Add. City Engineer,North Zone
CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT FP -NO 161 TP-NO 121 IN NARODA WARD, NORTH ZONE, AHMEDABAD
355751
Tender Notice No 10/2026-27 ,TENDER NO-1
Open
Civil Works - Buildings
Works
Ahmedabad
4 documents required · 4 mandatory
₹18,000
Municipal Commissioner, Ahmedabad
₹16.0 L
15 Oct 2026
15 Oct 2026
15 Oct 2026
27 Oct 2026
15 Oct 2026
Name of Work:- CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT
F.P.NO :- 161 , T.P.NO :- 121 IN NARODA WARD, NORTH ZONE,
Bill of Quantities
I. No. Qty Items Unit Rate Per Amount
Civil Work Estimate
1 Demolition & Dismantling work
a 40.00 Demolition of RCC work using Hydra 1047.38 Cu.M.
Breacker including stacking of servicable
materials and disposal of unservicable
materials with all lead and lift.Removal Of
Existing Building Foundation and Super
Structure If Any.
b 60.00 Demolition of Brick work and stone masonry 544.95 Cu.M.
including stacking of serviceable materials
and disposal of unserviceable materials with
all lead and lift.(ii) In Cement Mortar.Removal
Of Existing Building Foundation and Super
Structure If Any.
c Dismentaling of sheet roofing including ridges,
Hips, Valleys, Gutters etc. stacking of
serviceable materials and disposal of
unserviceable materials with all lead and lift.
i 10.00 (i) G.I.sheet roofing. 47.25 Sq.mt
ii 5.00 (ii) A.C. sheet roofing. 53.55 sq.mt
d 2000.00 Dismentling steel work including distempering 3.63 Kg.
and stacking the materials with all lead and
e 2.00 Dismentling doors, windows, ventilators etc. 185.85 Each
(wood or steel) shutters including chowkhats
architraves, hold fasts and other attachment
etc. complete and stacking them with in all
lead and lift. (i)Notexceeding 3 Sq.M. in area.
f 250.00 Removing & Scrapping of Old deteriorated 19.38 Sq.M.
Plaster of any thickness from Masonary /
R.C.C. member including stacking of
serviceable material & disposal of un
serviceable from site of work with all lead &
g 50.00 Dismentaling any type tiled of stone floors laid 47.25 Sq.M.
in mortar including stacking of serviceable
materilas and disposal of unserviceable
materials with all lead and lift.
2 Excavation for foundation including sorting
out stacking of useful material & disposing of
excavated stuff upto 50 mt. lead. Loose & Soft
soil.Excexuted With Mechanical Effort
a 2301.00 up to 1.5 mt. depth 115.92 Cu.M.
c 1937.00 3.0 to 5.0 mt. depth 141.11 Cu.M.
d 500.00 Add extra for Disposing off the excavated stuff 17.28 Cu.M.
of above items for lead of (A) 50 m to 100 m
e 100.00 Add extra for Disposing off the excavated stuff 34.56 Cu.M.
of above items for lead of (B) 100 m to 200 m
f Providing and installing cast in situ single
under reamed piles of specified diameter and
length below pile cap, excluding the cost of
Concrete, steel reinforcement but including
the cost of boring with bentonite solution and
the length of the pile to be embedded in pile
cap etc. all complete. (Length of pile for
payment shall be measured upto to the
bottom of pile cap) :
i 200.00 400 mm dia. Piles 638.83 Rmt.
ii 100.00 450 mm dia. Piles 705.03 Rmt.
g Extra over single under ream for providing
additional bulbs in under reamed piles, under
specified diameter excluding the cost of
Concrete, steel reinforcement (only the nos. of
extra bulbs are to be paid).
t 20.00 400 mm dia. Piles 813.05 Each
ii 10.00 450 mm dia. Piles 1103.43 Each
3a 1.00 Provdg. & laying cement concrete 1:5:10 (1 2492.52 Cu.M.
cement : 5 course sand : 10 hand broken
aggregates 40 mm nominal size) and curing
complete, excluding cost of form work in
foundation & Plinth.
3b Provdg. & laying cement concrete 1:3:6 (1
cement : 3 coarse sand : 6 hand broken stone
aggregates 40 mm nominal size) and curing
complete excluding cost of form work in
578.00 (A) Foundation and plinth 2976.00 Cu.M.
3c 227.00 Supplying of graded hand brocken stone size 609.82 Cu.M.
of 90 mm to 127 mm at site (Rubble or Spoul)
3d 986.00 Labour charges for spreading the spouls 90 16.07 Sq.mt.
mm to 127 mm thick layer good earth filling in
voids correcting the grade & camber comp.
with rolling, watering, incl. preparing
thesurface by brushing for removing all loose
or dirts ect.comp.
4 5.00 Provdg. & laying cement concrete 1:4:8 (1 2653.67 Cu.M.
cement : 4 coarse sand : 8 hand broken stone
aggregates 40 mm nominal size) and curing
complete excluding cost of form work in
foundation& plinth.
5 4750.00 Filling available excavated earth (excluding 129.10 Cu.M.
rock) in trenches, plinth, sides of foundations
etc. in layers not exceeding 20 cm. in depth
consolidation each deposited layer by
ramming and watering.
6 Conveyance charges of earth lime, murrum,
building rubbish, manure, garbage, sludge,
excavated rock, fly ash, aggregate of any kind
a 100.00 Conveyance charges 0 km to 1 km 320.20 Cmt
b 100.00 Conveyance charges 0 km to 2 km 347.73 Cmt
c 10500.00 Conveyance charges 0 km to 5 km 408.41 Cmt
d 10500.00 Extra For Lead on Above Item Above 5 km & 9.26 Cmt
e 10500.00 Extra For Lead on Above Item Above 6 km & 9.26 Cmt
f 10500.00 Extra For Lead on Above Item Above 7 km & 9.26 Cmt
g 10500.00 Extra For Lead on Above Item Above 8 km & 9.26 Cmt
h 10500.00 Extra For Lead on Above Item Above 9 km 9.26 Cmt
7a 15.00 Filling in plinth with sand under floors 455.63 Cu.M.
including watering, ramming, consolidating,
compacting and dressing etc. completed.
7b 644.00 Filling in foundation and plinth with murrum or 286.20 Cmt
selected soil in layers of 20 cm. thickness
including watering, ramming and consolidating
8 Brick work using common burnt clay building
bricks having crushing strength not less than
35 kg/Sq. cm. in cement mortar 1:6 (1 cement
: 6 fine sand) conventional brick
a 98.00 (a) in foundation & Plinth 3981.21 Cu.M.
b 353.00 Super structure Upto Floor Two Level 4253.46 Cu.M.
c 848.00 Super structure Above Floor Two Level 4293.55 Cu.M.
9 I.Half brick masonry in common burnt clay
building bricks having crushing strength note
less than 35 Kg/Sq. Cm. in cement mortar 1:4
(1 cement : 4 coarse sand) using conventional
brick in Super structure upto floor Four level
a 715.00 All Floor Level 646.70 Sq.M.
10.1 Providing and laying controlled cement
concrete of M-25 Grade and curing complete,
Excluding the cost of form work, Scaffolding,
cost of reinforcement for reinforced concrete
work For any Height up to any FloorLevel.
a 3.00 Foundations,Raft,Footings,Mass concrete 4238.04 Cu.M.
b1 2.00 RCC Retaining wall at All Floor 4519.88 Cu.M.
c1 4.00 Tie-Beam, Lintel , Beam- Bracket, Stair Case 4496.07 Cu.M.
& Landing, Coping ,Slab, balcony, weather
shed, loft , any cantilever etc All Floor
d1 2.00 Columns,Pillars, posts and struts at All Floor 4593.91 Cu.M.
10.2 Providing and laying controlled cement
concrete of M-20 Grade and curing complete,
Excluding the cost of form work, Scaffolding,
cost of reinforcement for reinforced concrete
work For any Height up to Floor Four Level.
a 4.00 Foundations,Raft,Footings,Mass concrete 3977.88 Cu.M.
b1 148.00 Tie Beam , Lintel , Beam- Bracket , Coping 4460.36 Cu.M.
,landing, Slab, balcony, weather shed, loft
any cantilever etc at All Floor
c1 3.00 Column at All Floor 4558.20 Cu.M.
d1 1.00 Stair Case All Floor 5418.91 Cu.M.
10.3a 383.00 Providing and laying in position Ready Mixed 4853.56 Cu.M.
M250 grade concrete for reinforced cement
conctere work , using cement content as per
approved Design Mix manufactured in fully
automatic batching plant and transported to
site of work in transit mixer for all lead having
continuous agitated mixer, manufactured as
per mix design of specified grade for
reinforced cement concrete work including
pumping of R.M.C. from transit mixer to site of
laying with all lead and lift, excluding the cost
of centering shuttering finishing and
reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to
accelerate/ retard setting of concrete, improve
workability without impairing strength and
durability as per direction of the Engineer - in
charge. Without Fly Ash (Min cement level as
per latest IS 456 shall be maintained)
(Cement level 450 kg )
10.3b 2606.00 Providing and laying in position Ready Mixed 5043.60 Cu.M.
M300 grade concrete for reinforced cement
conctere work , using cement content as per
approved Design Mix manufactured in fully
automatic batching plant and transported to
site of work in transit mixer for all lead having
continuous agitated mixer, manufactured as
per mix design of specified grade for
reinforced cement concrete work including
pumping of R.M.C. from transit mixer to site of
laying, excluding the cost of centering
shuttering finishing and reinforcement
including cost of admixtures in recommended
proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability
without impairing strength and durability as
per direction of the Engineer - in - charge.
Without Fly Ash (Min cement level as per
latest IS 456 shall be maintained) (Cement
10.4 18.00 Providing and laying in position Ready Mixed 4793.10 Cu.M.
M200 grade concrete for reinforced cement
conctere work , using cement content as per
approved Design Mix manufactured in fully
automatic batching plant and transported to
site of work in transit mixer for all lead having
continuous agitated mixer, manufactured as
per mix design of specified grade for
reinforced cement concrete work including
pumping of R.M.C. from transit mixer to site of
laying with all lead and lift, excluding the cost
of centering shuttering finishing and
reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to
accelerate/ retard setting of concrete, improve
workability without impairing strength and
durability as per direction of the Engineer - in
charge. Without Fly Ash (Min cement level as
per latest IS 456 shall be maintained)
(Cement level 400 kg )
10.5 Drilling suitable holes in reinforced or plain
cement concrete with power driven drill
machine to a minimum depth of 80mm upto
250mm in RCC beams, lintels, columns and
slabs to introduce steel bars for
sunshades/balconies including fixing the steel
bars in position using Hilti Chemical HY200-R
but excluding the cost of reinforcement, all
complete as per direction of Engineer-In-
a 300.00 8 mm Dia in 80 mm Deep & 12 mm Dia 183.52 Each
b 1100.00 10 mm Dia in 100 mm Deep & 14 mm Dia 263.66 Each
c 1100.00 12 mm Dia in 120 mm Deep & 16 mm Dia 343.80 Each
d 180.00 16 mm Dia in 160 mm Deep & 20 mm Dia 608.63 Each
e 60.00 20 mm Dia in 200 mm Deep & 25 mm Dia 1024.44 Each
f 30.00 25 mm Dia in 250 mm Deep & 32 mm Dia 1938.54 Each
11 Providing and laying controlled cement
concrete 1:2:4( 1cement : 2 coarse sand :
Graded stone aggregate 20 mm nominal size
) and curing complete, Excluding the cost of
form work and reinforcement for reinforced
concrete work in:
a 4.00 Foundations, footings, base of columns,grade 3923.53 Cu.M.
slab and mass concrete.
b 1.00 slab, landing shelves, Balconies, lintels, 4012.47 Cu.M.
beams, girders, and cantilever, up to aany
c 1085.00 P/A Trimix with dewatering machine and 54.00 Sqmtr
floater machine on constructed R.C.C. work
incl. cost of machine and labour etc. comp. as
d 450.00 Making 15 mm Groove in R.C.C work on road 30.00 Rmt
and filling it with poly sulfied selant and
finished it good incl. all labour charges etc.
comp. as directed
e 68.00 Providing and laying and fixing 25 mm thick 738.13 Sqmt
expansion joint by hydrocell semi rigid UV
resistance with high performance laminated
closed cell polythene foam joint filler in sheet
foam as directed, etc. complete.
12 Providing form work in ordinary timber
planking so as to give a rough finish including
centering, shuttering, strutting and propping
etc. height of propping and centering below
supporting floor to celling not exceeding 4 M &
removal of the same for in situ reinforced or
plain concrete work in
a 1088.00 (A) Foundation, footings, bases of columns 171.68 Smt
etc. and mass concrete.
b 5119.00 (B) Flat surface such as soffits of slabs, 252.00 Smt
landing and the like
c 1656.00 (C) Vertical surfaces such as walls (any 229.95 Smt
thickness) partitions.
(D) Columns, pillars, posts & struts.
d 3216.00 (1) Square, rectangular, polygonal in plan 297.68 Smt
e 20.00 (2) Circular or curved in plan. 422.10 Smt
f 6400.00 (H) (1) Sides and soffits of beam, haunchings 192.15 Smt
cantilevers, girders, bressumers, Coping and
lintels not exceeding 1 M in depth.
g 10.00 (2) Sides and soffits of beam, haunchings 259.88 Smt
cantilevers, girders, bressumers and lintels
exceeding 1 M in depth.
h 205.00 (L) chullah hoops, weather sheds, chhajas, 155.78 Smt
carbels etc including edges.
i 960.00 (M) Staircase with-sloping or stepped soffits 242.55 Smt
incl. risers & strings excluding landing.
j 1350.00 Extra for additional height of propping and 386.48 Smt
centering where the height of propping and
centering exceeds 4 .O M between supporting
floor to ceiling including temporary brick or
stone pillars for supporting as required.
(i)Height more than 4.0 M.and upto 5.0 M.
13 Providing T.M.T Fe 500D bar reinforcement
for R.C.C. work including bending, binding
and placing in position complete up to any
a 361927.50 All Floor Level 75.46 Kg.
14 80.00 Providing and laying polished Kota stone slab 982.83 Sq.M.
(Polished / River Finish, Green colour )
flooring over 20 mm. (average) thick base of
cement mortar 1:6 (1 cement : 6 coarse sand)
or lime mortar 1:1.5 laid over and joined with
grey cement slurry including rubbing and
polishing complete.25 mm th.
15 169.00 Providing and laying polished Kota stone slab 1176.03 Sq.M.
25 mm. thick in Platform ,Riser of Stair
Skirting, Tread , dado and pillars laid on
mm. thick cement mortar 1:3 (1 cement :
coarse sand) jointed with grey cement slurry
including rubbing and polishing and MAking
groove where it is Required etc. compl
16 5.00 Providing and laying white/Colur glazed tiles 6 908.17 Sq. M.
mm thick in flooring treads of steps and
landing laid on a bed of 12 mm thick cement
mortar 1:3 (1 cement : 3 coarse sand) finished
with flush pointing in white cement.
17 290.00 Providing and layingWhite / Colour glazed 1426.95 Sq. M.
tiles of size 600 mmx300mm x 8 mm /
mmx 450mm x 8 mm in skirting, risers of
steps, Floor and dedo on 10 mm. thick
cement plaster 1:3 (1 cement : 3 coarse sand)
and jointed with white cement slurry.
18 2.00 Providing and laying marble stone slab 2194.63 Sq. M.
flooring over 20 mm. (Average) base of
cement mortar 1:6 (1 cement: 6 coarse sand)
or L.M. 1:1.5 laid and jointed with grey cement
slurry including rubbing and polishing
complete: (A) Marble slab 25 mm. thick.
19a 3925.00 Providing and laying Vitrified tiles 8 to 10 mm 1062.50 Sq. M.
thick , 24'' x 24'' in flooring treads of steps and
landing laid on a bed of 12mm thick cement
mortar 1:3 (1-cement : 3-coarse sand)
finishing with flush pointing in white cement.
19b 4850.00 Providing and laying Vitrified tiles 8 to 10 mm 1130.15 Sq. M.
thick , 24'' x 24'' in skrting risers of steps and
dedo on 10mm thick cement plaster 1:3
(1cement : 3-coarse sand) and jointed with
white cement slurry
19c 285.00 P & L 24" x 24" vitrified 8 mm thick tile flooring 1383.99 Sq.M.
over 20 mm (average) base of cement mortar
1:6 ( 1cement: 6 coarse sand) on new surface
or fixing on existing flooring by adhesive
material including dismentaling of existing
flooring and jointed with color cement slurry
including finised with flush pointing & cleaning
the surface etc. complete for Antiskid
19d 200.00 Providing and Fixing 18 mm thick concrete 3574.35 Sq.M.
base exposed brick cladding including surface
waterproffing, polymer modified tile adhesive
and polymer modifies tile grout ( grey / white)
with neccesary scafolding etc compl. As per
direction of engg. Incharge.
19e 210.00 Providing and Laying Tactile Tile (For Vision 1663.72 Sq.M.
Impaired Persons as per Strandards) of Size
300x300x9.8 mm Having with Water
Absorption less than 0.5% and Confirming to
is:15622 of Approved Make in all Colours and
Shades in for Outdoor floors such as footpath,
Courtyard, Multi models Location etc., laid in
20 mm Thick Base of Cement Mortar 1:4 (
Cement : 4 Course Sand) in all Shapes &
pattern including Grouting the Joints with
White Cement mixed with Matching pigment
etc. Complete as per Direction of Engineer-in-
20 10.00 Providing and laying Ceramics tiles 6 to 8 960.47 Sq. M.
mm thick in flooring, treads of steps, landing
and dedo on 12 mm. thick cement plaster 1:3
(1 cement : 3 coarse sand) and jointed with
white cement slurry.
21 1950.00 Providing & Laying 18 mm thick Mirror polish 2385.71 Sq. M.
granite For flooring , counter , stair -riser
tread , skirting , dedo , Jambs etc. machine
cut or chiselled on bed of cement mortar 1:1
pointing with neat cement slurry incl.
moulding, Making grooves where it is required
etc. comp. as per instruction of engineer in
22a Provdg. 20 mm. thick Finish / Mala cement
plaster in single coat on fair side of brick /
concrete walls for interior plastering upto any
Floor level and finished even and smooth in
i 7374.00 All Floor Level 190.58 Sq.M.
b Provdg. 20 mm. thick Finish / Mala cement
plaster in single coat plastering on ceilings,
Beam side and sofits of stairs upto any Floor
level and finished even and smooth in
i 6189.00 All Floor Level 215.15 Sq.M.
c 1794.00 Providing & fixing 23 cm wide chicken mesh 292.59 Sq.mt
jali with nails & then application of 15 mm
plaster on R.C.C. & masonary joints as per
dir. of engg. In charge.
d 650.00 Providing and mixing water proofing materials 48.77 Per Bag of
in cement mortar in proportion recommended 50 Kg of
by the manufacturer. etc. comp. as per Cement
instruction of engineer in charge.
23a 3470.00 Providing 20 mm th. Double coat Sand face / 297.68 Sq.M.
Mala Cement Plaster on Walls upto any
Height Above Ground level consisting of
mm th. Backing coat of C.M. 1:3 ( 1 cement :
3 Ssand ) & 8 mm th. Finishing coat of C.M.
1:1 ( 1 cement : 1 sand ) ets. Complete.
24a 100.00 White / Color washing with lime on 12.29 Sq.M.
undecorated wall surfaces (two coats) to give
an even shade including thoroughly brooming
the surface to remove all dirt, dust mortar
drops and other foreign matter.
24b 2800.00 Providing & Applying 3 mm thick External Wall 424.92 Sq.M.
Rustic Type Texture as per Design & Make
as Approved by Consultants / Engineer in
Charge. Work Includes All Necessary
Scaffolding Work upto Any Height.
24 c 3470.00 Finishing walls with Acrylic Smooth exterior 174.97 Sq.M.
paint of required shade :New work (Two or
more coat applied @ 1.67 ltr/10 sqm over and
including priming coat of exterior primer
applied @ 2.20 kg/10 sqm)
24d 25.00 P./L. METALIC HERITAGE SURFACE 637.38 Sq.M.
Providing and fixing of HERITAGE textured
homogeneous wall finishing system from
BAKELITE HYLAM LTD or equivalent make
consisting of a two component system of (25
kgs per Pack) made of 92% silica particles
coated with fade resistant pigments, 100%
acrylic polymer bonding agent (5kgs per pack)
with the applied thickness of the coating being
between 0.8mm-1.2mm to be applied on
acured, smooth level plaster without keying,
as per the shades/combinations approved, as
per the manufacturer directions, for usages,
tobe applied by an approved applicator of the
manufacturer, as per the directions /
supervision of the engineers in charge, all
complete. Includes All Necessary Scaffolding
Work upto Any Height.
25a 7500.00 Wall Painting (two coats) with plastic emulsion 78.44 Sq.M.
/ Oil paint of approved brand and manufacture
and of shade required on undecorated wall
surfaces to give an even shade, over and
including a priming coat with alkali resistance
primer of approved brand and manufacture
after thoroughly brushing the surface free
from mortar droppings, and other foreign
matter and also including preparing the
surface even and sand -papered smooth
b 7500.00 Extra over above item for every subsequent 33.39 Sq.mt.
coat of of wall painting with plastic emulsion /
Oil paint of approved brand.
c 7500.00 Applying two coats of Birla (white cement 40.19 Sq.M.
based) or Asian (acrylic lapy-putty) or
equivalent & two coats of primer of approved
brand and manufacture on new wall surface to
give an even shade including thoroughly
brushing the surface free from mortar
dropping and other foreign matter and sand
papered smooth.
26 Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work site,
unloading, lowering in trenches, laying and
jointing the pipes in c.m. 1:1 incl. all jointing
materials such as cement, sand, hemp,
bitumen as dire. testing the pipe line to a head
of 1.5 mt. and hydraulic test as dire incl.
watering trenches, spreading , and carting
away of surplus earth within 100 mt.lead as
dire. etc. comp.
a 170.00 23 cm dia. 344.64 Rmt
Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work site,
unloading, lowering in trenches, laying and
jointing the pipes in c.m. 1:1 incl. all jointing
materials such as cement, sand, hemp,
bitumen as dire. testing the pipe line to a head
of 1.5 mt. and hydraulic test as dire incl.
watering trenches, spreading , and carting
away of surplus earth within 100 mt.lead as
dire. etc. comp.
b 35.00 15 cm dia 211.05 Rmt
c 25.00 10 cm dia. 288.23 Rmt
27 20.00 Constructing brick masonry chamber for 3863.85 No.
under ground C.I. Inspection chamber and
bends with bricks having croshing strength not
less than 35 Kg. Cm2 in C.M. 1:5 C.I. cover
with frame (Lightduty) 455mm x 610 mm
intenal dimensions total weight of cover with
frame to be not less than 38 Kg. (Wt. of cover
23Kg.) and Wt. of frame 15Kg.) (R.C.C.top
slab with 1:2:4 mix (1-cement:2-coarse
sand:4-graded stone aggregate 20mm size)
foundation concrete 1:5:10 inside plaster
mm thick with cement mortar 1:3 finished
smooth with a floating coat of neat cement on
walls and bed concrete etc. complete.(i)
Inside dimensions 455 mm x 610 mm and up
28 a 6.00 Constructing Manhole with R.C.C. top slab in 19139.07 No.
1:2:4mix (1-cement: 2-coarse sand:4-graded
stone aggregate 20 mm nominal size)
foundation concrete 1:3:6 mix (1-cement:3-
coarse sand:6-Brick bats 40+50mm size)
inside plastering 15mm thick with Cement
Mortar 1:5 (1-Cement:5-coarse sand) finished
with a floating coat of neat cement and
making channels in cement concrete 1:2:4
mix (1-Cement:2 -Coarse sand:4-stone
aggregate 20 mm nominal size) finished
smooth complete including curing and festing
(i) Inside size 900mm x 1200mm and up to
1.5M. deep including C.I. cover with frame
size 560 mm diameter total weight of cover
and frame to be not less than 128kgs. (Wt. of
cover 64Kg. and Wt. of frame 64Kg.) (A) With
230 mm thick walls of brick masonry using
brick having crushing strength not less than
35Kg./Sq.cm. in Cement Mortar 1:5 (1-
Cement: 5-Coarse sand) (2)B type depth up
29a 24.00 Providing and fixing white vitreous china flat 3344.35 No.
back or wall corner type lipped front urinal
basin of 340x280x470 mm sizes respectively
with standard flush pipe, Waster Pipe, Waste
Coupling, PVc Connection and G.I clamps
complete, including painting of fittings and
brackets, cutting and making good the walls
and floors wherever required : Cera Model
No. S4020103 or Equivalent
b 75.00 Providing and Fixing of C.P. Brass BIB Cock 1564.17 No.
of 15 mm Dia of Jaquar make florentine
series model no. 5047n or equivalent make
with all necessary fittings. as approved by
Engineer - in - charge.,
c 60.00 Providing and fixing brass screw down Angle 1160.57 No.
stop tap.(A) 15mm dia. Of Jaquar make
florentine series modelno. 5053n or equivalent
make with all necessary fittings. as approved
by Engineer - in - charge.,
d 10.00 Providing and fixing C.P. brass shower rose 279.37 No.
with 15mm or 20mm inlet Shower Arm.(A)
100mm dia. Each
e 20.00 Provding and Fixing of autoclosing pressmatic 3280.52 No.
pillar cock / bib cock with all necessary fittings
of Polished Bright Chrome Finish of Jaquar
make model no. 031L65 or equivalent make
as approved by Engineer in Charge. Rate
including of cost of labour, material etc. in
complete manner.
f 40.00 Providing and Fixing of C.P. Brass Two Way 1411.58 No.
Bib Cock of 15 mm Dia of Jaquar make
model no. 041kn or equivalent make
approved make with all necessary fittings. as
approved by Engineer - in - charge.,
g 24.00 Providing and Fixing of C.P. Brass urinal 2568.08 No.
Valve Auto Closing System With Full Built in
Control Cock & Wall Flange of 15 mm Dia of
Jaquar make model no. 077 or equivalent
make approved make with all necessary
fittings. as approved by Engineer - in -
h 35.00 Providing and Fixing of C.P. Brass Pillar Cock 3723.48 No.
Auto Closing System with Elbow Operated
Extended Lever of 15 mm Dia of Jaquar
Make Model No,031 MED or Equvalent
Approved Make & Model with all necessary
fittings. as approved by Engineer - in -
30 25.00 Provdg. & laying S.W. Gully trap with C.I. 1234.57 No.
garting brick masonry chamber & water tight
C.I. cover with frame of 300 mm x 300 mm
size ( inside) with standard weight. sqare
mouth trap size 150 x100 mm P trap
31 2000.00 Providing erecting and fixing double coated 3.91 Litre
ISI water tank of required capacity each with
all necessary fittings and connection etc.
complete on terrace
32 20.00 Extra rate over item of excavation of earth for 71.43 Sq.M.
excavation of asphalt pavement/RCC of
thickness up to 0.20 meter including
demolishing the asphalt carpet, metal, soiling /
cutting Reinforcement etc.comp. with stacking
the material as directed.-up to 0.20 meter
33 65.00 Providing and fixing PVC SWR Nahni trap IS 565.43 No.
14735 for drain - 100 mm diameter with jali of
the following nominal diameter of self
cleansing design with C.I scread down or
hinged grating including the cost of cutting
and making good the walls.
34a Provdg. And fixing Concealed / Open to wall,
ceiling & floor in true line and level UPVC pipe
Schedule- 40 of make as approved by engg.
incharge. pipe shall be fix on wall with the
help of clamp at every twi meter center to
center of shall be concealed as directed in
cluding neccesarry fitting etc. in cluding
testing of pipe and jointd and fixing the same
with adhesive solvent , including cost of all
materials of following nominal bore
iii 15.00 32 mm 117.97 Rmt
34b Providing and fixing concealed center point to
wall ceiling & floor CPVC (SDR 13.5) PIPE
having National Sanitation Foundation (NSF)
seal for potable water of following dia. nominal
bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete
iii 50.00 25 mm 247.25 Rmt
35 Provdg. And fixing to wall ,ceiling and floor
10.00 kg. F/Sq.Cm2 working pressure
polythelene pipes of the following outside
diameter, low, density, complete with special
flange compression type fittings, wall clips etc.
making good wall ceiling and floor.
b 150.00 (A) 75mm dia 274.68 Rmt
36 10.00 Providing and fixing water closet squatting 1351.15 No.
Pan ( Indian type W.C. Pan) size 580mm
(A)VitreousChina. (I)Long pattern = White
colour with Trap and Pair of Foot Rest
37a 40.00 Providing and fixing white vitreous china 12613.27 No.
extended wall mounting water closet of Cera
Make S1043101 Carat Model Or Equivalent
Model With EWC Soft Close Seat Cover,
Chair Bracket, nuts, bolts and gasket etc
b Providing and fixing chromium plated brass
half trun flush cock of approved quality
including fixing in pipe line etc. complete.
c 40.00 Providing and fixing Health Faucet of Jaquar 1543.36 No.
make model no. 573 oe equivalent make as
approved by engg. In charge with flexible tube
upto 1 metre long etc. complete.
38a 8.00 Providing and fixing 24"x18"x8" Carysil 7960.60 No.
Elegance or Equivalent Make of Single Bowl
Sink S.S. Matt Finish With Waste Coupling,
Waste Pipe,etc. cutting and making good the
walls wherever required.
b 28.00 Providing and fixing Under counter Wash 6641.14 No.
basine including 15 mm C.P. Brass Pillar tap,
32 mm C.P. Brass Waste of Standard make,
Include All Accessaries, Cutting & Making
good the wall / granite Wherever Required in
White Color : Model S2030101 of Cera Clair
Series or Equivalent make Waash basine of
size : 520x450 mm
c 15.00 Providing and fixing Wall Hung wash basin 3825.20 No.
Including 32 mm C.P. brass waste of standard
pattern, Include All Accessaries, cutting and
making good the walls / granite wherever
require:In White Color : Cera Cadal Or
Equivalent Make Wash basin of size 515 x
d 8.00 Providing and Fixing White Vitreous China 5581.19 No.
Laboratory Sink with C.I. Brackets, C.P. Brass
Chain with Rubber Plug, 40 mm C.P. Brass
Waste and 40 mm C.P. Brass Trap with
Necessary C.P. Brass Unions Complete,
Including Painting of Fittings and Brackets,
Cutting and Making Good to Wall / Granite
Wherever Required: Size 600 x 450 x
39a 42.00 Provdg. & fixing 600mm x 450 mm Bevelled 825.48 No.
edge mirror of superior glass mounted of .6
mm th. A.C. sheet or plywood sheet and fixed
to wooden pluge with C.P. brass screws and
40 30.00 Provdg. & fixing C.P..Brass towal rail 597.22 No.
complete with C.P. brass brackets fixed to
wooden plugs with C.P. Brass screws.(600
mmx 20 mm size)
41 Providing and fixing ball valve (brass) of
approved quality, High or low pressure, with
plastic floats complete :
ii 1.00 20 mm dia 1099.94 No.
iii 45.00 25 mm dia 1552.93 No.
iv 23.00 40 mm dia 3312.60 No.
42a Providing and fixing Full Way valve (HEX)
with wheel of approved quality :
i 8.00 15 mm Full Way valve (HEX) 1461.17 No.
ii 1.00 20 mm Full Way valve (HEX) 1924.61 No.
iii 16.00 25 mm Full Way valve (HEX) 2535.55 No.
iv 1.00 32 mm Full Way valve (HEX) 3377.64 No.
v 16.00 40 mm Full Way valve (HEX) 4661.10 No.
vi 6.00 50 mm Full Way valve (HEX) 6675.14 No.
43a 4.00 Providing and Fixing of C.P.Brass Pillar Cock 1725.21 No.
of 15 mm Dia of approved make with all
necessary fittings. as approved by Engineer -
b 12.00 Providing fixing of SS grab bar with all 1937.24 No.
hardwares for Physically Handicap toilet.
44a 900.00 Providing and laying integral cement based 1150.48 Sq.M.
water proofing treatment including preparation
of surface as required for treatment of roofs,
balconies, terraces etc consisting of following
(a) Applying a slurry coat of neat cement
using 2.75 kg/sqm of cement admixed with
water proofing compound conforming to IS.
2645 and approved by Engineer-in-charge
over the RCC slab including adjoining walls
upto 300 mm height including cleaning the
surface before treatment.
(b) Laying brick bats with mortar using broken
bricks/brick bats 25 mm to 115 mm size with
50% of cement mortar 1:5 (1 cement :
coarse sand) admixed with water proofing
compound conforming to IS : 2645 and
approved by Engineer-in-charge over 20 mm
thick layer of cement mortar of mix 1:5 (1
cement :5 coarse sand ) admixed with water
proofing compound conforming to IS :
and approved by Engineer-in-charge to
required slope and treating similarly the
adjoining walls upto 300 mm height including
rounding of junctions of walls and slabs.
(c) After two days of proper curing applying a
second coat of cement slurry using 2.75 kg/
sqm of cement admixed with water proofing
compound conforming to IS : 2645 and
approved by Engineerin- charge.
(d) Finishing the surface with 20 mm thick
jointless cement mortar of mix 1:4 (1 cement
:4 coarse sand) admixed with water proofing
compound conforming to IS : 2645 and
approved by Engineerin- charge
(e) The whole terrace so finished shall be
flooded with water for a minimum period of
two weeks for curing and for final test.“All
above operations to be done in order and as
directed and specified by the Engineer-in-
Charge :and shall be guaranteed for minimum
period of 10 years after handing over the
completed building by the main contractor to
be finished as directed. Stamp paper
guarantee 10 years to be furnished before
receiving any payment from the client.
With average thickness of 120 mm and
minimum thickness at khurra as 65 mm.
b 900.00 Providing and laying broken chine mosaic 739.89 Sq. M.
flooring for terrace using 12 mm to 20 mm
broken pieces of glazed tiles to be laid over
cement mortar 1:3 to plain or slope and to be
tempered to bring mortar creme out upto
surface using white cement including
rounding off junctions and extending them
upto 15 cm along the wall,clearing with water
and oxalic acid etc. as directed.
c 560.00 Providing and applying fibre reinforced 562.40 Sq. M.
elastomeric liquid water proofing membrane
with resilient acrylic polymers having Sun
Reflectivity Index (SRI) of 105 on top of
concrete roof in three coats @10.76 litre/
sqm. One coat of self-priming of elastomeric
waterproofing liquid (dilution with water in the
ratio of 3:1) and two coats of undiluted
elastomeric waterproofing liquid (dry film
thickness of complete application/system not
less than 500 microns). The operation shall be
carried out after scrapping and properly
cleaning the surface to remove loose particles
with wire brushes, complete in all respect as
per the direction of Engineer-in-Charge.
d 88.00 Filling in Sunken Portion with good Quality 4559.61 Cmt
Aerated light weight concrete block having
crushing strength not less than 35 kg/sqcm
and where directed by the Architect /
Engineer-in-charge, in sunk in layer. including
watering, ramming where it is required etc.
complete, as directed by the Architect /
Engineer-in-charge .
45 180.00 Providing and laying cement concrete flooring 348.08 Sq.M.
( I.P.S.) 1:2:4 (1-cement : 2-coarse sand : 4-
graded stone aggregate 20mm nominal size)
laid in one layer and finished with a floating
coat of neat cement. (B) 50mm thick.
46a 12500.00 Providing and fixing M.S. grills/ Gate of 100.17 Kg.
required pattern to wooden/ Granite frames of
windows etc. with M.S. flats at required
spacings and frame alround, square or round
bars with round headed bolts and nuts or by
screws all complete as per the structural
designs and directions of Engineer in charge
b 2500.00 Providing & Fixing Structural steel work ( 126.68 Kg.
Confirming to IS 4923-1997) riveted, bolted or
welded in builtup for all type sections, in
framed work, including cutting, hoisting, fixing
in position and applying a priming coat of
approved steel primer all complete as per the
structural designs and directions of Engineer
c 850.00 Applying priming coat over new steel and 34.34 Sqmt
other metel surface after and including
preparing the surface by throughly cleaning,
oil, grease, dirt and other foreign matter and
scoured with brushes fine steel wood,
scrapers and sand paper with ready mixed
priming paint brushing red lead.
d 850.00 Painting two coats (excluding priming coat) on 86.94 Sqmt
new steel and other metal surface with
enamel paint, brushing, interior to give an
even shade including cleaning the surface an
even shade including cleaning the surface of
all dirt, dust and other foreign matter.
e 180.00 Providing & Fixing 1.2 mm Thick S.S.-304 2270.21 R.Mtr.
Grade 900 mm to 1150 mm High S.S. Railing
having Hand Rail Member of 50 mm Dia.,
No. of Horizontal Pipe of 16 mm Dia. &
Baluster Suppprt of 40 mm Dia. At Every
Third Step as per Detail Given. Rate Includes
All Work Complete as per Description & as
per Direction of Engg. in Charge.
47a 75.00 Providing and fixing in position collapsible 5391.23 Sq. M.
steel shutters with vertical channels 20x10x2
mm braced with flat iron diagonals 20x5 mm
size with top & bottom rails of T-iron 40x40x6
mm with 38 mm dia. Steel pulleys complete
with bolts , nuts , locking arrangement
stoppers , handles including applying a
priming coat of red lead paint.
b 5.00 Providing corrugated 0.80 mm (22 gauge) 719.93 Sq.M.
thick G.I. sheets roofing fixed with galvanized
iron ‘J’ or ‘L’ hook bolts, and nuts 8 mm. dia
with bitumen and G.I. limpet washers filled
with white lead complete excluding the cost of
purlines, rafters and trusses.
c 2.00 Providing valleys 900 mm. overall in plain 1.6 1042.78 Sq.mt.
mm. thick G.I. sheet Class – 3 fixed with ‘J’ or
‘L’ hook bolts and nuts galvanized from ‘J’ or
‘L’ hook bolts and bitumen washers complete.
48a 9.00 Providing and fixing rolling shutters of 3468.72 Sq.M.
approved make made of 80 mm wide M.S.
laths inter-locked together through their entire
length and jointed together at the ends by end
locks mounted on specially designed pipe
shaft with bracket plates, guide channels and
arragements for inside and outside locking
with push-pull operation including the cost of
hood cover and spring etc. complete.(A)
Shutters having width below 3.5 M.
b 12.00 Providing and fixing rolling shutters of 4450.51 Sq.M.
approved make made of 80 mm wide M.S.
laths inter-locked together through their entire
length and jointed together at the ends by end
locks mounted on specially designed pipe
shaft with bracket plates, guide channels and
arragements for inside and outside locking
with push-pull operation including the cost of
hood cover and spring etc. complete. (B)
Shutters having width 3.5 M. and above
49a 239.00 Providing and fixing 27mm domal Series - 1.2 6373.85 Sq. M.
mm Th. Alluminium Section Three track
Sliding window With Metalic Powder Coating
and 4 MM Clear Glaas(Non Tuffen) Include All
Accessaries and Fixture etc. complete as per
the direction of Engineer-in-charge.
b 28.00 Providing and fixing 27mm domal Series - 1.2 4999.10 Sq. M.
mm Th. Alluminium Section Two track Sliding
window With Metalic Powder Coating and
MM Clear Glaas(Non Tuffen) Include All
Accessaries and Fixture etc. complete as per
the direction of Engineer-in-charge.
c 77.00 ALUMINIUM DOOR WORK 5401.70 Sq. M.
Providing and fixing Aluminium Door work
(Single Shutter OR Double Shutter with or
without fix glass) made from Jindal or
equivalent make Powder Coated (50 micron
pure polyester coating ) ,aluminium section
frame built up standard tubular and other
section of approved make confirming to IS
733 and IS 1285 , member size with shutters
of horizontal member , vertical member
Confirming to IS733 and IS 1285 fixed with
rawl plug abd screws or fixing clips or with
expansion hold fasteners including necessary
filling up of gaps at junctions at top bottom
and sides with required PVC/ Neoprene felt,
8/12 mm toughened glass of approved make
etc. Aluminum sections shall be smooth, rust
free, straight.mitred and jointed mechanically
wherever required including Door Hardware
such as cleat angles aluminum snap beading
for glazing /paneling, CP Brass/ Stainless
steel screws, Stoppers, heavy duty floor hing,
S.S. Hinges, aldrop , Locking system, heavy
duty Floor Springs, Pivot and fixtures and
transparent silicon sealant glass fixing to
frame as per details all complete as per
architectural drawings and the direction of
Engineer in Charge. rate incl. all type of
alumnium sections for doors as per the detail
Architectural dwg.
50 a 24.00 Providing and fixing standared extruded of 1163.92 Sq. M.
alluminium section of size 63 mm x 38.10 mm
x 1.2mm (Section:2434, @ Wt.0.643Kg/mt )
with colour anodized alluminium frame for
ventilation with 5 mm thick frosted glass as
details etc complete for Ventilation
50 b 32.00 Providing and fixing standared extruded of 1509.90 Sq. M.
alluminium section of size 63.50 x 38.10 x
1.95 mm ( Section no: 4605, @Wt 1.094 Kg /
Rmt with colour anodized alluminium frame
with 5 mm thick transparent bronze colour
tinted float glass as details etc complete for
50c 54.00 Providing Fixing 1.2 mm thick Alluminium 3124.44 Sq.mtr.
Section Partition -Fully Glazed / Partly
Panelled Partly Glazed / Fully Panelled
Having Size of Section of 2.1/2 x 1.1/2 with
mm Compact Sheet / 5 mm thick Glass Fixing
with 4 mm thick EPDM Rubber etc. Complete
as per Direction of Consultant /
50d 15.00 Providing Fixing 1.2 mm thick Alluminium 4061.77 Sq.mtr.
Section Partition Door -Fully Glazed / Partly
Panelled Partly Glazed / Fully Panelled
frame Having Size of Section of 2 .1/2 x
.1/2 and Door Section Having Size of Tips
Vertical 1 .3/4 x 1 .3/4, Top Rail 4 x 1 .3/4,
Middle Rail 1 .3/4 x 1 .3/4, Bottom rail 4 x
.3/4 with 4 mm Compact Sheet / 5 mm thick
Glass Fixing with 4 mm thick EPDM Rubber
Including Lock, Handle, Door Closer, Door
Stoper, Stopper etc Complete as per Direction
of Consultant / Engg.incharge.
51a 122.00 Providing and fixing Structural Glazing with 3953.75 Sq.mt.
using the 17 Micron anodised of approved
colour alluminium section as transium,
mullium of size 63mm x 38mm x 2 mm with
using 6 mm thick reflective structural glass of
approved make, colour / Tinted, toughned and
shade and fixed with silicone sealant and
spacer tap and at corner sealed neoprene
foam dust and Air sealed gasket mirred
including scaffolding, cleaning of glass
etc.complete at all heights anf lifts with all
necessary fitting and fixtures, anchore
fasteners, necessary M.S. or Aluminium
brackets, suitable design for openable or
sliding window as per Architectural drawing
and as directed by Engineer-in-charge.
Grooves between the glasses to be filled with
sealant of Dow corning - structural sealant
995, weather sealant 789. The entire facade
should be water proof. The mullions are to be
connected to bracket by SS-304 nut bolts.
Measurement shall be given as per actual
execution of the work. (Rate are included
providing & fixing of MS structure steel work
wherever Required)
52a 105.00 Providing and fixing ISI marked 35 mm thick 4332.15 Sq.mt.
flush door shutters conforming to IS :
(Part I) decorative type, core of block board
construction with frame of 1st class hard wood
and well matched teak 3 ply veneering with
vertical grains or cross bands and face
veneers on both faces of shutters with
mm thick Decorative Laminated Sheet on both
faces of shutters including ISI marked
Stainless Steel butt hinges, bright /matt
finished 125 mm Stainless Steel handles of
approved quality & make, ISI marked
oxidised M.S. door latches / Aldrop
Conforming to IS:5930 with necessary screws
etc. complete as per direction of Engg.
b 284.00 Providing wood work in frames of Doors, 602.04 10
windows cleare story windows and Cu.Decim
othersimilar works wrought, framede and fixed
in position. (A) Indian Teak Wood
c 470.00 Providing & Fixing Fluted Glass Partition and 15963.19 Sq.mt.
Door Using 16 x 45 mm Powder Coated
Alluminium Section with 8 mm Thick Fluted
Toughened Glass Including Lock, Handle,
Floor Spring, Connector, Silicon and All Other
Accessaries including Making Pit etc
Complete as per Direction of Consultant /
d 320.00 Providing & Fixing Profile Shutter Using 16 x 14838.39 Sq.mt.
45 mm Powder Coated Alluminium Section
with 5 mm Thick Fluted Toughened Glass,
Concealed Handle Section and Hinges
Including All Accessaries etc Complete as per
Direction of Consultant / Engg.incharge.
e 112.00 Providing and fixing of approved make Clean 10705.16 Sq.mt.
room doors. Doors should be finished in
Powder Coating with thickness of 60 microns
approx. in desired Shades. The manufacturer
company must be ISO 9001-2015 certified.
The door frame is a Single rebate profile of
minimum size 105mm X 57 mm made out of
1.2 mm minimum thick galvanized steel sheet.
The frame is finished with Powder Coating in
desired Shade. Frame having provisions and
necessary Arrangement for receiving
appropriate hardware like lock and hinges.
The door leaf shall be a minimum 46mm thick
fully flush double skin door with vision lite of
DGU Glass of Size 300 x 300 mm x 6 mm .
The door leaf shall be manufactured from
mm thick galvanised steel sheet. Door
Includes SS 304 Hinges, D type Pull Handle-
SS 304, Mortise Deadlock with cylinder -
70mm both side key , Flush type tower bolt,
Door Seal , Door Closer etc. Complete as per
Standard Requirement.
f 20.00 Providing and fixing of approved make 27488.83 Sq.mt.
radiation-proof lead line door with galvanised
steel. Recommended lead door design should
be a sandwich-type panel with both sides GI
Sheet with a minimum 2mm Lead infill. Doors
should be finished in Powder Coating with
thickness of 60 microns approx. in desired
Shades. The manufacturer company must be
ISO 9001-2015 certified. The door frame is a
Single rebate profile of minimum size 105mm
X 57 mm made out of 1.2 mm minimum thick
galvanized steel sheet & with 2mm lead infill.
The frame is finished with Powder Coating in
desired Shade. Frame having provisions and
necessary Arrangement for receiving
appropriate hardware like lock and hinges.
The door leaf shall be a minimum 46mm thick
fully flush double skin door without vision lite.
The door leaf shall be manufactured from
mm thick galvanised steel sheet. Door
Includes SS 304 Hinges, D type Pull Handle-
SS 304, Mortise Deadlock with cylinder -
70mm both side key , Flush type tower bolt,
Door Seal , Door Closer etc. Complete as per
Standard Requirement.
53 Providing and fixing 35 mm th. Shutters for
doors windows & clearstory windows incl.
wood frames as specified 12 cm. x 7cm. size
incl. anodised alluminium fixtures and
fastenings including primer coat of approved
quality and two coats of oil paint etc.
a 3.00 Fully glazed 4788.50 Sq. M.
b 3.00 Fully panelled 5478.89 Sq. M.
c 3.00 Partly panelled and partly glazed 5133.69 Sq. M.
54 75.00 Providing and Fixing FRP FRAME size 125 x 1999.98 Sq.M.
65 mm and 35 mm thick FRP shutter with
wood grain raised pannel design finish shutter
having extra reinforcement on sides and
edges and in polish finish The core of the
shutter is to be filled up with injected fire
extingushing grade.polyurethane foam done
in situ along with embedded wooden pieces
for stiffering and also for tacking hinges and
fixtures. The whole FRP frame and shutter is
to be water proof.weather proof,tennite proof
and resistance to mild acid/ Alkali, Rates are
to be inclusive of S.S. hinges with necessary
screws and brass fixtures and fasening.
55 Making connection to the ex.M.H.in running
sewer incl. Dewatering and other required
machinery etc. of following dia pipes at any
convenient time. All damaged work shall be
well repaired as per instructions.
a 1.00 For Pipe 150 mm to 300 mm diameter 1339.29 No.
b 1.00 For Pipe 400 mm to 600 mm diameter 2232.14 No.
56 2.00 Making connection of galvanised Mild steel 600.08 No.
distribution branch with galvanised mild steel
main 50mm to 80mm nominal bore by
providing and fixing tee including cutting and
threading the pipes complete
57a 3800.00 Providing throating or plaster drip, grooves 41.25 Rmt
and moulding to Wall , R.C.C. chajja and slab.
57b 180.00 Providing & Laying cement vatta 10 cm x 10 23.45 Rmt
cm in size quarter round in c.m. 1:1 (
cement, 1 coarse sand) laid in one layers
finishing with a floating of neat cement
watering etc complete as dire.
58 950.00 Carring out plinth treat ment to post 104.09 Sq.mt
construction/ existing structure by spraying
chemical solution for termite control treatment
including labour and material consist ment
withI.S.I specification. Using Chlordene and
Chiorpur files 20EC. As Per 6131_ paret- II
Consentration Weight one percent is
recommended i.e one litre 20EC chemical
emulsion with19 liter give1% concrentration
inclusive of one litre chemical emulsion
appication at the rate of 5 Litre chemical/ Sqm
of surface is recommended as per I.S
59 10.00 Carring out timber treatment to all wood work 54.98 Smt
including drilling holes and spraying oil based
chemical solution on surface of timber work
for termite control including labour and
material etc. complete. Using Chlordene
20EC. As Per 6113_part III Consentration
Weight 1.00 percent is recommended one litre
chemical emulsion dillute with 9 liter of
kerosene precent concentration. Total dillute
concrentration will be10litre inclusive of the
litre chemical emulsion application 0.75/Litre
chemical per one Sqmt printed two coat wood
60 450.00 Paver Block Providing and laying shot blasted 758.93 Sq.mt.
Non - interlocking, Paver blocks of specified
thickness, size, grade of concrete and colour
machine made and blasting by automatic shot
blasting machine and high density of as per
approved sample of approved make for
footpath, parking areas, service lanes,cross
over and other areas as mentioned in the
drawing. Including providing and laying
mm thick averave bedding layer of coarse
sand below paver block as per required
grading and specification. Laid paver block
shall be mechanically compacted. The work of
the paving blocks shall be executed in line
and level by skilled mason of flooring work
only. Small size of paver block with same
specification shall be used at residue or at
end. It should be laid in such a way that the
no cutting of the paver block to be necessary.
If cutting of paver block shall be required
than cut by machine only and laying to be
done by skilled flooring mason. The finished
surface of the paver block shall have coarse
sand Texture Finish. Pave blocks shall be
compacted and shall be re-laid if necessary.
Actual laid area shall be measured and paid
without any wastage. (A) 80 mm thick M-35
grade Grey Paver block of size 200mm x
200mm. As per approved rate
61 350.00 Providing and fixing pre-cast concrete kerb 358.06 R.mt.
stone of gray cement based concrete block
30cm length,30cm height and 15cm thick of
M250 grade concret as per approved design
and including excavation for fixing in proper
line and level,filling the joint with C:M 1:3
(1cement:3fine sand) etc complete.
62a 40.00 Providing and fixing double action hydraulic 4558.89 No.
floor spring of approved brand and
manufacture conforming to IS : 6315, having
brand logo embossed on the body / plate with
double spring mechanism and door weight
upto 125 kg, for doors, including cost of
cutting floors, embedding in floors as required
and making good the same matching to the
existing floor finishing and cover plates with
brass pivot and single piece M.S. sheet outer
box with slide plate etc. complete as per the
direction of Engineer-in-charge. With stainless
steel cover plate minimum 1.25 mm thickness
b 60.00 Providing and fixing aluminium extruded 1626.10 No.
section body tubular type universal hydraulic
door closer (having brand logo with ISi, IS :
3564, embossed on the body, door weight
upto 36 kg to 80 kg and door width from
mm to 1200 mm), with double speed
adjustment with necessary accessories and
screws etc. complete.
63 180.00 Designing, fabricating, testing, installing and 3061.95 Sq.mt.
fixing in position Curtain Wall with Aluminium
Composite Panel Cladding, with open grooves
for linear as well as curvilinear portions of the
building , for all heights and all levels etc.
(a) Structural analysis & design and
preparation of shop drawings for pressure
equalisation or rain screen principle as
required, proper drainage of water to make it
watertight including checking of all the
structural and functional design.
(b) Providing, fabricating and supplying and
fixing panels of aluminium composite panel
cladding in pan shape in metalic colour of
approved shades made out of 4mm thick
aluminium composite panel material
consisting of 3mm thick FR grade mineral
core sandwiched between two Aluminium
sheets (each 0.5mm thick). The aluminium
composite panel cladding sheet shall be coil
coated, with Kynar 500 based PVDF /
Lumiflon based fluoropolymer resin coating of
approved colour andshade on face # 1 and
polymer (Service) coating on face # 2 as
specified using stainless steel screws, nuts,
bolts, washers, cleats, weather silicone
sealant, backer rods etc.
(c) The fastening brackets of Aluminium alloy
6005 T5 / MS with Hot Dip Galvanised with
serrations and serrated washers to arrest the
wind load movement, fasteners, SS 316 Pins
and anchor bolts of approved make in SS
316, Nylon separators to prevent bi-metallic
contacts all complete required to perform as
per specification and drawing The item
includes cost of all material & labour
component, the cost of all mock ups at site,
cost of all samples of the individual
components for testing in an approved
laboratory, field tests on the assembled
working curtain wall with aluminium composite
panel cladding, cleaning and protection of the
curtain wall with aluminium composite panel
cladding till the handing over of the building
for occupation. Base frame work cost for ACP
cladding is included in this item rate. The
Contractor shall provide curtain wall with
aluminium composite panel cladding, having
all the performance characteristics all
complete , as per the Architectural drawings,
as per item description, as specified, as per
the approved shop drawings and as directed
by the Engineer-in-Charge. However, for the
purpose of payment, only the actual area on
the external face of the curtain wall with
Aluminum Composite Panel Cladding
(including width of groove) shall be measured
in sqm. up to two decimal places.
64 Providing and Fixing Box type metal letters
forming composite box made from 1mm thick
stainless steel plate of grade 304 having
brush finish of following font size to be fixed at
Main Gate in english and or Gujrati and
including fixing charges. etc. complete as per
direction of Engg. incharge. for Payment
Purpose Height of Letter will be measured.
a 2160.00 Upto 300 mm Height 93.85 R. Inch
65a 15.00 Providing and Fixing MURAL made out of 6804.07 Sq.mt.
2mm thick s.s. plate grade 304, including
making necessary design as per Architect
dwg. Through laser cutting including
connection to the R.C.C./Masonary with
necessary frame,anchor fastnuts,M.S.Plate
etc. complete as per direction of Engg.
65b 28000.00 Providing and Fixing Sinage - internal and 9.38 Sq.Inch
external signage boards with Vinyle Text on
ACP sheet / 2 mm th. S.S. Plate etc. complete
as per direction of Engg. incharge.
65c 10.00 Providing and fixing retro Reflective Hi 7535.31 Sq.mtr.
Intensity Micro Prismatic Grade Board using
2mm Aluminum / 4mm ACP, angle iron 75 x
75 x 6mm. Descaling and degreasing the
board as per requirement using epoxy
reflactive process by screen painting as
directed etc. complete including transporting
and fixing in C.C. 1:2:4 with necessary
excavation curing etc. complete as per I.R.C.
67-2012 design. A warranty for 7 years for the
Retro reflective sheeting from original
manufacturer & a certified copy of 3 year
outdoor exposure test report from third party
test lab for the product offered shall be
submitted by contractor. (B)Class B Type-
4(MDR/ODR) retro reflective sheeting
65d 180.00 Road marking with hot applied thermoplastic 364.08 Sqmt
paints with reflectorising glass beads on
bitumin surface providing and laying a hot
applied thermoplastic compound 2.5 mm thick
including reflectorising glass beads @
250gms per sqm area, thickness of 2.5mm is
excluding of surface applied glass beds as per
IRC:35-2015. The finished surface to be level,
uniform and free from streaks and holes.
zebra patta /bump patta lane/center line/ edge
line/cut patta. The white color marking should
provide liminance coefficinet on cemend road
shalll be min 130 mcd/m2/lux and Asphalt
road shall be min 100 mcd/m2/lux during the
service life during the day time. The marking
should meet the performance criteria for night
time reflectivity, wet reflectivity and skid
resistance as mentioned in the section-15 of
IRC 352015. Warranty for the Retro reflectivity
should be two years.
65e 10.00 CAT EYE/Pavement Marker(MNC two nail) 160.71 Nos.
made out of acrylic StreneAcrylonitrile or hi-
impact poly Steren fitted with moulded of
metheacrylate(MNC)reflector cube corner
reflector design,filled with tightly adhering
pooting compound as per ASTMD-788 size
11.5x7x1.60 cms or 10x10x1.75 cms provided
with bituminous adhesive in sufficient quantity
with each unit fixing with two shrank .Reflector
on both side.Co efficient of lumination as per
specification and compressive strenth
tones at 23 degree centigrade etc.B) Double
66a 2610.00 Providing and fixing eco-friendly light weight 1632.63 Sq.mt.
calcium silicate false ceiling tiles having T
egular edge & 15mm Thick Densified edges
on the Tile Periphery for Extra Strength The
Light weight calcium silicate ceiling tiles shall
have, light reflection 85% non-combustible as
per B.S.476 part IV, 100% humidity resistance
and also having thermal conductivity 0.043°
w/m KC. for the best thermal Insulation.
The Light weight calcium Silicate tile shall be
of approved texture Fine fissured/ Spintone/
Cosmos having NRC value of 0.5 & Globe
having NRC value of 0.75 NRC or equivalent
of size 595X595 mm to be laid on true
horizontal level suspended inter locking metal
grid of hot dipped galvanized steel sections
(galvanizing @ 120 grams per sqm including
bothside) consisting of main ‘T’ runner
suitably spaced at joints to get required length
and size of 24X38 mm made from 0.30 mm
thick (minimum) sheet, 1200 mm centre to
centre, and cross ‘T’ of size 24X28 mm made
out of 0.33 mm (Minimum) sheet spaced
mm along spaced between main ‘T’ at
mm centre to centre to form a grid of
1200X600mm and secondary cross ’T’ of
length 600mm and size 24x28mm made of
0.30 mm thick (Minimum) sheet to be
interlocked at middle of the 1200X600mm
panel to form grid of size 600X600mm resting
on periphery walls / partitions on a perimeter
wall angle pre-coated steel of size
(24X24X3000mm made of 0.40mm thick
sheet with the help of rawl plugs at 450mm
centre to centre with 25mm long dry wall
screws @ 230mm interval and laying 15mm
thick Densified edges light weight calcium
silicate ceiling tiles of approved texture (Fine
Fissured/ Cosmos/Spintone) in the grid
including, cutting /making opening for services
like diffusers, grills, light fittings, fixtures,
smoke detectors etc., wherever required,
Main ‘T’ runners to be suspended from ceiling
using G.I. slotted cleats of size 25X35X1.6mm
fixed to ceiling with 12.5mm dia and 50mm
long dash fasteners, 4mm G.I. adjustable rods
with galvanized steel level clips of size
85X30X0.8mm, spaced at 1200mm centre to
centre long main ‘T’ bottom exposed with
24mm of all T-sections shall be pre-painted
with polyester baked paint, for all heights,
, as per specifications, drawings and as
directed by engineer-incharge.Note:- Only
calcium silicate false ceiling area will be
measured from wall to wall. No deduction
shall be made for exposed frames/ opening
(cut outs) having area less than 0.30 sqm.
The calcium silicate ceiling tiles shall have
NRC. Value of 0.50 (Minimum) for Fine
fissured/ Spintone/ Cosmos and 0.75 NRC for
Globe, light reflection 85% noncombustible as
per B.S. 476 part IV, 100% humidity
resistance and also having thermal
conductivity. 0.043° w/m KC.for the best
thermal Insulation
66b 1210.00 Providing and fixing single layer water proof 600.94 Sq.mt.
gypusm board 12.5 mm thick of the make
New good Group Co.Ltd. or equivalent & New
good Group Co.Ltd. company sections using
water proof board of size 1220 mm x
mm x 8.0 mm suspended by G.I suspender of
size 25 mm x 3 mm with intermediate channel
of size 18mm x40mm x0.80mm at 1220 mm
center to center ceiling section of size 40mmx
35mmx 0.55mm at 457 mm center to center
and perimetre chanel A of size 20mm x 27mm
x 30mm x 0.50mm at edges & drops including
paper taps and sofit cleat, anchor fastener,
scoch bolt connecting cleat joining compound
top coat on ceiling including making
necessary opening for light fitting, diffuser etc.
complete as per detail drawing as directed.
67 15.00 Providing and Fixing 6 mm thick Lexan 1427.62 sq.mt.
Polycarbonate multi wall roofing sheet fixed
with hilti screw and rubber silicon sealer and
alluminium strip of size 50 x 3 mm etc
complete as directed by Engineer in charge
68 Manufacturing,testing ,supplying
loading,,transporting to work site,loading
unloading lowering in trenches,laying and
jointing RCC NP3 class pipes in C:M 1:1
including all jointing materials such as
cement,sand,hemp bitumen as directed
testing the pipe line to a head of 1.5 mt and
hydraulic test as directed etc comp.
a 200.00 300 mm Diameter 616.07 Rmt
b 10.00 450 mm Diameter 806.25 Rmt
69 20.00 Constructing Bombay Pattern Type Catch Pit 3125.00 No
of size 0.60 x 0.60 depth up to 1 mt including
excavation, B.B.C.C. (1:5:10), 23 cms thick
brick maso. wall in the prop. of CM (1:6) with
40 mm thick IPS flooring in the prop M15 at
bottom and 15 mm thick cement plaster inside
the catch pit in the proportion of CM (1:3) with
out jali etc. comp. as directed.
70 20.00 CatchPit Jali Fixing P/F FRC catch pit jali with 1383.93 No
frame 600mm x 600mm clear opening etc.
comp.. As directed by engineer in charge.
PERCOLATION WELL
71 120.00 Drilling of pilot bore hole in Alluvial Strata by 694.64 Rmt
direct Rotary Rig of 250 mm.
72 120.00 Reaming 400 mm 212.50 Rmt
73 1.00 Electro Logging charges with carting 16071.43 Job
74 60.00 Providing and Installing 200 mm dia IS:12818 1193.75 Rmt
upvc Casing Pipe "CM" class plain Pipe
75 1.00 Providing and Installing 200 mm dia IS:12818 669.64 Set
upvc End Cap, with Air Vent cowl
76 60.00 200 mm dia Regular with 1.5 mm sloted size 1146.43 Rmt
cage type trapezoidal shape wire wound little
carbon galvanized screen confirming to
77 10.00 Supply of Pea sized Gravel 2029.46 Cmt
78 1.00 Air Vent of 50 mm Bend 401.79 Unit
79 120.00 Lowering and Removing of Dropline up to 147.32 Rmt
80 1.00 Air Compressor 60 CFM/150 PSI 22205.36 Ls
Estimate For Civil Work With Percolation Total Rs.
I. No. Qty Items Unit Rate Per Amount
1.1 1.00 Supply of 400 KVA Outdoor type Compact 1704007.00 SET
Substation consisting of Transformer,HT
switchgear and LT Switchgear and confirming
to IS/IEC 62271-202. a) Transformer:
KVA Copper wound 11kV /433 V DYn11, Dry
Cast resin type Transformer with tapping
range +10 to -10% @ 2.5% ( with tolerance),
class F , with surge restorers, Digital WTI,
IS/IEC 62271-202 as per b) HT Compartment:
11kV, 21kA for 3 Sec . 630 A 50 Hz, gas
insulated VCB in SS tank in sheet enclosure
having provision for one no. direct connection
of Incoming supply cable up to 300sq mm and
one no. VCB( Manually charging & closing) in
series with LBS between VCB and
Transformer, Self Powered Relay 3 O/C +1
E/F Relay type CSPR-V5, mechanical
ON/OFF indicator, trip coil , Manual Close &
Trip PB, live cable indicator, mechanical
interlocks, pad locking facility, SF6 gas
manometer, cable boots, 3 nos. CTs with
Ratio -/1A, Cl: 5P10, 2.5 VA for protection c)
LV side compartment : one no. MCCB of
630A, 36kA, 4Pole, Microprocessor based
release with arrangement for bottom cable
( 100% for phase & 50% for N, Current
density - 1A/ sq mm) The enclosure should be
of IK10 type.The Enclosure shall construction
shall be GI of thickness at least 1.6/2mm.The
enclosure shall be Powder Coated. Each
compartment will be provided with the door
and pad locking arrangement. The
Compartment illumination lamp with door
operated switch shall be provided for each
compartment. The Transformer compartment
will have IP-34 ingress protection, whereas
the HT/LT compartment will have IP-54
protection.The connection between HT and
Transformer shall be by 3 runs of single core
95 sq mm XLPE aluminium cable and
between Transformer to LT switchgear shall
be by appropriate rating Aluminium PVC
1.2 1.00 Supply,installation,testing and commissioning 494665.00 No
of outdoor 11KV, 800A HT Metering cubicle
panel ( HTMC )with VCB as per Technical
specifications No: UGVCL/R&D -
PP/TS/HTMC/001/R1 for outdoor installation.(
CTPT & Meter excluded ).
DIESEL GENERATING SET
1.3 Supply, Installation, Testing and
Commissioning (SITC) of Silent Type Diesel
Generating (DG) Set(s) of prime power rating
(kVA) as specified, complete as a packaged
system, conforming to CPCB IV+ (or better)
emission norms, and complying with all
applicable statutory requirements, codes and
standards including (but not limited to) IS
4722:1968, IS 13364 (Part 2) and BS
(latest editions/amendments). The DG set
shall be suitable for 415 V ±10%, 50 Hz ±5%,
3-phase, 4-wire operation at 0.8 lagging
power factor, 1500 RPM, for tropical
conditions, and shall be capable of delivering
10% overload for one (1) hour after twelve
(12) hours of continuous operation (ISO
8528), unless otherwise stated by the OEM.
The scope shall include complete
accessories, interconnections,
foundations/anti-vibration arrangements,
exhaust system, acoustic enclosure, earthing
(as required), consumables for first
commissioning, and all works necessary to
render the installation fully functional and
compliant, as directed by the Engineer-in-
Factory testing shall be carried out with fuel
and load bank at 0.8 power factor and the DG
set shall be offered for inspection prior to
dispatch. The DG set shall be provided with a
durable QR code/label fixed on the
enclosure/control panel, linking to a document
repository containing (as a minimum)
approved GA drawings, wiring diagrams,
foundation and installation details, OEM
catalogues, operating & maintenance
manuals, factory test reports, type test
certificates (where applicable), warranty
certificate, geo-tag of manufacturing location,
and rating plate data as per relevant
IS/BS/ISO requirements. The OEM/Contractor
shall provide a Remote Monitoring System
(RMS) with minimum one (1) year connectivity
(SIM/data plan/server access as applicable),
including dashboard access, user
ID/password, and data download facility. RMS
shall, at minimum, capture and report: DG
status (Auto/Manual/Off), start/stop events,
kW/kVA/kVAR, V/I/Hz, PF, run hours, fuel
level, battery voltage, alarms/trips with time
stamp, and GPS/location (where supported).
All licences/subscriptions required for the
stated period shall be included in the quoted
(A) DIESEL ENGINE:-
Turbocharged, 4-stroke, water-cooled, multi-
cylinder diesel engine, suitably rated for the
specified DG set prime rating at site
conditions, complete with dynamically
balanced flywheel, heavy-duty engine
mounting, and electric starting arrangement.
The engine governing shall be electronic
(isochronous/droop as per OEM standard)
and shall comply with ISO 8528/BS
requirements for steady-state speed
regulation. Engine shall be complete with dry
type air cleaner with restriction indicator, lube
oil cooler (if required), radiator/cooling
package (as applicable), and all
sensors/switches required for protections and
annunciation. The engine shall be capable of
10% overload for one (1) hour after twelve
(12) hours continuous operation and shall be
suitable for continuous duty under tropical
ambient conditions. The offered engine model
shall be CPCB IV+ compliant and shall be
supplied with complete emission control/after-
treatment system (including DEF/urea dosing
where applicable) along with all accessories,
tanks, pumps, heaters and controls required
for compliant operation. The supply shall
include first fill of lubricating oil, coolant and
consumables required for initial
commissioning and testing. All fasteners,
couplings, guards, hoses and
standard/recommended accessories required
for safe and reliable operation shall be
included and shall be subject to
inspection/approval by the EIC.
(B)Engine-Mounted
Instrumentation/ControlPanel:
Engine-mounted instrument/control panel
shall be microprocessor based, with LCD/LED
display, event log and alarm/trip annunciation,
complete with all wiring, harnesses and
terminations. Indications/protections shall
include (minimum) the following and any
additional protections recommended by the
OEM: (i) Start/Stop key switch and/or push
buttons with emergency stop; (ii) Output
breaker: suitably rated 4-pole
ACB/MCCB/MCB as applicable, with
minimum 25 kA rupturing capacity (or as per
fault level at site, whichever is higher), with
shunt trip where required; (iii) Jacket
water/coolant temperature – indication and
high temperature alarm/trip; (iv) Lube oil
pressure – indication and low pressure
alarm/trip; (v) Lube oil temperature (where
provided) – indication/alarm; (vi) Battery
charging indication, battery voltage indication
and charging failure alarm; (vii) Engine speed
(RPM) indication and overspeed trip; (viii)
Engine running hours meter (non-resettable);
(ix) Fuel level indication and low fuel alarm;
(x) Fail-to-start / crank fail alarm; (xi)
Under/over frequency and under/over voltage
protection (alternator side) as applicable; (xii)
Common alarm and common trip indication
with potential-free contacts for BMS/remote
annunciation. All meters/indications shall be of
proven industrial quality and the panel shall
be wired, ferruled and labelled. The contractor
shall submit wiring diagrams, protection
settings and datasheets for approval prior to
dispatch/installation.
Synchronous, brushless alternator of
appropriate kVA rating, 415 V, 3-phase,
Hz, 1500 RPM, 0.8 lagging PF, continuous
duty, dynamically balanced rotor, self-cooled,
self-excited and AVR regulated. Enclosure
shall be SPDP, minimum IP23. Insulation
shall be Class H with suitable tropicalization;
temperature rise shall be within limits of the
applicable standard. The alternator shall
comply with IS 13364 (Part 2), IS 4722 and/or
BS 2613 (latest), as applicable. Voltage
regulation with AVR shall be within ±1.0%
(steady state) or OEM standard whichever is
better. The alternator shall be capable of 10%
overload for one (1) hour after twelve (12)
hours of continuous operation. Harmonic
distortion shall be suitable for non-linear
loads; alternator shall be equipped with
appropriate AVR features (e.g., soft start,
UFRO) and shall be suitable for motor starting
duties typical to the installation. Terminals
shall be brought out to a terminal box with
adequate space for termination and shall
include earthing terminals. All routine/type test
certificates (as applicable) shall be submitted
for acceptance.
(D) Base Frame & Foundation: Engine and
alternator shall be mounted on a suitably
designed, fabricated MS channel base frame
with stiffeners, lifting arrangement and
coupling guard, duly painted/treated for
corrosion protection. The set shall be installed
on an adequately designed cement concrete
foundation/pedestal with anchor bolts,
pockets, grouting and anti-vibration mounts
(AVMs) / spring isolators as per OEM
recommendations and site conditions.
Vibration levels shall be within OEM
permissible limits. The contractor shall be
responsible for alignment, levelling, tightening
torque and re-check after load trial, complete
in all respects.
(E) Fuel Tank: In-built/base fuel tank
fabricated from minimum 3 mm thick MS
sheet, duly leak-tested, complete with filling
arrangement, vent, and drain, cleaning
opening, level indication and isolation valve.
The capacity shall be adequate for minimum
eight (8) hours continuous operation at full
load. Fuel piping between tank and engine
shall be MS ‘C’ class pipes of suitable
diameter with compatible flexible connections
(where required), complete with all valves,
clamps, supports, unions and fittings. Any
additional safety provisions required by local
fire authority/UGVCL/competent authority
(such as double wall/bunding, flame arrestor,
etc.) shall be provided within the quoted
(F) Exhaust System: Heavy-duty residential
type exhaust silencer suitable for CPCB IV+
installation (with DEF/after-treatment system
wherever applicable) along with exhaust
piping of required length, bends, supports and
flexible bellow, complete with rain cap, drain
arrangement and all accessories. Exhaust
piping shall be thermally insulated/lagged and
cladded where required to ensure personnel
safety and to limit heat radiation inside the DG
room/enclosure. The complete exhaust
arrangement shall be designed such that
engine exhaust back pressure remains within
OEM permissible limits and shall comply with
applicable statutory and safety requirements.
(G)StartingSystem
12 V / 24 V DC electric starting system (as per
OEM design) comprising starter motor(s),
battery charger/alternator charging
arrangement, relays, cabling and terminals,
complete with maintenance-free batteries of
suitable Ah capacity to ensure minimum three
(3) consecutive cranking attempts. System
shall include battery isolator and indication of
charging healthy/failure. All battery
interconnections shall be with crimped lugs,
insulated sleeves and proper supports,
complete in all respects.
(H) Acoustic and Weatherproof Enclosure:
Acoustic enclosure shall be factory-fabricated,
weatherproof and corrosion protected,
suitable for outdoor installation, with minimum
IP65 protection (or better) for the enclosure
body. Enclosure design shall provide
adequate fresh air intake and hot air
discharge for engine radiator and alternator
cooling such that the internal temperature rise
remains within OEM limits at full load.
Provision shall be made for safe
access/maintenance including lockable doors,
viewing window (where provided), emergency
stop access, and cable entry glands. Noise
level of the complete DG set with enclosure
shall not exceed 75 dB (A) measured at 1.0 m
distance in free field conditions, in accordance
with applicable CPCB requirements. The
enclosure shall comply with CPCB IV+ (or
better) requirements and other applicable
local rules/regulations. All louvers, acoustic
infill/insulation, fasteners and sealing
arrangements shall be of fire-
retardant/industrial grade as per OEM
standard. Any deviation from the specified
noise/IP requirements shall be treated as non-
compliance unless explicitly approved by the
EIC in writing.
Erection, testing, commissioning and
satisfactory performance demonstration shall
be carried out as per site requirements and as
directed by the Engineer-in-Charge. The
scope shall include pre-commissioning
checks, insulation resistance tests, no-load
and load trials, safety/protection checks, and
performance test on load bank (where
directed) with submission of test records. The
contractor shall provide initial consumables
including first fill of diesel fuel (minimum up to
80% of fuel tank capacity), lubricating oil,
coolant, etc. required for commissioning and
the specified tests. The bidder/OEM shall
provide comprehensive warranty/guarantee
for the complete DG system (engine,
alternator, control panels, RMS, enclosure
and all accessories) for a minimum period of
two (2) years from the date of
commissioning/handing over, whichever is
later, covering defects in materials and
workmanship. During warranty, all
spares/repairs/replacements and visits
required to maintain the DG set in serviceable
condition shall be carried out at no additional
cost. All necessary statutory approvals,
inspections, testing and certification from the
Electrical Inspector/competent authority
(including provision, testing and sealing of
energy meter(s) wherever applicable) shall be
arranged and obtained by the contractor
within the quoted scope and time, at no extra
cost. Required O&M manuals, as-built
drawings, warranty certificates and training to
operating staff shall be provided prior to
Note: The DG set specifications shall comply
with the latest CPCB guidelines/notifications
and all applicable local rules/regulations
prevailing as on the last date of tender
submission applicable local rules/regulations
prevailing as on the last date of tender
1.00 (R) Continuous rating of 250 KVA ,BHP not 2437870.00 E.a.
less than 309 BHP
Providing & erecting approved make ATS
panel suitable for following size of 3 phase,
415 V., 50 cycles, A.C. diesel generating set
complete of scope as detailed below:
1) Power module: Motorised Changeover
switch with ATS controller, Auxiliary contactor
with NO & NC contacts with Automatic Battery
Charger, indicating lamps for Generator ON,
Mains ON, Load and suitable control terminals
and power terminals with neutral earthing
1.00 (G) ATS Panel for 180 / 250 kVA 3 phase DG 90679.00 Each
1.4 STABILIZER AND UPS
1.4.1 1.00 Supply,installation,testing and commissioning 828600.00 No
of 300kVA 3-Phase servo controlled voltage
stabilizer suitable for 3 Phase unbalanced
Load (100% unbalanced load ) with individual
phase voltage correction ,Three separately
operated dimmer provided for 3 Phase
unbalance loads indoor type having input 3-
Phase 4 Wire,Output 3-Phase 4 Wire, Latest
as per IS 9815 ( PART-1)1994, Input Voltage
Range 380V-480V,Nominal output Voltage
415V ± 1% Output voltage can be changed to
380V/400V,Input Frequency Range 47Hz to
53Hz,Duty cycle 100% continous,Waveform
distortion Nil,Micr controller based True RMS
sensing and correction,Provided suitable RC
Network, Triac based drive for AC step
synchronous motor,Ambient Temp. range 0-
55 Degree celcius, Relative Humidity 95%
non dripping,Under and over voltage cut
offs,425A ,3-Phase OP contactorprovided to
Trip the stabilizer in various Faults,500Amp.of
IPMCCB provided for short Circuit
protection,Single phasing prevention and
Phase reversal Trip, 400A of OP COS
provided for stabilizer Bypass, Transient
suppression,Spike Suppression through
Phoenix SPD,Manual/Auto operation provided
with programmable time delay, 2 Line Digital
Display,Parameter Dislplated: Input and
Output voltage ( Line and Phase ),Neutral -
Earth Voltage,Output
currents,Frequency,Fault annunciation,
Transformer Oil Grade 40kVA confirming to
IS335 Oil capacity 720Litres Approx., Busbars
Terminations provided IP & OP
Cables,Provided CRCA sheet cabinet
fabricatedfree standing floor mounting with oil
cooled Tank is Hot rolled steel on castor
Wheel type dust and vermin proof closed
1.4.2 Supplying and erecting approved make
online Un-interruptible Power Supply system
comprising flat cum-boost charger with IGBT
base rectifier & Inverter & sealed
maintenance free SMF batteries. The charger
having operating capacity for input 160-270V
AC & inverter having output 230V,50 Hz Ac
with 0.8 load power factor with battery,
over/under voltage output with over load &
short circuit protection equipment. The system
housed in CRC sheet duly powder coated
paint with following power backup.with MS
painted batteries stand, 10% Overload
capacity for momentary load.
1.4.2a 1.00 [H} 10 kVA with 1Hr Backup 265597.00 E.a.
1.4.2b 2.00 (J) 20 kVA 3 - phase with 1Hr Backup 393391.00 E.a.
1.5 45.00 Providing and erecting ISI Marked 3core 120 1527.00 Mtr
Sq.mm XLPE insulated 11 KV armoured
cable Aluminium conductor to be laid on wall
with clamps or in provided cable trench / pipe
approved manner as directed.
1.6 2.00 Providing and erecting cable end 7925.00 No
terminatation kit, heat shrinkable Push on type
Densons/ Raychem/ Elastimold make suitable
for 11 KV XLPE cable 3core 95 & 120 Sq.mm
( INDOOR Type )
1.7 2.00 Providing printed instruction chart both in 129.00 No
English and Gujarati and duly framed with
front glasses, for treatment of person suffering
from Electric shock
1.8 1.00 Providing pair of rubber hand gloves suitable 212.00 No
for working on 11 KV/22 KV supply.
1.9 10.00 Supplying rubber matting of following
thickness as per IS:15652/IEC
1.10 2.00 Supplying stand first AID box with antiseptic 297.00 No
cream, medicine for use on wounds due burn,
crepe bandage, gauge bandage, medicated
ready to use bandage (Band-aid) adhesive
tape for medicinal user, Scissors, anti-septic
solution (Savlon or similar) etc. (All above
contents shall be of standard makes)
1.11 3.00 Supplying FIRE bucket round bottom of 9 212.00 No
litres capacity made out of 24 gauge G.I.
sheet with extra handle at bottom duly painted
white inside and Red out side with FIRE
mark, filled with dry-sand and kept on existing
stand provided or hung on wall hook.
1.12 2.00 Supplying and erecting floor mounting stand 933.00 No
for keeping four nos. of FIRE buckets
comprising 1500 mm in length, 900 mm
height frame made out of 30mm X30 mm X
mm angle iron with cross supports for legs,
welded with 4 hooks and duly painted with
one coat of red lead and two coats of
approved enamelled silver paint.
1.13 2.00 Wall hook 22 to 25 cms. projection for keeping 60.00 No
fire buckets made out of 15 mm dia. M.S rod
grouted in wall to a depth of minimum 15 cms.
SUB - TOTAL OF HT WORK
2 INTERNAL WIRING
2.1 Point wiring for Light / Bell with 2-1.5 sq.mm
& earth wire of 1.5 sq.mm (Green) both are of
ISI marked 1.1 KV grade ZHFR/HRFR PVC
insulated multi strand copper wires up to
mtr length , in below type of pipe erected with
6A Modular type switch / bell push &
accessories and earth continuity of following
type, erected on PVC / Metallic/Wooden box,
single mounting base frame covered with
textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe
erected, with necessary Lamp holder/ceiling
rose / H.D.Connector as directed.
545.00 (f) with medium class Rigid PVC pipe and 605.85 Pt
accessories erected concealed in wall/ceiling
2.2 Point wiring for FAN with 2-1.5 sq.mm &
earth wire of 1.5 sq.mm (Green) both are of
.ISI marked 1.1 KV Grade ZHFR/HRFR PVC
insulated multi strand copper wires up to
mtr length, in below type of pipe erected with
6A Modular type switch and hum free EME
four or more step type electronic fan regulator
with separately mounted and accessories
with earth continuity of following type erected
on PVC / Metallic/Wooden box, single
mounting base frame covered with
textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe
erected. with necessary ceiling rose /
H.D.Connector as directed.
250.00 (f) with medium class Rigid PVC pipe and 841.05 Pt
accessories erected concealed in wall/ceiling
2.3 Point wiring for secondary light point with 2-
1.5 sq.mm & earth wire of 1.5 sq.mm (green)
both are of ISI marked 1.1 KV grade
ZHFR/HRFR PVC insulated multi strand
copper wires, in below type of pipe to be
erected complete with earth continuity and
necessary connection with primary light with
accessories erected on Metal / PVC /
wooden box covered covered with appropriate
front plate modules erected on / in wall /
ceiling for open / concealed wiring. with
necessary Lamp holder / ceiling rose /
H.D.Connector as directed.as per pipe
erected with following type of accessories.
Note:- Maximum up to 6 mtrs length, excess
will be considered as Mains for Secondary
405.00 (f) with medium class Rigid PVC pipe and 208.95 Pt
accessories erected concealed in wall/ceiling
2.4 Point wiring for Individual Plug with & earth
wire of 1.5 sq.mm (Green) both are of ISI
marked 1.1 KV grade ZHFR/HRFR PVC
insulated multi strand copper wires up to
mtr length, in below type of pipe erected
complete with Modular type switch & 5 pin
Plug erected on PVC / Metallic/Wooden box
covered with appropriate front plate modules
erected on / in wall / ceiling as per pipe
erected with following type of accessories.
2.4.1 240.00 [I] For 6A Plug and 6 a switch with 2-1.5 636.30 Pt
sq.mm Cu. Wire from nearby
switchboard/mcb db board
(f) with medium class Rigid PVC pipe and
accessories erected concealed in wall/ceiling
2.4.2 145.00 [II] For 16A Plug and 16 amp switch with 2- 930.30 Pt
2.5 sq.mm Cu. Wire from mcb db board.
(f) with medium class Rigid PVC pipe and
accessories erected concealed in wall/ceiling
2.4.3 45.00 [III] For 16A Plug and 16 amp switch with 2-4 1087.80 Pt
sq.mm Cu. Wire with 2.5 sq.mm ( green)
earthing wire from mcb d b board.
(f) with medium class Rigid PVC pipe and
accessories erected concealed in wall/ceiling
2.5 370.00 Point wiring for on board Looped Plug with 6A 306.00 Pt
Modular type switch & 5 pin socket erected on
PVC / Metallic/Wooden box, single mounting
base frame covered with textured /
metallic/white front plate modules erected on
/ in wall / ceiling with following type
2.6 Point wiring for Two Way Controlled Light
Point with 2-1.5 sq.mm & earth wire of
sq.mm (green) both are of .ISI marked 1.1 KV
grade ZHFR/HRFR PVC insulated multi
strand copper wires erected in below type of
pipe with 6A Modular type switches and
following type of accessories erected on PVC
/ Metallic/Wooden box, single mounting base
frame covered with textured / metallic/white
front plate modules erected on / in wall /
ceiling as per pipe erected. with necessary
batten/angle holder or ceiling rose or
H.D.Connector as directed.
18.00 (f) with medium class Rigid PVC pipe and 753.90 Pt
accessories erected concealed in wall/ceiling
2.7 Providing following type of Modular Type
Accessories mounted with PVC /
metallic/Wooden box, single mounting base
frame covered with textured / metallic/white
front plate , modules erected with necessary
connections as per site situation directed by
Engineer In charge.
2.7.2 85.00 (2) One No 5 pin plug 150.00 E.a.
2.7.3 140.00 (7) Blank Plate Single 25.00 E.a.
2.7.4 80.00 (9) 16 Amp. SP one way switch 179.00 E.a.
2.7.5 80.00 (10) 6/16Amp. Universal socket 198.00 E.a.
Modular MCB Switch
Pole Modular MCB Switch
2.8 Providing and erecting ISI mark Medium class
RIGID PVC PIPES of following size complete
to be erected on/in wall or ceiling erected with
necessary PVC fittings & Junction boxes fixed
with adhesive solution & Clamps with
following dia of pipes, in approved manner as
2.9 Providing & erecting PVC Corrugated Flexible
Conduit with required nos. of coupling, PVC
bushes, Check-nuts etc. complete of following
2.10 providing and erecting Mains with ISI marked
electrolyte stranded copper conductor, Non
PVC Zero Halogen free fire retardant
insulated copper conductor, insulated wire
(HRFR) conforms to IS-694, erected in
existing pipe with 1.5sq. mm copper
conductor of same specifications for earth
continuity of following size.
In Existing medium class Rigid PVC pipe and
2.11 providing and erecting Mains with 1.1 KV
grade FRLS PVC insulated ISI marked
stranded Copper conductor wire in following
type of pipe to be erected in / on wall / ceiling
with 2.5 sq. mm copper conductor FRLS PVC
insulated stranded wire of green colour for
earth continuity of following size
(A) with medium class Rigid PVC pipe and
(use earth wire of 4 sq.mm )
2.12 providing and erecting Mains with ISI marked,
1.5KV grade electrolyte multi stranded,
annealed copper conductor with heat resistant
PVC insulated conforms to IS 694, IEC -
erected in existing pipe of following size
(Specifically for control panel, relays, power
switchgears, motor starters & control wiring)
with required size of copper lugs, nuts and
bolts if required.
2.12.1 60.00 (d) One wire 4.00 sq. mm 47.00 Mtr
2.12.2 20.00 (e) One wire 6.00 sq. mm 70.00 Mtr
2.12.3 140.00 (f) One wire 10.00 sq. mm 114.00 Mtr
2.12.4 80.00 (g) One wire 16.00 sq. mm 176.00 Mtr
2.12.5 20.00 (h) One wire 25.00 sq. mm 293.00 Mtr
2.12.6 10.00 (k) One wire 70.00 sq. mm 829.00 Mtr
2.13 Supplying and erecting Flexible PVC insulated
multi strand multi core 1.1 kv grade ISI
marked copper wires of following size to be
erected as directed.
2.13.1 130.00 e) 1.50 Sq.mm 3 core round PVC sheathed 58.00 Mtr
2.13.2 90.00 h) 2.50 Sq.mm 3 core round PVC sheathed 97.00 Mtr
2.13.3 55.00 k) 4.00Sq.mm 4 core round PVC sheathed 219.00 Mtr
2.14 Supplying & erecting M.S. Box having
Gauge painted with red oxide or Heavy duty
PVC box erected flushed on wall or concealed
in wall with necessary plastering & finishing as
directed of following size.
2.15 Supplying and laying UPVC cable trunking
system comprising unplasticised polyvinyl,
chloride rigid material with ignition free and
flame proof confirming BS with necessary end
caps Internal and external bend, flat bends,
coupler, tee etc..All necessary accessories
and measuring of following sizes
2.15.1 10.00 (2) 100 mm x 50 mm trunking 424.00 Mtr
2.15.2 10.00 (4)100 mm x 50 mm trunking with TWIN 1309.00 Mtr
compartment With clip in divider
2.16 Supply & installation of surface mounted U
PVC snap-on adaptable trunking raceways,
fabricated out of U-PVC to Off-White or
approved shade as per IS 733 of thickness
2.0mm for the base and sides with all
accessories like removable covers, joints
,height spacer,angles complete with
necessary bends, suitable sized junction
boxes and tees etc, Complete.
10.00 (a)Size: 50x80mm PVC Raceways for Power 1052.00 Mtr
& Data with 2 compartments above
specifications.
2.17 Supply & installation of modular type
accessories for U PVC snap-on adaptable
trunking/Pop up Box with required items
erected with necessary connection. As
desired by Engineer In charge
2.17.1 2.00 i) 6 A SP 1 Way Switch 204.00 No
2.17.2 2.00 ii) 16A SP 1 Way Switch 351.00 No
2.17.3 2.00 iv) 6A universal socket shuttered 347.00 No
2.17.4 2.00 iv) 6/16 A universal socket shuttered 458.00 No
2.18 Supplying & erecting 20 Amp 10 KA ‘C
Curve’ single pole MCB with 20 Amp. Plug
socket, company fabricated powder coated
sheet steel enclosure erected as directed with
8.00 [A] Metal Clad Socket with metal clad top 574.00 E.a.
2.19 1.00 Providing & erecting insulated socket 3P+N+E 2169.00 E.a.
with Plug 32A rating which is comprised of
Four pole MCB slot and insulated socket IP40
SUB - TOTAL OF INTERNAL WIRING
3 Switchgears , Panels , MCBDBs & MCBs
Design, fabrication, assembling, supply,
installation, testing and commissioning of
cubicle type, wall / Floor mounted LT panel
suitable for 415 V 3 phase, 4 wire 50 Hz AC
supply system fabricated in compartmentised
design from CRCA sheet steel of 2 mm thick
for frame work ,Doors and partitions IP 42 and
covers,3 mm thick for gland plates i/c cleaning
and finishing complete 9 tank process in
house facility for powder coating in approved
shade, extendable type FP aluminium alloy
busbars of high condectivity, DMC/SMC
busbar supports, entire panel shall have a
common copper earthbar of size 25mm X
mm / 50 x 6mm al earth bar at the rear with
Nos. earth studs, solid connection from main
busbar to switchgears with require size of
aluminium busbar & control wiring with
sqmm FRLS insulated copper conductor
cable, cable alleys, cable gland plates i/c
accessrories as per specification and
providing switchgears, metering instruments
etc. for following panel.G.A.Drawing to be
approved by EIC or consultant. ( Outgoing
connectors must be nut-bolt type. Outgoing
mains for 63Amp MCBs must be of 4 x
16sqmm cu flexible wires).Incomers Mains for
MCBs shall be always from the busbars.
( a ) Providing cable clamps / supports within
distribution boards cable alley.
( b ) All hinged door shall be earthed through
2.5 sq mm tinned b raided copper wire.
( c ) Pad locking of MCCB’s handles in “OFF”
( d ) All the C.T.s should be auto short link
( e ) All the MCCB's should be with rotary
( f ) All incoming and outgoing air circuit
breakers shall be placed on middle portion of
the vertical in single tier formation.
( g ) Any descripancy found in SLD & Boq , it
should be brought in the notice of the client /
consultant, and the decision will be taken final
by Client / consultant.
3.1 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 50 K.A. and above
at 415 V having normal current rating up to
630A. with Microprocessor release suitable to
work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
housing . Overload release range 158-630A.
confirms to IS/IEC 60947-2.
1.00 ICS=100% of ICU only 41424.75 No
3.2 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. and above at
415 V . having normal current rating 250A.
with variable thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
1.00 ICS=100% of ICU only 20739.00 No
3.3 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
Microprocessor Release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
4.00 ICS=100% of ICU only 23850.45 No
3.4 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having normal current rating 125A. with Fixed
thermal & magnetic release suitable to work
on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
13.00 ICS=100% of ICU only 8774.00 No
3.5 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 25 KA. at
V,having normal current rating up to 25 A to
100A. with Fixed thermal & magnetic release
suitable to work on A.C. supply 50 c/s. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
16.00 ICS=100% of ICU only 6723.00 No
3.6 Providing and erecting Approved make Three
pole moulded case circuit breaker having
breaking capacity/strength ICU of 35 K.A. and
above at 415 V. having Normal current rating
200A.with variable Thermal & magnetic
release suitable to work on A.C.supply 50 c/s.
with all internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing.
1.00 ICS=100% of ICU only 16963.00 No
3.7 providing and erecting Approved make Earth
fault Relay suitable to mount with inter
connection suitable to following size of
moulded case circuit breaker having CT ratio
& MCCB rating as following along with shunt
trip 220V AC. with all internal connections &
complete erected in existing M.S.housing..
3.8 350.00 Fabricating the box type items made from 179.00 Kg
M.S. Sheet with A.I. supports, wings, doors,
handles other hardware materials as per
requirement design with finishing by three
tank powder coating processed inside and
outside painted, erected as directed including
minor civil work. to install above MCCB.
3.9 30.00 providing and erecting Miniature circuit 295.00 No
breaker single pole 0.5A to 2A system and
having breaking capacity 10 KA to be erected
in existing box. confirming to IS 8828/1996
3.10 20.00 providing and erecting Miniature circuit 122.00 No
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996 with
3.11 Providing & erecting 240 V MCB double pole
switch for motor & inductive load (C Curve)
having 10 KA breaking capacity & confirms to
IS : 8828 in existing box having following
3.12 Providing & erecting 415 V MCB Four Pole
for Motor & Inductive Load (C Curve) having
10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
3.13 Providing & erecting 415 V MCB three Pole
for Motor & Inductive Load (C Curve) having
10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
3.14 Providing and erecting Approved make
RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for
operation on single phase 240 V,50Hz. having
characteristic of quick action & tripping with all
advance feature & do not incorporate any
electronic component. for following Max.
rating erected as directed
3.00 (ii) 40Amps. DP 2434.00 No
3.15 Providing and erecting Approved make
RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for
operation on 3 phase and neutral 415V,50Hz.
having characteristic of quick action & tripping
with all advance feature & do not incorporate
any electronic component for following Max.
rating erected as directed.
3.16 Providing and erecting following additional
parts for panel mounting MCCBs
3.16.1 35.00 (A)Extended operating rotary handle with pad 952.00 No
lock with three position trip,off,on suitable for
25A to 250 A panel mounting cat-III
3.16.2 2.00 (B)Extended operating rotary handle with pad 1428.00 No
lock with three position trip,off,on suitable for
400A to 630 A panel mounting cat-III
3.17 8.00 Supplying and erecting approved make panel 1263.00 No
mounting type Digital Voltmeter having
digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.
3.18 8.00 Supplying and erecting approved make panel 1543.00 No
mounting type Digital Ammeter having
digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to
operate on 500 Volt AC , erected on existing
panel board with all connection, wiring etc
.with manufacturers calibration certificate.
3.19 16.00 Supplying and erecting Ammeter / Voltmeter 314.00 No
selector switch for 3 phase AC Supply 500 V
on existing panel board with necessary
3.20 45.00 Providing & erecting L.T. Current 272.00 No
Transformer with bar primary 50/5 to 1000/5
ratio 15 VA burden erected in existing CRCA
box duly secured with insulating materials
connected to the meter
3.21 2.00 Supplying & erecting approved make Power 5052.00 No
Factor Meter 150mm dia flush/projection type/
balanced & unbalanced load to work with
appropriately provided CT’s 100/5A to 400/5A
ratio & other accessories complete erected in
M.S. box & connected to the circuit by means
of PVC copper Core leads.
3.22 60.00 Supplying and erecting approved make 43.00 No
suitable panel indicator LED type lamp, lens
cover, complete erected with necessary
3.23 8.00 Providing and erecting metallic vitrified danger 69.00 No
notice board as per language suggested by
engineer incharge for MEDIUM VOLTAGE
installation to be erected as per IS-2551.
3.24 25.00 Providing and erecting required size 223.00 KG
Aluminium strip for earthing of H.T. , OCB /
ACB / Transformer, LT panel board, Motors
etc. using copper clamp.
3.25 10.00 Providing and erecting required size Copper 787.00 Kg
strip for earthing of H.T. OCB / ACB/
Transformer, LT panel board, Motors etc.
using copper clamp.
3.26 5.00 providng and erecting Approved make energy 2179.00 No
meter 3 phase 4 wire unbalanced load 500 V.
5 to 10A complete erected as directed with
necessary earth wire.Class-1
3.27 450.00 Providing , erecting , fabricating the M.S. 77.00 Kg
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one coat
of red oxide with erection on site as per
direction of engineer in charge with necessary
grouting, cementing, plastering & finishing
3.28 Supplying and erecting triple pole & neutral
440V/ 500V panel mounting Aluminium
Busbars with four equal Nos. of bus having
current density not more than 0.8 Amp. /
sq.mm (Rated current / cross section area)
duly wrapped with colour insulating tape for
phase sequence of following current carrying
capacity, erected with necessary bus bar
supports /insulators, main cable socket to
each busbar,erected in existing cubical panel
with necessary connections.
3.28.1 28.00 (A) Suitable for 100 Amp. Capacity 654.00 RnMtr
3.28.2 16.00 (B) Suitable for 200 Amp. Capacity 1027.00 RnMtr
3.28.3 1.00 (C) Suitable for 300 Amp. Capacity 1455.00 RnMtr
3.28.4 18.00 (E) Suitable for 630 Amp. capacity 3031.00 RnMtr
3.28.5 1.00 (F) Suitable for 800 Amp. capacity 6179.00 RnMtr
3.29 Supplying and erecting triple pole & neutral
440V / 500V panel mounting Copper Busbars
with four equal Nos. of electrolyte bus having
current density not more than 1.6 Amp. /
sq.mm (Rated current / cross section area)
duly wrapped with colour insulating tape for
phase sequence of following current carrying
capacity, erected with necessary bus bar
supports /insulators, main cable socket to
each bar, erected in existing cubical panel
with necessary connections.
12.00 (A) Suitable for 100 Amp. Capacity 1942.00 RnMtr
3.30 Providing & erecting weather proof, dust &
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per approval
from engineer incharge made from 14 SWG
thick CRC M.S. sheet for outer body & doors,
16 SWG thick CRC M.S.sheet for internal
partitions with necessary accesories
supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with
internal partitions & cable alley as per
requirements & instruction of engineer-in-
charge with erection of
supplied switch gears, BUSBARS, suitable
size of inter connecting PVC copper wire /
copper-aluminium strips, rubber grommets,
rib, bakelite control fuses/MCB for measuring
instruments, earth bus & earth bolts,
foundation flange - bolts-base Plates,
sufficient nos. of hinged doors, handles with
locking arrangement and rubber gasket,heavy
duty end terminal connection,danger notice
board,necessary ventilation,earthing strip
complete. The Panel shall be painted with
epoxy powder coating.
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with
following approved manufacturers with
following size.
(B) The standard companies switch gear shall
be used and only manufacturers at CPRI
approved factory
18.00 (i) with 350mm depth 14755.00 Sqmtr
3.31 Providing & erecting weather proof, dust &
vermin proof, floor mounted front operated
outdoor type double door cubical panel board
necessary IP-54 and above protection as per
approval from engineer incharge made from
14 SWG thick CRC M.S. sheet for outer body
& doors, 16 SWG thick CRC M.S.sheet for
internal partitions with necessary accesories
supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with
internal partitions & cable alley as per
requirements & instruction of engineer-in-
charge with erection of
supplied switch gears, BUSBARS, suitable
size of inter connecting PVC copper wire /
copper-aluminium strips, rubber grommets,
rib, bakelite control fuses/MCB for measuring
instruments, earth bus & earth bolts,
foundation flange - bolts-base Plates,
sufficient nos. of hinged doors, handles with
locking arrangement and rubber gasket,heavy
duty end terminal connection,danger notice
board,necessary ventilation,earthing strip
complete. The Panel shall be painted with
epoxy powder coating.
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with
following approved manufacturers with
following size.
(B) The standard companies switch gear shall
be used and only manufacturers at CPRI
approved factory
1.00 (i) with 350mm depth 16162.00 Sqmtr
3.32 Supplying & erecting XLPE(IS:7098)(I)-88 ISI
unarmoured copper cable 1.1 KV grade to be
erected as directed of following size.
3.33 providing and erecting Mains with ISI marked,
1.5KV grade electrolyte multi stranded,
annealed copper conductor with heat resistant
PVC insulated conforms to IS 694, IEC -
erected in existing pipe of following size
(Specifically for control panel, relays, power
switchgears, motor starters & control wiring)
with required size of copper lugs, nuts and
bolts if required.
3.33.1 270.00 (a) One wire 1.00 sq. mm 16.00 Mtr
3.33.2 310.00 (b) One wire 1.50 sq. mm 22.00 Mtr
3.33.3 225.00 (c) One wire 2.50 sq. mm 34.00 Mtr
3.34 Design, Supplying, installing, testing of factory
fabricated ready made Three phase APFC
Panel Cubical Panel fabrication should be
type tested as per IEC 61921, 61439:1&2
Capacitor Duty Contactor for switching as per
following Steps Incomer Switch of MCCB type
Icu=Ics=50KA at 400/440 Volts, with OC, SC,
internal earth fault protection Incomer Switch
of MCCB type Icu=Ics=50KA at 400/440 Volts,
with OC, SC, internal earth fault
protection,Copper tinned insulated
Busbar,Cubical panel should be indoor type
with IP 43 and IK 10,Metalized polypropylene
film tye3-phase 528/550Volt Capacitor,De
tuning Reactor for each capacitor,Panel
having Short Circuit and Overload
protection,Each step Capacitor having
suitable MCB with Sc, OL, internal earth fault
relay,Each stage having Stage Contactor
(Capacitor load rating),PF regulator master
controller having suitable steps with LCD
display, Rs 485 Communication port,
Indication LED Lamps for main incomer and
ON-OFF for each capacitor bank,MS Chanel
for Floor mounting, Cable entry as per site
situation,Cooling fans for panel
3.35 Supplying & erecting approved make IP
grade Company fabricated Timer Panel of
following capacity for switch On-Off street
lights on time scheduling basis made from
16G CRCA sheet duly epoxy power painted
inside and outside with hinged doors and
locking arrangement consisting of suitable
size of 4 Pole MCB and 4 pole contactor (cat-
III)with analog time switch, auto manual
switch of same make and suitable input and
output Bakelite terminals and with door
earthing approved by Engineer in charge.
MCBDBs and MCBs
3.36 510.00 providing and erecting Miniature circuit 122.00 E.a.
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996 with
3.37 Providing & erecting 240 V MCB double pole
switch for motor & inductive load (C Curve)
having 10 KA breaking capacity & confirms to
IS : 8828 in existing box having following
3.38 Providing & erecting 415 V MCB Four Pole
for Motor & Inductive Load (C Curve) having
10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
3.39 6.00 Sheets steel powder coated enclosure 175.00 E.a.
suitable for incorporating One/Two nos. MCB.
3.40 Providing and erecting Sheet Steel powder
coated MCB distribution board - flush /
surface mounted fitted with busbar, neutral
link, earth bar and DIN rail, Conforms to IS
8623-1 & 3, IEC 61439-1 & 3 without MCB to
house appropriate nos. of MCBs.(The DBs
should be used of same company of MCB to
be used) suitable for
(A) single phase incoming and horizontal
single phase outgoing
(b) sheet steel double door (IP-43)
3.40.1 4.00 (i)4 way ( concealed manner ) 747.60 E.a.
3.40.3 25.00 (iii)8 way ( concealed manner ) 1369.20 E.a.
3.40.5 3.00 (iv)12 way ( concealed manner ) 1773.60 E.a.
3.41 (B) three phase incoming and single phase
horizontal type outgoing Per phase isolation
(b) sheet steel double door
3.41.1 5.00 (i)4 way ( concealed manner ) 2779.20 E.a.
3.41.3 14.00 (ii)6 way ( concealed manner ) 3462.00 E.a.
3.41.5 12.00 (iii)8 way ( concealed manner ) 4054.80 E.a.
3.42 Providing and erecting Sheet Steel powder
coated Vertical MCB distribution board
(VTPN) - flush / surface mounted double door
(IP54) fitted with insulated copper busbar,
isolated neutral link, earth bar and DIN rail,
confirming to IS 13032 and BS 5486-1986,IP-
54 suitable for 63/100 AMP TPN MCCB +
RCCB as incomer and three phase outgoing
as per following .(The DBs should be used of
same company of MCB to be used)
3.42.1 6.00 (A)4 way outgoing 9925.00 E.a.
3.42.2 1.00 (B)6 way outgoing 12061.00 E.a.
3.43 Providing and erecting Sheet Steel powder
coated Vertical MCB distribution board
(VTPN) - flush / surface mounted double door
(IP54) fitted with insulated copper busbar,
isolated neutral link, earth bar and DIN rail,
confirming to IS 13032 and BS 5486-1986,IP-
54 suitable for 250 AMP TPN MCCB +
RCCB as incomer and three phase outgoing
as per following .(The DBs should be used of
same company of MCB to be used)
1.00 (A)4 way outgoing 13315.00 E.a.
3.44 Providing & erecting 415 V MCB three Pole
for Motor & Inductive Load (C Curve) having
10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
3.45 Providing and erecting Approved make Three
pole moulded case circuit breaker having
breaking capacity ICU of 25 K.A. at 415 V
having normal current rating up to 25 A to
100A. with Fixed thermal & magnetic release
suitable to work on A.C. supply 50 Hz. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
6.00 ICS=100% of ICU only 5832.00 E.a.
3.46 Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
Microprocessr release having Overcurrent
Range 40-160A suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
2.00 ICS=100% of ICU only 23850.45 E.a.
3.47 providing and erecting Approved make ELCBs
/ RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for
operation on single phase 240 V,50Hz. having
characteristic of quick action & tripping with all
advance feature & do not incorporate any
electronic component. for following Max.
rating erected as directed
3.48 Providing and erecting Approved make
RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for
operation on 3 phase and neutral 415V,50Hz.
having characteristic of quick action & tripping
with all advance feature & do not incorporate
any electronic component for following Max.
rating erected as directed.
3.49 30.00 Providing and erecting metallic vitrified danger 69.00 E.a.
notice board as per language suggested by
engineer incharge for MEDIUM VOLTAGE
installation to be erected as per IS-2551.
3.50 42.00 Providing & erecting Medium Voltage Danger 26.00 E.a.
Notice Board sticker as per language
suggested by engineer incharge of standard
size as per IS-2551
SUB - TOTAL OF Switchgears , Panel and
Follow IS code :3043 is the guideline for
4.1 850.00 Providing and erecting required size HOT 77.00 KG
deep Galvanised iron strip for earthing of H.T.
, OCB/ ACB/ Transformer LT panel board,
Motors etc. using proper clamp.
4.2 130.00 Providing and erecting required size Copper 787.00 KG
strip for earthing of H.T. OCB / ACB/
Transformer, LT panel board, Motors etc.
using copper clamp.
4.3 20.00 Providing and erecting Annealed bare Copper 787.00 KG
wire 8 to 16 SWG.
4.4 110.00 Providing and erecting HOT deep Galvanised 77.00 KG
iron strip wire 8 to 16 SWG.
4.5 4.00 Providing and erecting Pipe type earthing with 815.00 E.a.
40 mm dia 2.5 mtr long 'B' grade G.I. pipe with
necessary coupling buch buried in specially
prepared earth pit & G.I. earth wire of 8 SWG
erected & connected as directed (For panel)
4.6 4.00 For using salt and charcoal / coke as required 170.00 E.a.
for pipe type earthing.
4.7 Supplying & erecting earth pit of minimum
bore dia.150mm size approved make Earthing
Electrode consisting Pipe-in-Pipe Technology
as per IS 3043-1987 made of corrosion free
hot dipped G.I.Pipes having Outer pipe dia of
50mm having 80-200 Micron galvanising,
Inner pipe dia of 25 mm having 200-250
Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded
by highly conductive compound with high
charge dissipation suitable for following type
of applications with chamber and heavy duty
cover.(approved make OEM has to submit
test certificate) & having back filling
compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 W/ meter testing
as per IEC 62561-2017, Voltage drop:- <
volt at no load & dry form, Sulphar content:-
<2%(C) Back fill Compound :- Earthing
compound should be capable to retain
moisture for long time Necessary test report
must be submitted.
4.7.1 2.00 (a) For Electrical Installation up to 440V in 4546.00 E.a.
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
4.7.2 14.00 (c) For Electrical Installation covering 8551.00 E.a.
Transformer Neutrals, Lightning arrester
Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e
independent Earthing in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of 25 Kg.
4.8 Supplying & erecting in earthpit of minimum
bore dia. 225mm size approved make Safe
Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of
corrosion free hot dipped G.I.Pipes having
Outer pipe dia of 80 mm having 80-200
Micron galvanising, Inner pipe dia of 40 mm
having 200-250 Micron galvanising,
connection terminal dia of 14 mm with
constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications with chamber and heavy duty
cover (A)(approved make OEM has to submit
test certificate including value of earth
resistance of installation duly stamped and
signed by agency and officer Incharge has to
ensure the value of earthing resistane
mentioned in test Certificate) & having back
filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter
testing as per IEC 62561-2017, Voltage drop:-
< 1 volt at no load & dry form, Sulphar
content:- <2%(C) Back fill Compound :-
Earthing compound should be capable to
retain moisture for long time Necessary test
report must be submitted by Agency.
16.00 [C] For Electrical Installation covering 10489.00 E.a.
Transformer Neutrals, Lightning arrester
Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA)i.e.
independent Earthing located in other than
normal soil i.e. Soft Rock, Marshy Soil etc..
-Length of Pipe : 3 Mtrs.
-Back filling Compound :2 nos Bags of 25 Kg.
4.9 6.00 S.I.T.C. of Earth Link : 50mm x 6 mm 1ft 400.00 No
Long GI.earth link fixed by necessary screws
4.10 6.00 S.I.T.C. of Earth Link : 50mm x 6 mm 1ft 1425.00 No
Long CU.earth link fixed by necessary screws
SUB - TOTAL OF Earthing
5 CABLES, Cable Termination and cable
5.1 Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Aluminium
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
of following size of cables
5.2 Providing and erecting XLPE (IS:7098)(I)-88
ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables
5.3 Providing and erecting XLPE (IS:7098)(I)-88
ISI armoured cable multistrand Aluminium
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
of following size of cables
5.4 Providing and erecting FRLS-
XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Copper conductor for 1.1 kV. to
be laid on wall with necessary clamps or in
existing trench / pipe at road crossing or floor
of following size of cable.
5.5 Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand / Solid Copper
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
at road crossing or floor of following size of
5.6 Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
at road crossing or floor of following size of
225.00 (C) 4 core 10 Sq. mm 838.00 Mtr
5.7 285.00 Making trench in soft soil of suitable width of 55.00 Mtr
90 cm deep for laying cable or locating the
fault all over the run and back filling the same
and making the surface as normal ground.
5.8 60.00 Covering of cable with second class bricks or 139.00 Mtr
cement tiles laid cover the cable crosswise &
also on both sides with covering of 7. 5 Cm.
layer of sand above & below cable (16 bricks
5.9 10.00 ( A )Making trench in Hard Murrum / Tar Road 74.00 Mtr
of suitable width of 90 cm or required depth
for laying any size of cable or locating the fault
all over the run and back filling the same and
making the surface as normal ground.
5.10 5.00 (B) If additional machinery like hammer driller 354.00 Mtr
or JCB use [Add]
5.11 Drilling the road without breaking the road
surface (Asphalt) for laying of cable for
feeding power supply by making up to
following size of holes at both ends complete.
5.11.1 5.00 (A) Up to 100 mm bore dia 488.00 Mtr
5.11.2 5.00 (B) Up to 150 mm bore dia 610.00 Mtr
5.12 Supplying following size of Light duty “A”
Class G.I . Pipe & erecting as directed by
Engineer-in-charge.
5.00 (A) 25 mm dia 171.00 Mtr
5.13 Providing & laying. R.C.C. Hume pipe for
cable to be laid 90 cm. below ground across
the road crossing or on floor with necessary
material in an approved manner and making
the ground as per original.
5.14 Providing & laying approved make Double
walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same
material at required depth in existing trench
for laying of cable. below ground / road
surface for enclosing cable
5.14.1 100.00 (A)50 mm outer dia 62.00 Mtr
5.14.2 280.00 (B)63mm outer dia 73.00 Mtr
5.14.3 20.00 (C))90 mm outer dia 95.00 Mtr
5.14.4 85.00 (D)120 mm outer dia. 136.00 Mtr
5.15 Providing & laying approved make ISI
marked Rigid PVC pipe having 6Kg / cm2
(Class-3) to be erected at road crossing on or
floor as directed for laying of cable. The pipes
as following size of dia & weight per 6 mtr.
5.15.1 10.00 (D) 75 mm inner Dia. (5.5 Kg/6RMT) 124.00 Mtr
5.15.2 10.00 (F) 110 mm inner Dia. (11.63 Kg/6 RMT) 234.00 Mtr
5.16 Providing and, fixing heavy duty flange type
brass cable gland with rubber ring for PVC
insulated armoured cable complete with out
going tails, insulating tape etc for following
size of cables.
5.17 Providing and, fixing heavy duty flange type
brass double compression type cable gland
with rubber ring for PVC insulated armoured
cable complete with out going tails, insulating
tape etc for following size of cables.
5.18 Solder less crimping type Aluminium lugs
conforming to IS suitable for cable of following
size evenly crimped with high pressure tool &
connected to switchgear terminals with
brass/cadmium plated nut bolts in an
approved manner.
5.19 Solder less crimping type Copper lugs
conforming to IS suitable for cable of following
size evenly crimped with high pressure tool &
connected to switchgear terminals with
brass/cadmium plated nut bolts in an
approved manner.
5.20 Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be single or
double bended as per required and as per IS
2062/1079 and shall be coated with hot dip
galvanizing as per IS 2629/4759. with max
17.5% perforation with coupler plate / Fish
plate and GI hardware like nut - bolt and
washers etc. erection with necessary support(
included) as per Specification and as per
instruction of engineer in charge..
SUB - TOTAL OF Cables,Cable
Terminations & Cable Trenches
6 Light Fixtures & Fans
Supply , Installation, testing and
commissioning of pre-wired, LED fitting/post
top luminaries etc of all types, complete with
all accessories and tube etc. directly on
ceiling/ wall, including connection with 1.5 sq.
mm FRLS PVC insulated, flexible, copper
conductor, single core cable with flexible
conduits and coupler and earthing etc. as
required. Note:- The LED Light fixtures
should comply all international standards third
party ( LM 79 for complete fixture, LM 80 for
individual LED ). The Manufacturer /
Channel Partner of the Manufacturer has to
submit 4- Years unconditional free
Replacement Guarantee for complete fixture.
6.1 Supplying and erecting LED indoor fittings
with LEDs of wattage 0.2 Watt to 0.5 Watt
assembled on single MCPCB, with housing
used as a heat sink shall be made of thick
sheet Steel conforming to IS: 513/CRCA/
aluminium die cast powder coated and high
U.V. & corrosion resistance with diffuser with
company mark/name 160V to 270V, Power
Factor more than 0.95, THD < 15%,CCT
3000 K to 6500K, Luminaire efficacy>
lumens/watt , LED driver efficiency > 85 %(
fitting required LM-79 & LM-80
Certificates)(NOTE: Below description have
shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.)
6.1.1 ( A ) Tube Light with integral / non integral
6.1.1a 4.00 (iii) 18-20 Watts, Surge - 2KV,IP-20, 293.00 No
conventional 2/ 4 feet
6.1.1b 110.00 (v) 36-40 Watts, Surge-2 KV, IP-20, 530.00 No
conventional 4 feet
6.1.2 (B) LED Panel Light with provision for Plane
front frame with translucent cover fixed to
housing complete.IP20
6.1.2a 35.00 (i)up to 8 Watts,4" x 4", Surge-2 KV 271.00 No
6.1.2b 150.00 (iii) 12-15 watts, 6" x 6", Surge-2 KV 462.00 No
6.1.2c 100.00 (iv) 18 to 20 watts, 8" x 8", Surge- 2 KV 607.00 No
6.1.3 25.00 (H) Mirror Light 9 Watts, wall mounted 309.00 No
minimum 1 feet long
6.1.4 (I) Adjustable spot light with COB led having
aluminium reflector of following wattage
6.2 225.00 Providing & erecting Approved make Power 1929.00 No
Saving 50 Watt Ceiling Fan with double ball
bearing ISI mark with Condenser 230 volt
A.C. 50 Hz 1200 mm sweep complete
having 3blades with aluminium blades with
canopy & 30 cm. down rod erected with
earthing.(Make shall be approved by Engineer
6.3 15.00 Providing & erecting Approved make Ceiling 1721.00 No
Fan with double ball bearing ISI mark with
condenser A.C.230V 50c/s. 1400 mm. sweep
complete, canopy erected on existing hook or
clamp with earthing [ Make shall be approved
by Engineer in Charge]
6.4 5.00 Providing & erecting Approved make Ceiling 1963.00 No
Fan with double ball bearing with Condenser
230 volt A.C.50 Hz. 900 mm sweep complete
having 3 Aluminium blades, canopy erected
complete. [ Make shall be approved by
Engineer in Charge]
6.5 10.00 Supplying and erecting approved make 2329.00 No
oscillating type medium duty bracket fan with
Aluminium Blades A.C. 23OV. 50cy/s wall
mounted with height adjustment and rotary
tilting device complete with guard, mounting
accessories kit, pull cord for speed and
oscillation flexible Core plug top complete
erected with lead wires as directed. 400MM.
6.6 60.00 Supplying & erecting approved make low 1687.00 No
noise decorative exhaust fan having size
250mm with 1350 RPM with square frame
ABS body with inbuilt lowers & square frame.
6.7 245.00 Supplying & erecting fan hook box of 10 mm 107.00 No
M.S. round bar bounded to the RCC bars up
to 50mm length each side and pierced
through a 16 Gauge M.S. box / Heavy Duty
PVC box complete erected concealed in
Ceiling with necessary finishing.
6.8 245.00 Providing 2.5mm.thick laminated acrylic sheet 18.00 No
to cover the fan hook or Fan box.
6.9 245.00 Supplying and erecting 19 / 20 mm. nominal 107.00 Mtr
bore Medium Class M.S. Pipe down rod
erected duly painted for fan complete with
proper insulation without leakage and
6.10 Supplying & erecting single phase approved
make industrial exhaust fan suitable for
medium duty ring mounted low noise
operation suitable for medium duty having
following dia size and maximum speed in
6.11 1.00 Providing suitable M.S. louver shutter of the 365.00 No
6.12 1.00 Supplying & erecting electro galvanised G.I. 628.00 Sqmtr
wire micro mesh jali cover of grade
required size with suitable wooden frame duly
fitted in wall outside of exhaust fan for insect
6.13 6.00 Providing and erecting PVC body surface or 780.00 No
pendent mounting LED Bulk type 9 watt
Lighting Fitting with electronic driver. And
lumen output from luminaire 720lm , input
voltage range 90-300VAC , 50Hz cool
white(3000 to 6500k), inbuilt driver, -20degC
to +60degC working temperature, AL frame
with Beam Angle 120deg
SUB - TOTAL OF Light Fixtures & Fans
7 External lighting
Supply , Installation, testing and
commissioning of pre-wired, LED fitting /post
top luminaries etc of all typesof external lights,
complete with all accessories and tube etc.
directly on pole / pole bracket , including
connection with 1.5 / 2.5 sq. mm FRLS PVC
insulated,3 core flexible, copper conductor,
with flexible conduits and coupler and earthing
etc. as required.
7.1 Supplying and erecting LED street light /
Flood light fittings with High power White
LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High
pressure die cast aluminum housing with
smooth finish powder coated and heat sink
extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened
glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more
than 0.95, THD < 10 %, CCT 3000 K to
5700K,Uniformity ratio >0.45, Luminaire
efficacy> 100 lumens/watt . LED driver
efficiency > 85 %.( fittings required LM-79 &
LM-80 certificates)(NOTE: Below description
have shown ranges of Wattage capacity of
LED fittings.The Engineer incharge may
select any wattage capacity between the
7.1.1 (A) Street Light (IP-65), Surge protection -4KV
/5000K integral and 10 kv non integral ,Light
must have 440VAC line supply protection. It
should withstand 48 hours for 440VAC line
7.1.2 (B) Flood Light (IP-65), Surge -4KV/5000K
,Light must have 440VAC line supply
protection. It should withstand 48 hours for
440VAC line supply
7.1.2c (C) Post Top Lantern LED fitting comprises of
finish cast aluminum spigot and spun
aluminum canopy fixed with opal
polycarbonate, pipe arrangement for vertical
mounting driver and accessories wired up to
terminal block.IP
7.2 Supply of approved make frp/grp pole having
followiing specifications :
FRP/GRP pole made by centrifugal moulding
process using thermoset resin
polyester/epoxy resin system having minimum
glass content 45.0%.The pole should be in
one pieceand tapered round in shape,having
smooth outside surface finish and should be
totally fre from corrosion as well as non
conductive and shock proof. Pole should be
provided with FRP/GRP base bracket dully
fabricated from metal(M.S) and dully claded
with FRP/GRP material to avoid any metal
exposer and painted with PU paint.
Pole should mechanical properties i.e
Specfic gravity (ASTM D 792) 1.3‐1.8 Kg/m3,
2. Glass Content % by weight (ASTM D 2584)
45.0 ‐55.0%, 3. Water absorption (ASTM D
570) <0.5%, 4. Tensile Strength(ASTM D 638)
200+/‐50Mpa, 5. Flexural strength (ASTM D
790) 250+/‐50Mpa, 6. Compressive Strength
(ASTM D 695) 200+/‐50MPa, 7. Yeild
Strength(ASTM D638) 250 +/‐50MPa.
Pole should be flame retardant as per IS
6746.Resin used shall be UV resistance and
pigmented. Pole should be painted with first
coat of epoxy primer and then two coat of
highly weather resistance polyurethen paint to
ensure proper addhesion of the
paint.Minimum thickness shall be 80 to
micron.Defelection of the pole shall not
exceed more than 10.0 % of the length of the
pole for the given load.Pole should be
generally made as per the dimensional
data,performance criteria and some
interchagebility features of poles as per the
standard ANSI C123.20 latest version of
ASTM D 923/01 including cable termination
box with necessory accessories.The size of
pole and type of installation with foundation
Anchor Base & Internal junction box as per
the manufacturer details and site requirement
. The cost of 6 Mtr & 10 Mtr pole's Flood light
mounting ring is included.
(3) 'B' class (Heavy Duty) frp/grp pole
suitable for base plate mounting
7.2.1 4.00 [B] Overall Length of 4.0 meter, Average 12320.00 E.a.
thickness : 6mm, Top/Bottom Outside Dia.
76/143mm +/‐2.Weight of Pole 15.4 Kg
approx. (Without base) Metal Anchor Base
dully frp claded (Size : 290 Ø * 12mmthk
Mounting hole PCD 240mm * 4 nos. of 16 Ø
7.2.2 14.00 [D] Overall Length of 6.0 meter, Average 19337.00 E.a.
thickness : 7mm, Top/Bottom Outside Dia.
76/176mm +/‐2.Weight of Pole 25.0 Kg
approx. (Without base) Metal Anchor Base
dully frp claded (Size : 340 Ø * 12mmthk
Mounting hole PCD 285mm * 6 nos. of 20 Ø
7.3 Providing FRP/GRP arm bracket of having
15˚ arm with 50 mm OD pipe *5 mm
thk,1000mm long from pole centre
7.3.1 13.00 (a) Single arm bracket 2165.00 No
7.3.2 1.00 (b) Double arm bracket 2749.00 No
7.4 2.00 Supplying & erecting sintex make SMC 472.00 No
press moulded composite FRP. loop-in, loop-
out approx. 2mm thick box complete with
bakelite connector strip 4way & hinged doors
having locking arrangements with mounting
clamp with nuts, bolts & washers suitable for
erection on wall ( c)150mm x 125mm x
7.5 6.00 Providing cement concrete.for foundation or 5077.00 CU Mtr
for concrete filling in 1:2:4 ratio with 20 to
mm stone metal duly plastered with necessary
curing for pole muffing or any other purpose.
7.6 2.00 B' class galvanised iron pipe 32 mm outside 340.00 No
dia 45 cms long duly welded on 20 cms x
cms x 3 mm thick M.S. base plate, erected on
wall or corner for mounting street light
luminaire with necessary hardware materials
SUB - TOTAL OF External Lighting
8.1 1.00 Supplying & erecting approved make 2332.00 Job
Automatic liquid level controller 6A. with
sensor testing as per instruction of Engineer
in charge on site complete with wiring
connection with existing wires , with copper
conductor from pump to upper and lower tank.
8.2 Supplying and erecting Flexible PVC insulated
multistrand multicore 1.1 kv grade ISI marked
copper wires of following size to be erected as
90.00 e) 1.50 Sq.mm 3 core round PVC sheathed 58.00 Mtr
8.3 Providing and erecting ISI mark Medium class
RIGID PVC PIPES of following size complete
to be erected on/in wall or ceiling erected with
necessary PVC fittings & Junction boxes fixed
with adhesive solution & Clamps with
following dia of pipes, in approved manner as
8.4 5.00 Providing & erecting water cooler having 60874.00 No
storage capacity 150 Ltr. & cooling capacity
150 Ltr.per hour @ an ambient temp of 45˚ C.
The outlet temp. of the water should drop by
15˚C within a hour, The water cooler should
be comprising of hermetically sealed
compressor, fan motor, condensing unit,
water tank surrounded by evaporating, coil,
thermostats, relay etc.complete with
necessary inlet & outlet connection. The body
of water cooler will be made from Stainless
8.5 5.00 Supplying and erecting water filter cum 5371.00 No
purifier with ultra violate technology.
(Aquaguard / waterdoc model or equivalent
symphony/ crystal/videocon model)
8.6 Providing & erecting open well horizontal
mono block pump set with cast iron body,
complete for three phase submersible motor
8.6.1 2.00 [D] For 5 HP 3 phase open well horizontal 20417.00 No
mono block pump set suitable for 1350 LPM
to 310 LPM @ 10 to 42 Mtr head suitable for
50/65 mm dia delivery pipe
8.6.2 1.00 [E] For 7.5 HP 3 phase open well horizontal 28303.00 No
mono block pump set suitable for 1550 LPM
to 370 LPM @ 13.5 Mtr to 42 Mtr head
suitable for 65/75 mm dia delivery pipe
8.7.1 Supplying & erecting approved make motor
control cubical panel [Star delta] made from
16G CRCA sheet duly epoxy powder painted
inside and outside with hinged doors and
locking with suitable size of ON - OFF isolator
(AC 3 / 23 duty) main fuses. Digital volt and
current meter (in a single unit) with micro
controller based control unit and current
sensing single phasing preventer electronic
overload protection, over voltage
(Programmable) protection and under voltage
(Programmable) protection, prod less dry run
protection programming facility for setting of
all parameter like overload current, high
voltage limit, low voltage limit, dry run limit
with digital indication on seven segment LED
display for any fault like over load, high
voltage, low voltage, dry running single
crimped, electronic star delta timer, feather
touch start / stop push buttons to be erected
on angle iron frame. Grouted on wall the
contactors will be of L& T, Siemens , BCH
8.7.2 Supplying & erecting approved make motor
control cubical panel (Direct - on - line) made
from 16 G. CRCA sheet duly epoxy powder
painted inside and outside with hinged doors
and locking, arrangement consisting of
suitable size of ON- OFF isolator (AC -
3/23duty) main fuses, single phasing
preventer, indicating lamps for R- Y - B
phases, overload relay, Automatic water level
controller, Ammeter, Voltmeter each with two
way selector switch incoming, wires duly
socket crimped, main contactor & overload
relay, start - stop push buttons, to be erected
on angle iron frame grouted on wall as
directed. The isolator, overload relay &
contactors will be of L & T, Siemens or BCH
2.00 (a) DOL up to 5.0 H.P. 7646.00 No
8.8 1.00 Charges for doing liasioning work for 93220.34 No
obtaining the necessary clearances from the
Electrical inspector / competent Authorities for
the total Electrical installation,co-ordinating
with various agencies including getting
highrise permission. All necessary drawings,
calculations, test certificates, etc. as required
by these authorities shall be prepared and
furnished by the EPC Vendor. Any
modification/rectification as required by these
authorities shall be carried out by theEPC
Vendor at free of cost. The fees required to be
paid to these authorities for inspection shall
be borne by Owner on production of
documentary evidences.
8.9 Supplying and erecting horizontal / vertical
mounting type storage water heater with
copper container housed in M.S./S.S. body
insulated with glass wool / puff complete with
heating elements,adjustable thermostats
300C to 850C, indicating lamp, safety valve,
fusible plug, etc.complete erected with coach
bolts, nuts. washers & cementation
6.00 (C)25 Ltr. with 2 KW. heating element 11342.00 No
Premium category
8.10 12.00 Providing & erecting fibre reinforced PVC 180.00 No
flexible pipe with brass locking nuts &
washers & clips at both ends complete
erected without leakage
SUB - TOTAL OF MISC. Work
9 PASSENGERS ELEVATOR
Supply ,installing , commissioning and testing
of Stretcher Lift ( Hospital lift ) 15/16
passengers (MRL LIFT) as per R & B S.O.R (
Category - Premium ) having following
specifications:- G+5 Floor
Supplying, Erecting, Testing & Commissioning
the passenger lift having following main
[1] GEAR LESS LIFT DRIVE comprising of
High Starting torque Lift 3 phase 440 V A. C.
Permanent Magnet Synchronous motor of
proper rating with high efficiency shall be
[2] Micro processor based / PLC, ACVVVF,
vector control drive with encoder feedback
closed loop system shall be used for lift car
and door operation which shall be full
collective selective operation hall call demand
response, UP/DOWN hall stops, Main, Up/
Down Contactor with overload and phase
reversal relay and safety controls.
[3] Car with M S platform with bracings of
adequate size and to sustain the impact load
cabin + passenger with safety factor of fire for
steel and side panels of Stainless steel of
sheet of grade 304 duty. Car ceiling will be
S.S. finishes with aesthetic appearance with
LED ceiling lights. Car flooring shall be of anti
skid PVC with choice of colour of engineer in
charge. Car doors shall be of stainless steel
grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also
be S.S. 304 finished with emergency stop
device, mechanical door safety device, facility
of auto/ attended mode. All car panel buttons
and all floor switches must be with brail
language as per lift act.
[4] All landing doors must be fire rated for
hour shall be fully automatic centre opening/
telescopic opening made of hairline finish
steel grade of 304 with key holes and infrared
curtains with Unlocking facility from outside
[5] Appropriate battery operated emergency
light in the car along with alarm switch shall
be provided. Also, Emergency Light & Fan
should start immediately without any Time
Delay as soon as power fails.
[6] Digital scrolling indicator system for up-
down arrow along with floor position indicator
shall be provided inside the car and at all
[7] Full height infra red curtain with multiple
cross / crossing light beams shall be provided.
[8] Automatic Rescue Device (ARD) shall be
provided accordingly of passenger capacity
with Manual Rescue Operation ( Manual
Cranking Facility).
[9] Audio visual indication in the lift car
showing over loading shall be provided such
that doors kept open till excess load is
[10] Spring buffers/PU Buffers shall be
[11] Car fan as per passenger capacity with
automatic sleep timer shall be provided.
[12] Voice annunciator with suitable music
shall be provided in lift car.
[13] Self diagnostics system for operational
and safety parameters shall be provided in
[14] Mechanical over speed governor with
governor calibration as per actual site
parameters and submission of calibration
certificate submission, door key holes in the
floor doors, fireman switch shall be provided.
[15] Lift machine hoisting arrangement in the
lift machine room and monkey ladder for lift pit
should be provided by the lift agency, along
with the other steel structure works,
foundations for the machine etc…
[16] In the hoist way fascia plate shall be
provided without any extra cost, where ever
required as / if directed by engineer in charge.
[17] Permanent wiring with necessary safety
devices like RCCB in all circuit, Over Voltage
Under Voltage protection and THD eliminator
in circuit for lift machine room and lift well
with proper numbers of light points, with
fixtures, exhaust fan and plug points shall be
provided by the agency. Only 3 phase Power
Supply shall be made available by
department in lift machine room. Necessary
Earthing as per Lift Act/Rules shall be
arranged by Lift Agency.
[18] Any civil/ electrical works for additional
and alteration in lift shaft and machine room
related to erection of lift shall be made by lift
agency without any extra cost. (granite/marble
fixing around all landing door openings are not
in lift agency’s scope.)
[19] Agency has to provide all working
drawings and documents and liaison services
for obtaining all necessary permission from lift
inspector and other authorities.
[20] acrylic transparent licence/display A4 size
holder in lift car
[20A] As per statutory requirement of Govt. Of
Gujarat lift & escalator act 2000, lift agency
1. Car top safety barricade
2. Push & talk communication system.
3. Fireman's switch operation at Ground
4.carrying out third party lift inspection
during/after lift erection and provide report by
third party authorized by concern licensing
authority 5.agency has to provide third
party insurance upto completion of free
maintenance period and submit the document
[21] Car Panel Operating Buttons with floor
position indicator/buttons must be of Auto
Glow type clearly visible when view from
[22] For Physically Handicapped person Full
Length Handrails of hairline finish steel grade
of 304 should be provided at appropriate
height on the Rear & Side Wall Panels in Lift
[23] With Necessary KVA rating voltage
controlled Stabilizer suitable for your
controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb
required for lift is in scope of work which rating
is sugested by CEICED Department
(electrical Inspector)
(B) SPECIAL FEATURES DESCRIPTION OF
LIFTS for PREMIUM category
1. Advanced control system dual 64 bit
embedded microprocessor with CANBUS
Serial Communication mode including
Regenerative power efficient operation,on site
programming facility, Anti nuisance, Pte-
opening, BMS/RMS with necessary online
real time monitoring system having necessary
connectivity for remote monitoring & other
suitable supporting hardware & software
devices to fulfil the purpose.
2. Floor Indication LCD Display with call
registration & brail mark with arrival gong and
hall lantern & TFT Screen in the car with MP3
Voice Announcer.
3. CAR Panel should be Scratch resistive SS
Moonrock finish / Hair Line / Honeycomb for
car and all Doors, All landing doors must have
fire rating up to 2 hours and car door must
have multi-level crisscross beam door
4. To & fro communication system & wiring
(i.e. car , control room & guard room ) and
Each elevator are equipped with remote
monitoring system.agency has to provide
mobile app and user id and password for
15/16 Passengers, Stretcher Lift Ground plus
5 upper floor with Rated Speed of
AMC LOGO design as per given by
department to be embossed inside the lift car
wall opp. To door.
2.00 (C) With General PLUS ADDITIONAL 2258904.00 No
SPECIAL FEATURES attached herewith.
SUB TOTAL of Passengers Elevator
10.1 Providing and erecting approved make split
air-conditioning unit consisting of copper
condensing unit with fan motor, hermetically
sealed rotary compressor with accessories
etc. duly connected separately erected
evaporating unit and blower motor with its
accessories by means of extra supplied
proper insulated copper tubing,drain PVC
pipes suitable for ( cost includes powder
coated Stand, Eco Friendly green gas
charging, 15A plug top & Remote Control)
with necessary core cutting.
(1)For ISEER Range (KWH/KWH)(3.1 to 3.99)
Premium Category
10.1 3.00 [a] For 0.8 to 1.0 Ton Capacity 42885.00 No
10.2 21.00 (b) for 1.5 ton capacity 57116.00 No
10.3 44.00 (c) for 1.7 to 2.0 ton capacity 64577.00 No
10.4 3.00 (d) for 2.2 to 2.5 ton capacity 75294.00 No
10.2 Supplying and installing MS angle , powder
coated / Painted standard type of wall/floor
stand mount for outdoor unit of split AC of
following capacity, erected with necessary
hardware materials as directed.
10.2.1 24.00 (A) 25mm*25mm*3mm thick M.S angle 1305.00 No
suitable for upto 2 TR. Capacity of ac machine
10.2.2 47.00 (B) 35mm*35mm*5mm thick M.S angle 1496.00 No
suitable for above 2 TR to 4 TR Capacity of ac
10.3 1525.00 Supplying and erecting insulated pair of soft 1147.00 RMT
copper tubing including power and control
cable,necessary PVC drain pipes for Split AC
machine up to 4 TR capacity
10.4 Rigid UPVC drain pipe of 10 Kg/cm2. rating
with 9 mm thick.nitrile rubber insulation.
10.5 430.00 Supplying & fixing 50mm thick TF quality 409.00 Sqmtr
expanded polystyrene for underdeck
insulation on slab/wall /shaft exposed to
sun/atmosphere as per specifications.
10.6 850.00 Providing , erecting , fabricating the M.S. 77.00 Kg
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one coat
of red oxide with erection on site as per
direction of engineer in charge with necessary
grouting, cementing, plastering & finishing
SUB TOTAL of HVAC WORK
11 AV SYSTEM FOR MEETING ROOM
11.1 1.00 SITC of 3LCD Lamp based projector having 33560.00 No
wxga (1280x800) or better resolution with
minimum white brightness of 3800 lumens
and color brightness of 3800 lumens. The
projector should have minimum 1HDMI,1VGA
input. Having contrast ratio of 15000:1 or
more. the projector should have auto vertical
key stone correction of +/- 30 degree and
Manual Horizontal of +/-30 degree. the
projector should have optical lens, throw ratio
1.30-1.56:1. Zoom Factor of 1.2. Lens focus
Manual having focal length 16.9mm to
20.28mm. projector should have features like
AV mute slide, quick corner and split function
and should support wireless functionality with
inbuilt wifi or wifi dongle. [Approved by
Competent Authority i.e. not Below the rank of
Executive Engineer ]
11.2 1.00 SITC of universal Projector mounting kit, with 6781.00 No
necessary grouting, fasteners etc. with
adjustable height and suitable for all types of
projectors. [Approved by Competent Authority
i.e. not Below the rank of Executive Engineer ]
11.3 1.00 SITC of 100 inch Self Lock MW (7 x 5) 3773.00 No
Instalock Slow Retraction Screen, Aspect
Ratio-4:3 [Approved by Competent Authority
i.e. not Below the rank of Executive Engineer ]
11.4 1.00 Supply, Installation Testing & Commissioning 820.00 No
5 Mtr. HDMI Interface Cable as per the
detailed Specifications supports transmission
of 4K Signals as per the detailed
11.5 1.00 Supply, Installation Testing & Commissioning 1760.00 No
15 Mtr. HDMI Interface Cable as per the
detailed Specifications supports transmission
of 4K Signals as per the detailed
11.6 2.00 SITC of Column loudspeaker 40W, metal, 12349.00 No
[Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
11.7 1.00 Supplying & erecting Amplifier having 13424.00 No
following specification:
Power Output :250W (RMS) (300W Max.)
inputs : 6 Misc. & 2 Aux.
frequency Response :50-1500HZ I3db
Tone Controls :Cut & Boost type
LED Meter :5 LED Arrays
The amplifier suitable to operate 240V A.C.&
24volt D.C. (Battery) with automatic
changeover from AC to Battery operation,
duly protected by wrong Battery Polarity
connections. [[Approved by Competent
Authority i.e. not Below the rank of Executive
SUB TOTAL of AV SYSTEM FOR MEETING
ELECTRICAL WORK TOTAL
I. No. Qty Items Unit Rate Per Amount
CCTV System Work Estimate
Final specification and block diagram shall be
submitted by CCTV camera system vendor.
1.1 43.00 SITC of 1/2.8" CMOS 3MP IP Fixed Lens IR 13222.00 No
rugged DOME Camera having progressive
scanning system , Pixels 3MP (2304 x
1296),Lens 2.8 mm, Fixed, F1.4, Minimum
Illumination color / BW: Color: 0.002 Lux @
F1.6, BW 0 Lux IR ON,IR Distance
Mtrs,Wide Dynamic Range 130 Db,Privacy
Masking Off/On (5 Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain Control
0 ~ 100%,Angle of View (H x V) H:87.2°
V:49.1°,Ethernet 10 Base-T/100 Base-TX
Ethernet (RJ-45),Protocols:IPv4, IPv6,
TCP/IP, HTTP, HTTPS, RTSP/RTP/RTCP,
IGMP/Multicast, SMTP, SNMP, DHCP, NTP,
DNS, DDNS, CoS, QoS,802.1X, UPnP,
mDNS(Bonjour), UDP, ICMP, ARP, TLS,
SFTP,Body Material Aluminium +
Polycarbonate,Number of Video Streams
4,Ingress Protection IP66, IP67, Event Notifi
cation HTTPS, HTTP, SMTP, ONVIF, Bit Rate
100 K ~ 6 Mbps Certificates: FCC PART
CE (EN 55032), ICES-003,CE (EN 55035),UL
listed to UL/CSA 62368-1, BIS IS 13252 (Part
1)/IEC 69050-1,RoHS, REACH, WEEE,BIS
1.2 6.00 SITC of 1/2.8" CMOS 3MP IP Fixed Lens IR 13222.00 No
rugged Bullet Camera having progressive
scanning system , Pixels 3MP (2304 x
1296),Lens 3.6 mm, Fixed, F1.4, Minimum
Illumination color / BW: Color: 0.002 Lux @
F1.6, BW 0 Lux IR ON,IR Distance
Mtrs,Wide Dynamic Range 130 Db,Privacy
Masking Off/On (5 Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain Control
0 ~ 100%,Angle of View (H x V) H:87.2°
V:49.1°,Ethernet 10 Base-T/100 Base-TX
Ethernet (RJ-45),Protocols:IPv4, IPv6,
TCP/IP, HTTP, HTTPS, RTSP/RTP/RTCP,
IGMP/Multicast, SMTP, SNMP, DHCP, NTP,
DNS, DDNS, CoS, QoS,802.1X, UPnP,
mDNS(Bonjour), UDP, ICMP, ARP, TLS,
SFTP,Body Material Aluminium +
Polycarbonate,Number of Video Streams
4,Ingress Protection IP66, IP67, Event Notifi
cation HTTPS, HTTP, SMTP, ONVIF, Bit Rate
100 K ~ 6 Mbps, Certificates: FCC PART
CE (EN 55032), ICES-003,CE (EN 55035),UL
listed to UL/CSA 62368-1, BIS IS 13252 (Part
1)/IEC 69050-1,RoHS, REACH, WEEE,BIS
1.3 2.00 Supply , Installation , Testing and 66202.00 No
commissioning of 32 Channel NVR (Network
Video Recorder) Embedded Linux based for
recording upto 32CH at 1080P, 960fps with
nos. SATA HDDs minimum 40TB storage or
more (recording requirement all cameras
recording at 2MP, 25fps for 30 days), H.265
HEVC/H.264/MJPEG codec decoding, Front
Panel with LEDs Indication for Power & HDDs
Status, 3 nos. USB, ONVIF S, Time Sync with
NTP, Encrypted Streaming & Control, 2-Way
Audio Line & Out, PTZ Operation Pan, Tilt,
Zoom, Support, Pre & Post Alarm Recording
Support, Recording/Evidence Clip Export to
USB, 16 Channel Synchronous Playback,
Playback control i.e Play, Pause, Stop, Fast
Forward, Backward, Speed Control, Timeline
& Zoom; Snapshot, Web Client, Central
Monitoring Software, iPhone; iPad; Android
based Mobile clients, 02HDMI & 01VGA
Output, 04 On Board HDDS each up to 10TB,
Alarm Input (16 nos.), Alarm Output (04 nos.),
RS232/485, eSATA, 256 Mbps throughput,
NDAA Section 889 Compliant, Operating
Temperature –10°C to 55°C, Certification :
Certifications: ONVIF compliant, UL/CSA
62368-1, CE (EN 50130-4), FCC Part 15, EN
55032, NDAA & RoHS (EN63000) compliant.
Including fixing accessories and cable
termination with required connectors/Jack,
complete in all respect as per instruction of
engineer in-charge.
1.4 4.00 Supply Installation Testing & Commissioning 25150.00 No
of 8TB Surveillance Harddisk
1.5 2.00 Supply, Installation, Testing and 53465.00 No.
Commissioning of 43 inch, Professional LED
Display Cum Commercial TV with Android
& Inbuilt play store, UHD resolution, 400 nits
brightness, It's 24*7 usage, 50,000 hours life,
3 years warranty, Android 11 with inbuilt play
store, Inbuilt wifi, Landscape / Portrait mode,
Inbuilt Bluetooth, 2 GB / 16 GB Memory,
Inbuilt SOC with HDMI cable
1.6 Providing and erecting ISI mark Medium class
RIGID PVC PIPES of following size complete
to be erected on/in wall or ceiling erected with
necessary PVC fittings & Junction boxes fixed
with adhesive solution & Clamps with
following dia of pipes, in approved manner as
CAT 6 UTP Cable
1.7 Supplying & erecting approved make LAN
cable of following size in existing pipe as per
1.8.1 3.00 Supply, Installation, Testing & Commissioning 12053.57 No
of 9U wall mount rack.
1.8.2 1.00 3U wall mount Rack 5025.01 No
1.9 3.00 SITC of 24 x 10/100/1000BASE-T PoE ports 4 31680.00 No
x Gigabit RJ45/SFP Combo ports Advanced
L2 switching and security features L2+ Static
Routing Optional “standard mode” or
“surveillance mode” management user
interface 193 W PoE budget (Including Five
year free maintenance with guarantee)
1.10 2.00 SITC of 8 x 10/100/1000BASE-T PoE ports 2 18218.00 No
x Gigabit SFP ports Advanced L2 switching
and security features L2+ Static Routing
Optional “standard mode” or surveillance
mode” management user interface 65W PoE
[Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
1.11 2.00 Supply, Installation Testing & Commissioning 820.00 No
5 Mtr. HDMI Interface Cable as per the
detailed Specifications supports transmission
of 4K Signals as per the detailed
1.12 49.00 Supply, installation, fixing, testing and 440.00 No
commissioning of PVC Junction box for CCTV
Camera, IP65, outdoor application. Junction
Box size will be as per vendor's requirement
and site condition.
1.13 3.00 SITC of Patch Panel Cat 6 UTP Keystone 4357.00 No
Type- 24 Port-Fully Loaded (Including Five
year free maintenance with guarantee)
1.14 49.00 SITC of Jack Cat 6 Keystone UTP (Including 160.00 No
Five year free maintenance with guarantee)
1.15 49.00 SITC of CAT6 UTP 24AWG PATCH 155.00 No
CORD:1M,Plug 30U' Snag less (Including
Five year free maintenance with guarantee)
SUB -TOTAL OF CCTV SYSTEM
2 LAN NETWORKING
2.1 Supplying and laying UPVC cable trunking
system comprising unplasticised polyvinyl,
chloride rigid material with ignition free and
flame proof confirming BS with necessary end
caps Internal and external bend, flat bends,
coupler, tee etc..All necessary accessories
and measuring of following sizes
2.1.1 5.00 (2) 100 mm x 50 mm trunking 424.00 Mtr
2.1.2 5.00 (4)100 mm x 50 mm trunking with TWIN 1309.00 Mtr
compartment With clip in divider
2.2 Supply & installation of surface mounted U
PVC snap-on adaptable trunking raceways,
fabricated out of U-PVC to Off-White or
approved shade as per IS 733 of thickness
2.0mm for the base and sides with all
accessories like removable covers, joints
,height spacer,angles complete with
necessary bends, suitable sized junction
boxes and tees etc, Complete.
5.00 (a)Size: 50x80mm PVC Raceways for Power 1052.00 Mtr
& Data with 2 compartments above
specifications.
2.3 Supply & installation of modular type
accessories for U PVC snap-on adaptable
trunking/Pop up Box with required items
erected with necessary connection. As
desired by Engineer In charge
2.3.1 4.00 i) 6 A SP 1 Way Switch 204.00 No
2.3.2 2.00 ii) 16A SP 1 Way Switch 351.00 No
2.3.3 4.00 iv) 6A universal socket shuttered 347.00 No
2.3.4 2.00 iv) 6/16 A universal socket shuttered 458.00 No
2.3.5 2.00 vi) Cat-6 LAN Socket 561.00 No
2.5 LAN NETWORK
2.5.1 42.00 SITC of CAT6 UTP 24AWG PATCH 155.00 No
CORD:1M,Plug 30U' Snag less (Including
Five year free maintenance with guarantee)
2.5.2 42.00 SITC of CAT6 UTP 24AWG PATCH 199.00 No
CORD:2M,Plug 30U' Snag less (Including
Five year free maintenance with guarantee)
2.6.1 3.00 SITC of 24 x 10/100/1000BASE-T ports 4 x 15247.00 No
Gigabit RJ45/SFP Combo ports Advanced L2
switching and security features L2+ Static
Routing Optional “standard mode” or
“surveillance mode” management user
2.6.2 3.00 SITC of Patch Panel UTP Keystone- 24 Port- 1485.00 No
Unloaded (Cat 5e,Cat 6 & Cat 6 A )
(Including Five year free maintenance with
2.7 Providing & erecting main Distribution (MDF)
indoor type, back mounted frame as per DoT
standard approved with krone strips
1.00 (a) Suitable for 10 pair 985.00 E.a.
2.8 Providing & Erecting Netwrok rack with
following capacity with Necessary cooling
fan,Cable manager,6A PDU,equipment rack
with necessary mounting accessories.
2.9 Supplying & erecting approved make LAN
cable of following size in existing pipe as per
2.1 Providing & Erecting approved make following
size of TV Co-axial flexible cable comprising
inner conductor of solid bare copper insulated
with Foam PE & Secondary conductor made
of poly - Aluminium film bonded Al. Braids @
suitable coverage overall sheathed with
black PVC insulation.
2.11 Providing following type of Modular Type
Accessories mounted with PVC /
metallic/Wooden box, single mounting base
frame covered with textured / metallic/white
front plate , modules erected with necessary
connections as per site situation directed by
Engineer In charge.
45.00 (8) Computer RJ-45 socket 159.00 E.a.
SUB -TOTAL OF LAN NETWORK SYSTEM
I. No. Qty Items Unit Rate Per Amount
FIRE FIGHTING SYSTEM
Design,Drawing, Supply,installing,testing
and commissioning of FIRE HYDRANT
1 Internal / External Hydrant
1.1.1 Supplying, Installation, Testing and
Commissioning of electric driven main
Hydrant fire pump suitable for automatic
operation and consisting of following:
complete in all respect as required.
2.00 a) Horizontal type, single stage, centrifugal, 230151.00 Set
end suction pump of cast iron body & bronze
impeller with stainless steel shaft, mechanical
seal to ensure a minimum pressure of
kg/sq. cm. at highest and farthest outlet at
specified flow of 2280 lpm at 65 Mtr. head
conforming to IS 1520.with suitable size of
footvalve confirming to IS 4038, Pressure
rating PN2 , preventing entry of foreign body
to pump through suction pipe, perfectly flat
seating surfaces for good sealing.
b) Suitable HP Squirrel cage induction motor,
TEFC, suitable for opertion on 415 volts,
phase 50 Hz. AC with IP 55 class protection
for enclosure, horizontal foot mounted type
with Class - 'F' insulation, conforming to IS-
c) M.S. fabricated Common base plate,
coupling, coupling guard, foundation bolts etc.
d) Suitable cement concrete foundation duly
plastered with anti vibration pads.
The pump shall be capable of giving not less
than 150% discharge at ahead not less than
65% of the rated head.
1.1.2 1.00 Supplying, Installation, Testing and 61717.00 Set
Commissioning of electric driven
pressurisation pump suitable for automatic
operation and consisting of following:
complete in all respect as required
a) Horizontal type, single stage, centrifugal,
end suction pump of cast iron body and
bronze impeller with stainless steel shaft,
mechanical seal at specified flow of 180 lpm
at 56/70 m. head conforming to IS: 1520.with
suitable size of footvalve confirming to IS
4038, Pressure rating PN2 , preventing entry
of foreign body to pump through suction pipe,
perfectly flat seating surfaces for good
b) Suitable HP Squirrel cage induction motor
TEFC type suitable for operation on 415 volts,
3 phase 50 Hz. AC with IP 55 Class of
protection for enclosure, horizontal foot
mounted type with Class F' insulation,
conforming to IS :
c) M.S. fabricated Common base plate,
flexible rubber coupling, coupling guard,
foundtion bolts etc. as required.
d) Suitable cement concrete foundation duly
plastered with anti vibration pads.
1.1.3 ENGINE DRIVEN PUMP
1.00 Supplying, Installation, Testing and 506181.00 Set
Commissioning of diesel engine driven main
fire pump suitable for automatic operation and
consisting of following: complete in all respect
a) Horizontal type, single stage, centrifugal,
end suction pump of cast iron body and
bronze impeller with stainless steel shaft,
mechanical seal to ensure a minimum
pressure of 3.5 kg/sq. cm at highest and
farthest outlet at specified flow of 2280 lpm at
65 m. head conforming to IS
b) Suitable HP, 1500 /1800 RPM water cooled
with radiator, diesel engine conforming to
relevant BS & IS standard complete with auto
starting mechanism, 12/24 volts electric
starting equipment, 180 AH lead acid battery
with battery stand, exhaust pipe extended
upto 6 m. outside pump house duly insulated
with 50 mm thick glass wool with 1.0 mm.
thick aluminium sheet cladding, residential
silencer, instruments and protection as per
specification, stop solenoid for auto stop in the
event of fault with audio indications, painted
with post office red colour etc. as required.
c) One 200 Ltr capacity day oil storage tank
fabricated from 3 mm thick M.S. plates. Tank
shall be provided with inlet, outlet, overflow,
air vent, drain connections, filling connection
& level indicator. Tank shall be mounted on a
suitable steel structure (Painted with 2 coats
of red oxide paint). Tank shall be provided
with two or more coats of synthetic enamel
paint outside over two coats of red oxide
d) M.S. Fabricated Common base plate,
coupling, coupling guard, foundation bolts etc.
e) Suitable cement concrete foundation duly
plastered with anti vibration pads.
1.2 FIRE PANELS
1.00 FIRE CONTROL PANEL FOR Main Hydrant 341210.00 No
pump and Jockey pump and Diesel Engine
Fabrication, Supplying, Installation, Testing &
Commissioning of electrical control panel of
cubical construction, floor mounted type,
fabricated out of 2mm thick CRCA sheet,
compartmentalised with hinged lockable
doors, dust and vermin proof, powder coated
of approved shade after 7 tank treatement
process, cable alley, inter-connection, having
switchgears and accessories mounting and
internal wiring, earth terminals, numbering etc.
complete in all respect, suitable for main fire
pump, pressurisation pump complete as per
CPWD specification with following in coming
and Outgoings, suitable for operation on
415V, 3 phase, 50Hz Ac Supply with
enclosure protection class IP 42 as required
:suitable for operation on 415 V, 3 phase,
HZ, AC supply with enclosure protection class
IP 42 as required.
A. Incoming Feeder:-
(i) 1 No of 200 A,35KA, 415V,FP MCCB with
Thermalmagnetic Based Releases having
O/C, S/C ,E/F protection, Digital ELR
96x96mm with CBCT, FP Spreader Terminals
1 set= 8 Pcs, Extended Rotory Handle for
MCCB, 240V AC Shunt Trip coil for MCCB.
(ii) LED type indicating Lamp with suitable
rating 2 Amp SP MCB:- 1 Set (each set
comprise of R,Y,B)
(iii) Digital type 3 phase Multi function Meter
with suitable rating of MCB & 3 Nos. of single
core epoxy resin cast type CTs of 200/5
Amps, 10 VA, CL 1.0 ratings -1 Set.
415 V, 200 Amps, FP Aluminium Busbars with
Heat shrinkable color code insulation sleeves.
OUTGOINGS:-( All outgoing feeders for
pumps should have digital Ammeter with
selector switches and LED type ON,OFF,Trip
indicating Lamps )
1 sets - 125 A, 25kA TPN MCCB, Ics=100%
Icu, with fully automatic Star/Delta starter
suitable for 50 HP pump with overload
protection, current sensing type single phase
preventor complete with all acceessories and
internal wiring required for automatic
operation,selector switch for local/remote,
auto/manual/OFF operation.
1 sets - 125 A, 25kA TPN MCCB, Ics=100%
Icu, with fully automatic Star/Delta starter
suitable for 50 HP pump with overload
protection, current sensing type single phase
preventor complete with all acceessories and
internal wiring required for automatic
operation,selector switch for local/remote,
auto/manual/OFF operation.
1 no.63A,16KA MCCB Ics=100%,Extended
Rotry handle with TM release having O/C &
S/C protection with 10 HP fully automatic star/
delta starter , current sensing type, Single
Phase Preventer, ON/OFF Push Button &
LED type Indicating lamps complete with all
accessories and internal wiring required for
automatic operation, selector switch, for
local/remote, auto/manual operation
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch & 3 attempt
starting device, timers and relays as required,
push buttons, start/stop in manual mode.
ii) LED type Indication lamp for High/Low
Lub. Oil pressure, High Water Temp and
Engine ON indication.
iii) Battery charger suitable for 12 V/24 V DC
with boost and trickle selector switch, 0-30 V
DC volt meter, 0-20 Amp DC Ammeter.
iv) All standard relays, accessories for
automatic operation of diesel engine, wiring
with 1.5 sq mm PVC insulated copper wire
between various sensors and system
controller / starter, suitable size cable for
battery charging etc. as required.
System Controller
Designing, Supply, Installation, Testing and
Commissioning of system controller to control
operation of Main Electric Fire Pump, Diesel
Pump, Pressurisation Pump, Terrace Pump in
sequence as per specification consisting of
relays, timers, sensors, annunciation window
for fault indication, control wiring complete as
3 NOS. 25A DP MCB " C " Curve
1.3 PRESSURE GAUGES, PRESSURE
SWITCHES & Pressure vessel
1.3.1 3.00 Providing, fixing, testing and commissioning of 1329.87 Set
Pressure Switch with Needle Valve.
1.3.2 3.00 Providing and fixing in position the 1264.00 Set
industrial type pressure gauges with gun
metal / brass valves complete as required
1.3.3 1.00 Supplying, Installation, Testing and 48500.00 No
commissioning of Air vessel fabricated from
10mm MS plate with dished ends,dia of
mm and height 1500 mm with suitable
supporting legs, outside painted with one coat
of primer and two coats of synthetic enamel
paint of approved shade, complete with one
25mm dia connection from pump delivery, one
25 mm drain with valve.Complete as per
technical specification & drawing details.
1.4 Providing, laying, testing & commissioning of
'C' class heavy duty MS Pipe conforming to IS
1239 i/c fittings like elbows, tees, flanges,
tapers, nuts bolts, gaskets etc., in ground
including excavation and providing cement
concrete blocks as support, anticorrosive
treatment with coaltar/asphalt tape as per IS
10221, refilling the trench etc. of following
sizes complete as required .( For HYDRANT )
1.5 Providing, laying, testing & commissioning of
'C' class heavy duty MS pipe conforming to IS
3589/IS 1239 including Welding, fittings like
elbows, tees, flanges,tapers, nuts bolts,
gaskets etc. and fixing the pipe on the
wall/ceiling with suitable clamp/support frame
and painting with two or more coats of
synthetic enamel paint of required shade
complete as required :
1.5.9 5.00 200mm Dia ( wall thickness 6.3mm ) 4938.01 Mtr
1.6 Supplying and fixing Single headed internal /
External hydrant valve with 1 No. 63 mm dia
instantaneous FM Gunmetal/Stainless Steel
coupling and cast iron wheel,ISI marked,
conforming to IS 5290 (type A) with blank
Gunmetal/Stainless Steel cap and chain as
15.00 Single headed Stainless steel 5549.04 No
1.7 14.00 Providing, fixing, testing and commissioning of 10499.50 No
Wall mounting swing type first aid Fire Hose
Reel with drum, hanging bracket, 30 M x
mm dia high pressure hose reel tubing as per
IS:884 with shut nozzle and ball valve and all
required accessories.
1.8 14.00 Supplying, Installation, Testing and 4726.50 No
commissioning of weather proof Fire Hose
cabinet size 900x 600x300mm to house
fire hydrant & hose, including all other
related accessories fabricated from M.S.
sheet (16 Gauge) of fully welded construction
having front door with locking arrangement,
partially glazed with 4 mm thick glass. Cabinet
shall be powder coated & painted with post
office red colour
1.9 28.00 Providing ISI marked RRL (IS : 636, type‐A) 4020.55 No
fire hose pipe 15 meter long and 63 mm dia
with ISI marked (IS : 903) Stainless steel male
and female coupling bound and rivetted to
hose pipes with copper rivets and copper wire
complete as required.
1.10 14.00 Providing Stainless steel ISI marked 63 mm. 1502.28 No
dia. male Instantaneous pattern short branch
pipes with 20 mm dia. Nozzle as per IS :
suitable for 10 Kg/sqcm operating pressure
and suitable for interconnections to hose pipe
coupling as required.
1.11 Supplying and fixing of fire brigade connection
of cast iron body with gun metal male
instantaneous inlet couplings complete with
cap and chain as reqd. for suitable dia MS
pipe connection conforming to IS
1.11.1 1.00 2 way - 100 mm dia M.S. Pipe 6094.09 No
1.11.2 1.00 4 way - 150 mm dia M.S. Pipe 12631.09 No
1.12 2.00 Providing, fixing, testing and commissioning of 1949.25 No
25 mm dia Air Release Valve and Ball Valve
assembly on top of each riser for Air release
1.13 1.00 Providing, fixing, testing and commissioning 4940.68 No
Pressure Relieaf Valve 25mm dia with Ball
1.14 15.00 Supplying and fixing orifice plate made out of 1932.76 No
6 mm thick stainless steel (Grade 304) with
orifice of required size to be fitted between
flange & landing valve of external and internal
hydrants to reduce pressure at the outlet to
the level of 3.5 kg/cm2 complete as required.
1.15 Supplying, fixing, testing and commissioning
of butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked
complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as
1.16 Providing, installation, testing and
commissioning of non-return valve of following
sizes confirming to IS:5312 complete with
rubber gasket, GI bolts, nuts,washers etc.as
1.17 Providing, installation, testing and
commissioning of stainless steel Y-strainer
fabricated out of 1.6 mm thick stainless steel,
Grade 304, sheet with 3 mm dia holes with
stainless steel flange.
1.18 14.00 Supply, Installation, Testing and 737.27 No
Commissioning of Brass. Ball Valves with all
fittings required. 25mm size
1.19 Supplying and erecting Flexible PVC insulated
multistrand multicore 1.1 kv grade ISI marked
copper wires of following size to be erected as
150.00 f) 1.50 Sq.mm 4 core round PVC sheathed 84.00 Mtr
1.20 12.00 SITC of fire pump start stop push buttons in 954.50 No
1.21 1.00 SITC of 4 Zone standalone Fire Alarm 12300.00 No
control Panel, 16X2 Character LCD
Display, provision for zone wise contact and
sounder. Panel does not have provision to
connect Repeater Panel. Approval: CE
Mark.(Including Five year free maintenance
with guarantee)
1.22 Providing and erecting ISI mark Medium class
RIGID PVC PIPES of following size complete
to be erected on/in wall or ceiling erected with
necessary PVC fittings & Junction boxes fixed
with adhesive solution & Clamps with
following dia of pipes, in approved manner as
1.23 12.00 Supply, Installation, Testing and 1201.75 No
Commissioning of Single action Manual Pull
Station.Shock and Vibration Resistant, pull
Down Lever Remains Down Until Reset. Shall
be Polarity Insensitive (with all mounting
accessories , complete with Junction Box for
mooting on Surface, Cable lugs at Ends,
cable compression glands, cable tags and
1.24 12.00 Supply, Installation, Testing and 1201.75 No
Commissioning of Conventional Sounder cum
strobe having tone settings with range of
95dbA and field selectable 15/30/75/110
candelas.(with all mounting accessories
complete with Junction Box for mooting on
surface, cable lugs at ends, cable
compression glands, cable tags and
CABLES AND TERMINATIONS
1.25 Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
at road crossing or floor of following size of
1.26 Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
at road crossing or floor of following size of
1.28 Providing and, fixing heavy duty flange type
brass cable gland with rubber ring for PVC
insulated armoured cable complete with out
going tails, insulating tape etc for following
size of cables.
1.29 Solder less crimping type Copper lugs
conforming to IS suitable for cable of following
size evenly crimped with high pressure tool &
connected to switchgear terminals with
brass/cadmium plated nut bolts in an
approved manner.
1.30 Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be single or
double bended as per required and as per IS
2062/1079 and shall be coated with hot dip
galvanizing as per IS 2629/4759. with max
17.5% perforation with coupler plate / Fish
plate and GI hardware like nut - bolt and
washers etc. erection with necessary support(
included) as per Specification and as per
instruction of engineer in charge..
1.32 SEWAGE PUMPS
2.00 Supplying, Installation, Testing and 19676.50 No
commissioning Sewage water submersible
pumping sets of CI casing & impeller, SS
shaft, including with inbuilt water level
sensors for operating the pumps automatically
and all accessories suitable for operation on
220 V-240 V, single phase, 50 Hz. AC supply
> 10 mm solid handling capacity,Minimum
Capacity - 50 LPM,Minimum Head >
1.33 1.00 Charges of Preparing Design , Drawings 85000.00 job
,Testing of Fire Fighting System with
necessary Approval from Local Fire authority.(
Including Pre-NOC and NOC from Fire
authority. ) The fees required to be paid to
these authorities for inspection shall be borne
by AMC ( owner ) on production of
documentary evidences.
1.34 Providing, fixing, testing and commissioning of
below Auto Glow Signages.
1.34.2 12.00 Fire Equipment: 4" X 12" 514.97 No
1.34.3 12.00 In case of Fire, do not use lift, use staircase: 650.00 No
1.34.5 12.00 Fire Extinguishers 8"x 4" 480.00 No
1.34.7 12.00 Fire Hydrant 4” X 12” 514.97 No
1.34.8 12.00 Fire Hose Reel.4” X 12” 514.97 No
1.34.9 12.00 DCP Extinguisher 8"x 4" 480.00 No
1.34.10 12.00 CO2 Extinguisher 8"X 4" 480.00 No
1.35 Providing, fixing, testing & commissioning of
15mm dia quartzoid bulb type sprinklers of
rating with required accessories :
1.35.1 270.00 Pendent Sprinkler 57°C standard response 362.25 No
(K-80) UL Listed
1.35.2 15.00 Pendent Sprinkler 68°C standard response 471.50 No
(K-80) UL Listed
1.36 Supplying, installation, testing &
commissioning of sprinkler flexible pipe (UL
Listed) of stainless steel complete with
NPT on reducer thread with maximum
working pressure of 175 PSI test pressure of
875 PSI (Burst) with branch line (Inlet) 25mm
NPT male thread to sprinkler head (Outlet)
15mm NPT female thread with reducer,
nipple, 2 side brackets,center bracket,
stockbar of following sizes complete as
required etc of following sizes as required:
1.37 2.00 Providing fixing, testing and commissioning of 4939.25 No
Drainning & Testing Assembly 25mm dia with
Sight Glass , Union joint , Ball Valve & Drain
1.38 Supplying, Installation, Testing and
commissioning of Flow Switch on sprinkler
distribution header on each floor with
necessary Junction Box and shall be
connected to fire alarm panel through cable.
Flow switch shall be "UL" Listed size 150mm
dia/ 100mm dia/ 80mm dia.
1.39 1.00 Providing, fixing, testing and commissioning of 41510.40 No
Sprinkler Alarm valve of cast iron body and
brass/bronze working parts comprising of
water motor alarm, bronze seat clapper, and
clapper arm, hydraulically driven mechanical
gong bell to sound continuous alarm when the
sprinkler system activates,pressure guages,
emergancy releases, strainer, pressure
switch, cock valve complete with drain valve
and bypass, test control box, ball valves,
flanges,gasket etc. 100mm dia.
1.40 120.00 Supplying, Installation, Testing and 122.88 Mtr
commissioning of 2 C X 1.5 Sqmm Copper
Armoured for Flow Switch Cabling from
Announciation panel to Flow Switch.
SUB-TOTAL OF FIRE HYDRANT System
2 FIRE EXTINGUISHERS AND LIGHTNING
2.1 FIRE EXTINGUISHER
2.1.1 12.00 FIRE EXTINGUISHER Supplying, Installation, 2724.25 No
Testing and commissioning of Dry Chemical
Powder (DCP) 6 Kg Fire Extinguisher Mono
Ammonium Phosphate Powder 40, Stored
Pressure Type, Pressure Gauge, Controllable
discharge mechanism Class A, Rating 3A &
Class B rating 21B as per IS 15683 ISI MARK
(ABC Dry Chemical Powder - MAP 40%)fitted
with required accessories including wall
suspension brackets.
2.1.2 12.00 Supplying, fixing, testing and commissioning 6526.00 No
of CO2 type Fire Extinguisher of capacity
kg filled with Co2 Gas as per IS 15222 with
controll discharge mechanismfitted with Hose
& Horn applicable on Class B fire rating 21B
confirms to IS 15683, bearing ISI mark. Co2
Cylinder as per IS
2.1.3 1.00 Providing & fixing of ISI marked water CO2 3450.00 No
type Portable fire extingusher,9 LTR capacity,
Hydraulic test pressure 35Kgf/ cm2,
Discharge range 2 Mtr,Average discharge
time: Min. 13Sec,Fire Rating 3A,Grade:
2.1.4 1.00 Providing & fixing of ISI marked, Squeeze 4200.00 No
Grip Cartridge Type water CO2 type Portable
fire extingusher,9 LTR capacity, Hydraulic
test pressure 35Kgf/ cm2, Discharge range
Mtr,Average discharge time: Min. 13Sec,Fire
Rating 3A,Grade: IS:15683.
2.1.5 1.00 Providing,fixing, testing and commissioning of 2950.00 No
10Kg Modular type fire extinguisher having
Nitrogen expellant ,ceiling mounted,Sprinkler
Nozzle is gas tight the release temperature is
adjusted with sprinkler imported bulb set at
57 degree C or 68 degree C ,coverage area
2.2 LIGHTNING ARRESTER
2.2.1 6.00 SITC of Vertical Air Termination Solid 9323.00 No
aluminium with Base- 10 mm dia and
mm long. Air Termination Base tested for
conditioning, Ageing Test & Lightning impulse
current withstand test: 100 kA of 10/350µs
waveform in an accredited Third party
laboratory as per 6.3 & 6.4 of IEC 62561-1
2017 protocol with MAST 34mm dia 3000 mm
long- Cold Galvanized
2.2.2 165.00 SITC of 8 mm dia solid Aluminium Conductor 297.00 Mtr
for roof top mesh grid and tested as per IEC
62561- 2 conducted in the Govt. accredited
thirty party laboratory to meet the requirement
of IS/IEC 62305 with Required Accessories -
Aluminium Holding clamp at every 1 mtr
distance, Aluminium/SS cross splicer at every
crossing of Alu. conductor, Expansion piece
with connectors at every 20 mtr distance,
Aluminium straight Splicer to connect
conductors. All Accessories should be tested
as per IEC 62561-1 2018 Cl. 6.3 for
conditioning & Ageing Test & 6.4 for
Lightning impulse current withstand test:
kA of 10/350µs waveform(Ageing & Electrical
test ) conducted in a sequence manner &
tested in the Govt. accredited Third party
laboratory to meet the requirements of IS/IEC
2.2.3 220.00 SITC of Galvanized Steel Flat 25x6 mm 153.00 Mtr
thickness from earth electrode directly in
ground as required. Zinc coating: 500 g/m
square (Approx:70 micron coating) tested and
used exclusively for lightning protection
earthing system and ring equipotential
2.2.4 6.00 SITC of 14.2 mm dia 3 mtr long Earth 5933.00 No
electrode of High tensile steel electrode with
250 micron copper bonding & 1 bag of Carbon
fill Based environment friendly backfill tested
as per IEC 62561-7 in NABL accredited
Laboratory and suitable stainless Steel double
sided clamp. Eco Friendly rust proof heavy
duty weather proof Polyethylene Earth Pit
Chamber with following dimensions :254 mm
dia (top), 330 mm dia (bottom) & 260 mm
2.3 20.00 Heat / FIRE RESISTANT COATING OF 3690.00 Kg
CABLE: Supply and apply intumescent based
coating Hilti 678on cables / bunch cables &
cable tray for at least 1 mtr in every 14 Mtrs
for horizontal runs and to entire length of
vertical runs. The coating shall have a density
in the range of 1.2 to 1.4 Kg / L. The coating
shall be non-toxic, asbestos and halogen free
and shall have good mechanical strength. The
coating shall comply with IEC 332 part
(1992). The product shall carry test certificate
for mold resistance rating of 0 as determined
by ASTMG21-96. The product should have a
VOC content of approx... 60g/l as per LEED
2009 and should not have any de-rating effect
on the cable. Manufacturer should submit
relevant certificates for mentioned attributes.
Coating shall be carried out by approved
machine spraying system which will yield
uniform thickness and better finish. Fire stop
installation shall be done by Hilti Accredited
Fire stop Specialty Contractor (HAFSC) and in
accordance with guidelines. Firestop specialty
Contractor need to submit work completion
certificate along with installation report
through Hilti documentation Software CFS DM
for periodic inspection & maintenance
2.4 20.00 FIRE STOP FOAM Hilti CP 620 on both sides 4460.00 No
of wall, with minimum 2 Hours fire rating when
tested in accordance with UL 1479 / ASTM-E
814, for horizontal openings in floors or slabs
made of concrete / masonry or Gypsum after
passing service lines like cable trays or cables
/ cable bundles. The expanding foam expands
seven times its volume to fill the cavity at the
time of dispensing the material and shall fully
cure within two minutes after dispensing. The
product shall be age tested as per Dafstb and
DIBT Standards. The product shall provide
water tightness when tested for W rating as
per UL standards and shall carry test
certificate for sound insulation of 50 dB when
tested in accordance with ASTM E 90. The
product shall carry test certificate for mold
resistance rating 0 as determined by ASTM
G21-96 and shall have a VOC content of
approx... 1.3g/l as per LEED 2009. The
product shall be tested in accordance with
IEC 60068-2-57: 1999-11 (Environment
Testing) as per Part 2-57: Test for Vibration-
Time –history method and VERTEQQII for
seismic zone 4. The system shall be UL listed
& classified and product shall bear the UL and
FM approval logo on the packing. If none of
UL test certificate comply with actual
application, an EJ document prepared by a
qualified personnel and based on nearest
third party tested & approved systems like UL
test certificates & in accordance with IFC
guidelines shall be produced by manufacturer.
A Fire stop submittal shall be produced by
manufacturer, in accordance with approved
passive fire protection method statement, for
technical approval. Fire stop installation shall
be done by Hilti Accredited Fire Stop specialty
Contractor (HAFSC) and in accordance with
Hilti guidelines and UL system test certificates
along with installation report through Hilti
documentation Software CFC DM for periodic
inspection & maintenance purpose.
SUB TOTAL of FIRE EXTINGUISER &
Lightning Arrester
3 FIRE DETCTION & FIRE ALARM SYSTEM
3.1 1.00 Supply, Installation, Testing & Commissioning 203348.75 No
of Microprocessor based Networkable
Analogue Addressable Fire Alarm Control
Panel. The Panel shall be compliant with
EN54-2, EN54-4 and approved by LPCB. The
Fire Alarm Control Panel shall have inbuilt
loops and expandable capacity upto 8 loops.
The Panel must have Full colour 800 x
LCD with resistive touch screen and
automatic backlight dimming. The Panel must
also have the capability to take Addressable
Intelligent Wired and Wireless Devices on
same loop. Each loop shall have a capacity of
127 analogue Addressable devices and
Base sounders/Base Sounder Beacons. The
panel shall have an event log of minimum
10,000 events @ 1 second resolution,
Filterable and Printable. The Panel shall have
Three access levels. Panel shall support upto
5000 Cause & Effects entries, with upto
20,000 inputs controlling & 20,000 Controlling
outputs across the network. The Panel shall
have capability for Peer to Peer networking
through RS485 network card. The Panel must
have 4 inbuilt programmable sounder circuits,
each circuit rated at 2.5A.The Panel must
have inbuilt 3 programmable inputs and
inbuilt programmable relay outputs. The Panel
shall have up to sub-addressable
programmable Inputs/Outputs via optional
RS485 COMMS serially connected
expansion cards. The Panel shall have 240 V
AC power supply along with automatic Battery
Charger. The Panel shall be fully expandable
via common plug in loop driver boards. The
user shall have a choice of using the panel
with 5.25 Amp or 10.25 Amp power supply
unit which is inbuilt in the FACP and should
be approved to EN54-4. The Panel shall have
configurable via USB port to PC or memory
stick. The Panel shall have dedicated RS232
serial port for optional printer. Approved by
3.2 230.00 SITC of Analogue Addressable Multi- Sensor 3597.20 No
which is fully compatible with Analogue
Addressable Protocol,having removable high
performance chamber with Twin fire LED's
allow 360 degree viewing, User selectable
sensitivity modes 1% to 4.5% obs/m,
Incorporate Optical and dual Heat elements,
lock mechanism (sensor to base),
Electronically addressed, Pulsing/non-pulsing
controlled from panel. Approved by LPCB &
VdS. (Including Five year free maintenance
with guarantee)
3.3 15.00 SITC of Analogue Addressable Multi- Heat 3498.30 No
Sensor which is fully compatible with
Analogue Addressable Protocol,having
removable high performance chamber with
Twin fire LED's allow 360 degree viewing,
User selectable sensitivity modes 0 to
degree Celsius, Incorporates Fixed
Temperature and Rate Of Rise Heat
elements, lock mechanism (sensor to base),
Electronically addressed, Pulsing/non-pulsing
controlled from panel. Approved by LPCB
(EN54: Part 5) (Including Five year free
maintenance with guarantee)
3.4 245.00 SITC of sensor common mounting base, 354.20 No
includes stainless steel contacts, slim profile -
only 8mm, quick connection via square cable
clamps, facility for remote indicator, Approved
by LPCB (Including Five year free
maintenance with guarantee)
3.5 20.00 Supply,Instllation,Testing and Commissioning 2477.10 No
of Fault isolator Module capable of monitoring
shorted loop circuit and automatically restore
communications when shorted conditions are
corrected (Including Five year free
maintenance with guarantee)
3.6 135.00 Supplying, installation, testing & 193.20 No
commissioning of response indicator on
surface/recessed MS Box having two LED,
metallic cover complete with all connections
etc as required.
3.7 12.00 SITC of Manual Call Point approved to EN54- 4191.75 No
11:2001, Approved by LPCB Easy to install,
push-fit wiring terminals (Including Five year
free maintenance with guarantee)
3.8 12.00 SITC of Analogue addressable loop powered 7442.80 No
Base Sounder, variable sound output 50 ~
dB(A) (±2 dB(A)) output at 1 metre, 51 user-
selectable tones (all tones EN54-3
compatible), Auto shutdown feature prevents
noise-pollution, Approved by LPCB & VdS
(Including Five year free maintenance with
3.9 2350.00 Supplying & laying of 2x 1.5 sqmm fire alarm 135.70 Mtr
armoured cable, 600/1000V rated with
annealed copper conductor having XLPE
insulation, steel wire armouring & FRLS
outer sheath complete as required.
SUB -TOTAL OF FIRE DETECTION&
I. No. Qty Items Unit Rate Per Amount
LANDSCAPING WORK :
1 240.00 LAYING OUT LAWN – After excavating soil 85.00 Sq.mt.
upto 30 cm. depth & removing unwanted stuff,
stones etc. Preparing soil for planting by
supplying and mixing 6 inch river fine site and
0.5 cmt FYM maximum 100 sqmt of lawn area
and doing termicide @ 1 fit / 100 sqmt area
and planting selection 1 type / approved lawn
grass at maximum 6 cm x 6 cm distance and
maintain it upto 120 days. Maintainance
include all operations i.e. watering, grass
cutting, gap filling, applying of fertizer if
2 144.00 Supplying, Spreading and leveling of good 575.00 Cmt.
earth like firtile soil as directed etc compt.
3 60.00 Supplying, Spreading and leveling of good 575.00 Cmt.
quality river Kap Filling 100 mm as directed
4 2000.00 Supply and Planting saplings of Hedge 15.00 Nos
plants like kadvi mahendi, karmda, dyuranta,
nikodeviya etc. specifies bag size is 4 inch x
6 inch, well established & free from disease at
site. as per the instructions
5 100.00 Supply and Planting saplings of Ficus panda, 150.00 Nos
Ficus benjamina, Ficus benjamina variegated,
Ficus longisland bag size is 13 inch x 13 inch,
well branched, well established & free from
disease at site as per the instructions
6 100.00 Supply and Planting saplings of (Jasud, 85.00 Nos
Ixora, Ticoma Gaudi-chaudi, Gultora,
Jetropha, Haemeliya, Chandani, Mogaro,
Galfemia, , Allamenda, Desi Gulab, Euphorbia
mili, Jasud Hybrid, Chandani double,
Madhukamini, Madhumalti, Ticoma Capensis,
Ixora draft, Nikadevia, English Karen etc.)
having height of minimum 2.00 to 2.5 ft. and
bag size is 8 inch x 10 inch, well branched,
well established & free from disease at site
as per the instructions.
7 200.00 Supply and Planting saplings of Golden 45.00 Nos
Bamboo having height of minimum 5 to 6 ft.
and bag size is 8 inch x 10 inch, well
branched, well established & free from
disease at site as per the instructions.
8 50.00 Supply and Planting saplings of Palm(Botal 3500.00 Nos
palm,foxtel) having height of minimum
to 12.00 ft. and bag size is 21 inch x 21 inch,
well branched, well established & free from
disease at site as per the instructions
9 80.00 Supply and Planting saplings of champa 450.00 Nos
(deshi) having height of minimum 8 to 10 ft.
and bag size is 15 inch x 16 inch, well
branched, well established & free from
disease at site as per the instructions.
10 5.00 Supply, Spreading and leveling of Brick dust 1300.00 Cmt
(Chharu) particle size having maximum
11 100.00 Supply Saplings and Planting of trees 250.00 Nos
species as specified ( Alstonia scholaris,
Erythrina indica, Jacaranda
mimosifolia,Delonix regia , Anthocephalus
cadamba, Spathodea companulata,Neem
(Azadirachta indica), Lagerstromia speciosa
Tabebuia argentea, Cordia sebestena,
Mimusops elengi, Bauhinia blakeana, Kigelia
pinnata, Cassia fistula, Banyan, Ficus
religiosa, Peltophoroum, Bottle brush, Silver
Oak, Billi, Mahagony, Pendula, Desi
Asopalav,Sevan, Badam, Ficus infectoria,
Pinkesiya, Millingtonia hotensis, Rain Tree,
Bakm limdi, kasid, Ashok tree, parkia,
Tabebuia Rosea, millettia, etc.) having height
of minimum 7.00 to 8.0 ft. and bag size is
inch x 13 inch, well branched, well established
& free from disease at site as per the
12 50.00 Supplying insecticides at site well packed in 300.00 20 L Bottle
bottle of 20 litre. weight including royalty and
carriage with all leads and lifts (product to be
brought in company sealed packing only)
I. No. Qty Items Unit Rate Per Amount
Furniture Work ( Curtains and Cupboard
1 10.00 Proviging and Fixing Storage Shutter made 6805.00 Sq.mt.
out of 50mm X 25 mm Indian Teakwood
Frame and 18 mm Ply Board. With 1 mm thick
laminate finish in the front and 0.8 mm thick
Laminate on Back Side with 12 mm thick
Indian teakwood beading. The scope also
include providing and fixing s.s. finish
hardware as per the Requirement. The rate
include cost of all labour, material and with all
hardware like handle, magnate, tackels,
adhesive, screws, etc.for satisfactory
completion of this items.All Exposed Wood
Work shall have malamine polish etc.
2 7.00 Meeting Table Ovel M4 ( 1355 MM WIDE ) 11879.04 RMT
Providing and supplying meeting table ovel in
shape of size 1355 mm Wide as shown in
drawing.The top made out of 19 mm thk.ply
wood with laminate top as shown in
drawing.20 mm thick teak wood beading is
provided all around table top with 5 mm
groove in the center. The top is supported by
2 nos. of vertical square box made out of
mm thick ply board of size 300mm x 300mm
rest on the wooden base of size 400mm x
400mm x 40mm as shown in drawing.The rate
includes cost of all labour,material and with
tools,tackles,adhesive,screws,etc.for
satisfactory completion of this item.
3 450.00 Providing & Fixing Sun Control Reflective 646.37 Sq.mt.
Type Film / Frosted Film as Selected by
Architect/ Engg. In Charge For Glass Doors /
Windows etc. as Directed.
4 500.00 Providing & Fixing in Position Vertical Roller 1372.03 Sq.mt.
Blinds with Minimum 3 % and Maximum 5 %
Light Transperace Screen Fabric Incuding
Providing & Fixing of Powder coated G-
Channel at the Topof Window with necessary
Screw , Cleats etc. and PVC Roller ( Weight
Pipe) and PVC Chain For Up and Down
Movement of Blinds etc. of Approved Make
and as per Drawings / Instruction of Engg. in
Charge For All Colors and Shades. Rates
Includes all Lead and Lift For All Floor Level,
All Height , All Material , Accessories, Fixing
Scaffolding , Labor etc. Complete in All
Respects. All Required Accessories &
Material must be From Same Manufacturer.
5 240.00 Cubical track for cubical curtain :- supply and 737.29 Rmt.
installation of heavy duty Aluminium cubical
track size 20mm wide x 30 mm high, made of
aluminium Extruded with white powder
coating complete with continous PVC liner,
nylon giders and hooks , plastic end cap,
connecting bridge, overlapping joint
connector, Wall bracket with matching screws
to make up cubicle approx. height to 2100 mm
clearance from floor level at approx. 1000 mm
spacing with all accessories of approved
brand/make along with alluminium Extruded
hospital curtain's track system with shite
powder coating with all accessories as per
approved sample. All required accessories
and materials must be from same
manufacturer. This Item is Excluding Curtain.
6 600.00 Cubicle Curtain :- Supply & Installation of 400.00 Sq.mt.
Water Repellant, Antimicrobial Cubicle
Curtain with High Strength18" Oval net at Top
as Approved by Consultant / Engg. In Charge.
Eyelets on Curtains & Hooks and All other
Required Accessories, Fixing , Scaffolding,
Labor etc. Complete in All Respects. All
Required Accessories & Material must be
From Same Manufacturer.
Total of Furniture Work ( Curtains and Total Rs.
Cupboard Shutter)
Signature of Bidder
AHMEDABAD MUNICIPAL CORPORATION
ENGINEERING DEPARTMENT- NORTH ZONE
Name of Work : CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT F.P.NO
:- 161 , T.P.NO :- 121 IN NARODA WARD, NORTH ZONE, AHMEDABAD
FINANCIAL BID (Online Only)
Sr.No. Description Amount
1 Amount For Civil Work Rs.12,07,03,092.09
2 Amount For Electrical Work Rs.
3 Amount For CCTV & ELV Work Rs
4 Amount For Fire Fighting System Work Rs
5 Amount For Landscaping Work Rs.
6 Amount For Furniture Work ( Curtains and Cupboard Shutter) Rs.
I/We am/are willing to carry out work at ______% above / below (should be written in figures and words)
the estimated cost mentioned above.
Estimated cost put to tender : Rs. 15,96,01,948.77 Estimated cost put to tender : Rs.
Add_____% above : Rs ___________ Deduct_____% below : Rs __________
In words : Rupees _______________________ In words : Rupees_____________________
Signature of Bidder Additional City Engineer ( North Zone.
Seal Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NZ NARODA CHC NOTICE INVITINH TENDER 2.9.26.pdf
NZ NARODA CHC VOL-1 PART A TENDER DOCUMENTDT.02.09.2026.pdf
NZ_NARODA_CHC_Final Price Bid Vol -II_Dt 02-10-2026.pdf
NZ_NARODA_CHC_Vol-1 Part B TS_Civil Work Dt 02-10-2026.pdf
NZ_NARODA_CHC_Vol-1 part-C Electrical Specification.pdf
NZ_NARODA_CHC_Vol-1 part-D CCTV Work Specification.pdf
NZ_NARODA_CHC_Vol-1 part-E Fire Fighting Specification.pdf
TENDER DRAWING NARODA CHC.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .