fixing concealed hinge of approved quality for 19-20mm thickdoor with stainless steel screws complete :
providing and fixing name board of 6 mm thick acrylic Sheet by mirror printing. Fixing on surface by means of double coated vinyl pasting with 2 inch studs. including cutting, finishing etc completing upto all level.
Providing and fixing 1 Pair Cold Rolled Steel Ball Bearing Drawer Telescopic Channel Runner, Loading Capacity 45 Kg, 450 mm, 18 Inches, Zinc plated ( best make of approved quality ) including necessary cutting and making good etc. complete
ELECTRICAL WORKS
POINT WIRING
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Short point
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
SUB/CIRCUIT MAINS
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp.
BHP SETUP
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
POWER CIRCUITRY and UPS
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp,16 KA,TPMCCB
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
SITC OF ONLINE UPS 10 KVA (3 Phase I/P - 3 Phase O/P)<br>SITC of Online UPS with 20 min backup with 12 V 160 Ah battery of minimum 2 yr warranty. The system shall be true online, double conversion technology with input pf >0.98, input current THD <10% and 100% generator compatible. The system shall comply to IEC /EN 62040-1 and relevant IS standard. 10kVA 3ph input / 3ph output
SITC OF 160Ah TUBULAR BATTERY<br>SITC of 160Ah Tall Tubular Battery with Better Charge Acceptance & Long Back up having 30% More Acid Volume per Ampere hour than Ordinary Tubular Batteries. High Purity, Extra-Strong, Flexible Oxidation-Resistant Gauntlet for Better Performance & Long Life. Puncture-Resistant Polyethylene Separator for Internal Short Circuits. High Durability with Sealed Plastic Housing. Easy Maintenance with Level Indicators. Inverter Support: 600 VA - 10 KVA. Boost Charging: 15.1 Amp Starting Rate, 7.6 Amp Finishing rate. Trickle Mode Charging: 126 mA (Min), 504 mA (Max).
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required
SITC 63A RCCB<br>Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>63 amps
SITC 2 TON SPLIT AC<br>Supply, installation, testing and commissioning of 2 TR, 3 star rated (as per BEE) Air Cooled High Wall mounted Inverter type Split Air Conditioner consisting of high wall mounted type room unit (fan coil) with cordless remote control and one number outdoor condensing unit comprising of enegy efficient suitable rotary compressor for operation on single phase, 230 V, 50Hz supply, fixing the outdoor unit on a raised platform as per manufacturers recommendation and fixing of room (fan coil) unit on wall, standard 4 m distance refrigerant copper piping with 13mm nitrile rubber insulation, providing and making interconnection between room & condenser as per site conditions, comprising of 1" dia drain PVC pipe with insulation 4m, canvas connections, full electrical cabling from power plug near indoor unit and to outdoor unit, ODU MS stand, first charge refrigerant gas, suitable stabilizer etc complete as required. Make: Voltas, Toshiba, Blue Star, Siemens, Mitsubuishi, Hitachi or equivalent
ADS WORKS
EXHAUST FAN - 150CFM 10mm ESP<br>Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be Single/double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply. All units shall be complete with duct flexible connector and volume control damper, etc. complete as required - 150CFM 10mm ESP
SITC 4 -WAY PERFORATED AL DIFFUSER<br>SITC of 4 way perforated aluminum diffusers having the Frame fabricated from high quality extruded aluminum profiles with the advantages of corrosion resistance and rigidity. Perforated panel should be fixed to the frame by screws. having options for ncluding different types of internal cores. Core is fixed to the frame with aluminum pins loaded with steel springs. Core can be easily removable and interchangeable to allow for maximum flexibility in installation and maintenance. For supply air diffusers, Perforated sheet is slightly lowered below the center line. This arrangement provides improved horizontal airflow, etc. complete as required.
Supply, Installation of Acoustic Insulation of ducts using open cell processed nitrile rubber having a density of 140-180 Kg/m3 and thickness of 10 mm with Microban Certified anti-microbial protection etc. complete as required
Supply ,Installation of Thermal Insulation of ducting using Closed Cell Elastomeric nitrile rubber having a density of 40-60 Kg/m3 and with Microban Certified anti-microbial protection etc. complete as required - 9mm
SITC LAMINAR HOOD/PLENUM<br>SITC of Laminar Hood with Filter module housing HEPA filters made out of SS-304 - 18 Gauge sheet and Al. perforated sheet at Bottom. Size of each module shall be approximately 1800 mm (width) X 1800 mm (Length) X 350 mm (Height). Hood shall have necessary inlets with heavy duty collar dampers with minimum of 8 no's of size 600 mm X 600 mm.
HEPA FILTER - NEGATIVE PRESSURE<br>Supply and installation of 1500CFM Flange type HEPA filters (610X610X300MM) efficiency not less than 99.99% for particles of size down to 0.3 micron at exhaust system terminal collars.
SITC of UV Airborne Duct System designed for installation into commercial HVAC system ducts for the purpose of airborne disinfection using ultraviolet germicidal irradiation with maximum installation flexibility and costeffectiveness the UV lamps are mounted onto a framework of standard 0.5” EMT tubing having remotely mounted weather resistant power supply which can withstand the wet environment found inside of air handlers or the exposed conditions of outdoor packaged air conditioning systems. High output lamps are typically recommended for airborne treatment. <br>Standard 32” lamps with L-brackets for easy installation with 32”, 46”, 60” normal-output or 32” high-output lamps. Combine single, dual, triple, quad lamp configurations to suit any size HVAC installation as per technical specifications or on approval from HLL Electrical Engineer
Wall Mount Rack - 4U<br>Wall Mount Racks are made with solid steel structure 4U 19",with minimumdimensions 240x545x350 mm,(H x W x D), in a single section with front lockable glass door and with provision of two side cable entry from top and bottom with proper internal cable management and heatmanagement. Having IP20 level protection.RAL 7035 SHADE , neatly finished etc as required
DUCTING .8mm GSS<br>Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.<br>Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick
DUCTING .6mm GSS<br>Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.<br>Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick
ELECTRICAL FITTINGS
SITC of 1X1 Square/Circular type Recess mounted Slim circular/square type LED panel in white finish with anti-glare diffuser and separated energy efficient electronic driver. with a minimum of following technical specifications -Input Voltage : AC 220-240 V, 50/60Hz,Driver Type : Constant Current. Non- Integral,P.F >= 0.5 For 3W & 7W, >= 0.9 For 15W & 20W,Voltage Operating Range : 80-400V,High Surge Protection : 2.5 KV,CRI : Ra > 70,LED Life : 30,000 BH,Optics : Poly carbonate Diffuser,Accessories : With Driver and mounting accessories complete as required, any change in the pecifications should be made under the consent of Electrical Engineer or Engineer in charge
2X2 SQUARE TYPE RECESS MOUNTED LED LIGHT<br>SITC OF 600mmX600mm square type Cool White, Warm White, Pure White LED light fixture with Integrated Driver & Backlight Technology with a minimum system efficacy of 95w/Lm, Standard CCT: 3000K*, 4000K & 6500K, high color rendering CRI >80, with high efficiency driver, minimum of 35000 hours working life, and Surge protection -4KV (light variant as decided by engineer in charge),including connection with existing point using suitable gauge copper conductor directly to the ceiling rose. Each module should be tested and QC approved by competent authority and the same to be furnished before electrical engineer HLL Lifecare limited before purchase or else any higher version approved by the Electrical Engineer HLL Lifecare Limited
WALL FAN<br>Supply and installation of wall fan, white colour, 5 star rated as per BEE complete with blades, casing , wall mounting accessories etc(Make Havells/bajaj/usha/V-guard/crompton)
Cat 6 RJ 45 outlets to be fixed on existing modular face plates and including termination of Cat 6 cables on the outlets
EARTHING
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providingmasonry enclosure with cover plate having locking arrangement and watering pipe etc. withcharcoal/ coke and salt as required
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
interprise innovation projects private limited
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .