Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹20.0 L
EMD Value
₹20,000
Closing Date
29 Oct 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
executive Engineer,GSPHCL,Ahmedabad
Supplying, Installing, Testing and Commissioning of 125KVA DG set and related items at “L” type barrack, Sabarmati Central Jail. Ahmedabad. (First attempt)
354171
09(2026-2027)
Open
Electrical Works
Works
Ahmedabad
10 documents required · 9 mandatory · 1 optional
₹900
GUJARAT STATE POLICE HOU.CORPORATION LTD.Ahmedabad
₹20,000
9 Oct 2026
9 Oct 2026
9 Oct 2026
29 Oct 2026
9 Oct 2026
Name of Work: SITC of 125KVA DG set with related items at L type barrack, Sabarmati Central Jail.Ahmedabad.
Schedule of rate for R & B / 2026-27 (June 2026) (Without GST)
Item Description Qty Unit Rate Amount (Rs.)
1 Supplying and erecting, commissioning and testing 125 KVA Diesel Generating set as per the latest CPCBIV+ norms having continuous 1.00 Each 12,25,655.00 RS: Twelve lac Twenty
rating, 3 phase, 415 volts, 50 cycles A.C. supply comprising of a totally enclosed Water cooled diesel engine with multi-cylinders Inline Five Thousand Six
arrangment developing suitable BHP not less than following capacity at 1500 RPM with 10% overload for one hour in 24 hours Cost Hundred Fifty Five
including liaison work i.e. Preparation of site plan tracing & its blue prints, Site plan approval from Energy & Petro. div., KWH Meter testing for only
D.G. Set, Site test report & other license stamped letter issuing, Certificate from Elect. Inspector, Registration at Elect. Duty wing, Kutch.
D.G.Set inclusive::: Testing: Testing means full load & 10% over load testing of D.G.Set at Company / Dealer work shop. Cost inclusive of
Diesel, To & Fro Fair, Lodging boarding etc. of two engineer of corporation. Also full Diesel tank with diesel ( 100% ) At the time of handing
over D.G.Set to Benficial. 200 Ltr Capacity Heavy Duty standard oil M.S./PVC Barrel & Diesel Filling hand Pump of required capacity.Agency
has to give service & All in All maintanance contract As per tender Item to OEM. During defect liability Period .Agency has to replace
oil,Diesel,filter,air filter,filing up DEF ( Diesel Exhuast Liquid ) etc as per site reguirement and OEM Guideline & working hour of D.G set.
Agency has to Provide fitness certificate at time of final SD release.)..All parts of the DG set are warranted for the defect liability period and the
agency will replace them free of charge in case of manufacturing defects, transport damage or lack of regular service. The details
Specification of DG se is As Per Annexure A125
Executing comprehensive (All -in-All) service & manitenance with spare parts as per terms & condition of tender DG manufacturer for defect 1.00 Job 94,000.00 RS: Ninty Four
liability period. For that main agency has togive All-in-All comprehensive maintenance contract to DG manufacturer and copy of this contract Thousand only
will be submited before final bill. Agency has to quote rate accordingly. Agency has to also provide the fitness certificate from DG manufacturer
and submit to GSPHCL. Agency has to submit FDR of approved bank as per clause 2.0 section 3 Rs. 94000.00 + GST or quoted rate which
ever is higher to GSPHCL.for minimum maturity period of four years in favour of GSPHC . Which will be releared after successful completion
2 of AMC & at the and of defect liability period. DG OEM has to mantain written record of service & maintenance during defect liability daily
period duly sigh by police dept. and submited regularly to GSPHCL. DG agency has to do maintanance as per terms & condition In tender.
Agency have Replace outer Air element ,Filter Element Primary, Oil Filter, Filter Element Secondary, Gesket, battery, charger, Valve Cover,
Belt Alternator, Fan Belt, Lube Oil, Coolent etc.Cost Of Diesel not Included in this item during defect liability Period as per site required &
working hours of DG set, OEM has to Provide Fitness certificate at time of releasing S.D
Providing and erecting Medium Class FIA approved and ISI mark white colour (embossed) RIGID PVC PIPES of following size complete 30.00 Mtr. 24.00 RS: Twenty Four
3a erected with necessary PVC fittings & Junction boxes fixed with adhesive solution & clamps on / in wall / ceiling along with continuous fish wire only
to draw mains with necessary fittings and junction boxes for following dia. (a) 20 mm. dia.
For 25 mm. dia. 30.00 Mtr. 33.00 RS: Thirty Three
Providing & fixing 25 mm. dia. PVC insulated G.I. corrugated Flexible pipe with necessary socket, PVC bushes saddle, Check-nuts etc. 30.00 Mtr. 37.00 RS: Thirty Seven
complete of following sizes. only
Item Description Qty Unit Rate Amount (Rs.)
Providing & Erecting 2.0 mtr long Earthing system by making minimum bore of 225 mm dia in soft soil. Suitable for doing pipe-in- 4.00 Each 6000.00 RS: Six Thousand
pipe technology earthing.Earthing electric rod must be made from Corrosion free Hot dip galvanizing pipes having following only
(A) Earthing Electrode: outerpipe:- 88 mm minimum O.D., ISI 'B ' Class ISI mark of Reputed Brand, Inner pipe:- 42 mm minimum
O.D., Pipe B Class ISI mark reputed Brand Terminal Size: 70mm X 100mm length, Terminal Should be made from inner pipe for
that pipe must be pressed and gave rectangular shape so its work as a terminal.The hot deep galvanising must be done after
above process.Galvanised thickness must be minimum 75 micron any where. SS Nut bolt:- 2 no.with washer suitable for 14mm
dia. hole must be provided at terminal. total minimum Weight(approx.) of earth electrodewith inside conductive material minimum
should be 26 kg.
(B) Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm/meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no
load & dry form, Sulphar content:- <2%
(C) Back fill Compound:- Earthing compound should be capable to retain moisture for long time Back Filling Compound weight is
1. Short circuit test by ERDA/ CPRI for 25KA
2. Resistivity test of conducting material from NABL accredited lab.
3. Hot dip galvanised / zinc coating micro test from reputed laboratory.
4. General test report from OEM regarding specification of earthing.
[Make and model approved by EIC Strictly subject to item specification only] [OEM has to submit all detail & sample for approved
before supplying]
[Water must be poured in bore before starting earthing. Earthing value must be measured with earth tester. Agency has to bring
the earth resistance to at least 02 ohms & voltage between neutral & Earthing upto 02 volt. Agency has to maintain earthing & its
value for one year. Earthing must be done in the presence of A.E. (GSPHCL)]
Providing & Erecting Earthing Chamber and cover:- Earthing chamber should be size of 400 mm X 400 mm X 400 mm depth and 4.00 Each 1025.00 RS: One Thousand
Cover should be heavy duty cast iron with required size of 300 mm X 300 mm X 4 mm thick. Necessary test report must be Ten Hundred Twenty
submitted. Five only
For above earthing additional charges for boring in hard rock soil (by breaker) & filling soft soil in earth pit (certificate for soil have to given by 4.00 Each 325.00 RS: Three Hundred
5c DEE / AE along with photographs) Twenty Five only
Providing & erecting L.T. Current Transformer with bar primary 50/5 to 1000/5 ratio 15 VA burden havong 0.5 class accuracy erected in 3.00 Each 272.00 RS: Two Hundred Seventy Two
6 existing CRCA box duly secured with insulating materials connected to the meter
Supplying & erecting 12 mm thick backelite sheet of approved make and grade on 25 x 25 x 3 mm red oxide painted angle iron frame suitable 2.00 Sq. Mtr. 2289.00 RS: Two Thousand
for fixing ICDP SWITCH and energy meter (contractor shall make approved drawing of Bakelite sheet To arrange required No. of Energy Two Hundred Eighty Nine
7 meter & ICDP switch -busbar etc. as per Actual space available in electrical room at site) only
Providing and erecting metallic vitrified danger notice board as per language suggested by engineer incharge for MEDIUM VOLTAGE 2.00 Each 69.00 RS: Sixty Nine
8 installation to be erected as per IS-2551. only
Providing, erecting, fabricating the M.S. structure as per requirement of site as per structure design Including proper size approved by EIC of 1500.00 kg 77.00 RS: Seventy Seven only
M.S. angles, flats, bars, square pipe, channels, sections (Tata,Zindal,Asian,Jsi Make) complete with cutting, welding, grinding and finishing
duly painted with Asian/Nerolac make premium quality oil paint and true care red oxide metal primer,asian paint make with erection on site as
9 per direction of engineer in charge with necessary grouting cementing, plastering and finishing complete. All hole opening of square pipe end
must be closed with M.S plate welding. Payment will be done on KG as per Actual weight.
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. 85.00 Kg 77.00 RS: Seventy
10 using suitable size insulator clamp with min. 80 micron with sleeve as per IS. Test certificate must be submiited by agency Seven only
Item Description Qty Unit Rate Amount (Rs.)
Supplying and erecting approved make GRP/FRP Perforated type Cable Tray Material – Corrosion Resistant Polyester Flame Retardant U.V. 40.00 Rmt 230.00 RS: Two Hundred
Stabilized Resin System - Manufactured from Pultruded Sections- Polyester Resin System, Glass Content : 55 – 60 % - - Standard Length : Thirty only
3000 mm- Support Span – 1500 mm, Deflection L/200 - Specification NEMA FG1 1993- UV Resistant - Flame Retardant – IS 6746 -
Appendix K/UL 94, Very Low Flammability - Specification Followed NEMA FG1 1993 Oxygen Index – Minimum 30% as per ASTM D 2863 -
11a Flame Spread (Extent of Burning) – 20 mm as per Standard ASTM D 635 - Tensile Strength – 4000 – 8000 Kg/Cm2 as per Standard ASTM D
638 - Flexural Strength – 2500 – 10000 Kg/Cm2 as per Standard ASTM D 790- Izod Impact Strength – 130 Kg/Cm2 as per Standard ASTM D
256- Compressive Strength – 2500 – 5000 Kg/Cm2 as per Standard ASTM D 695- Barcol Hardness – 50 – 65. For Width - 150 mm,
Pultruded “C” Channel with 30mm Sides 3 mm Thickness, Loading 15 Kg./Mtr.
Supplying & erecting Sintex or approved make SMC press moulded composite FRP. loop-in, loop-out approx. 2mm thick box complete with 2.00 Each 890.00 RS: Eight Hundred
bakelite connector strip 4way & hinged doors having locking arrangements with mounting clamp with nuts, bolts & washers suitable for Ninty only
erection on pole with cable clamps& earth bolt of following size of box.a) 300mm x 200mm x 100mm [deep]
Providing & erecting FRLS -XLPE (IS : 7098) (I)-88 ISI marked armoured Aluminium conductor cable for 1100 volt to be laid 90 cms. Under 150.00 mtr 642.00 RS: Six Hundred
ground or to be laid on wall with suitable G.I. heavy guage 1.0mm thick cable clamp or in existing DWC pipe underground or road crossing Forty Two only
12 or floor. For 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid on wall with necessary 50.00 Mtr. 451.00 RS: Four Hundred
13 clamps 1.00 mm thick to be laid 90 cms underground with 1.00 mm thick G.I heavy duty grade or in existing trench / pipe at road crossing or Fifty One only
floor of following size of cables. For 4 core 4 Sq. mm
Providing & fixing Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high 6.00 Each 45.00 RS: Forty Five only
14a pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. For 120 Sq.mm.
14b For 70 Sq.mm. 2.00 Each 25.00 RS: Twenty Five only
Providing & fixing Solderless crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure 50.00 Each 8.00 RS: Eight only
15 tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. For upto 6 Sq.mm.
Providing & fixing Double compressed heavy duty flange type brass cable gland with rubber ring for P V C insulated armoured cable complete 8.00 Each 43.00 RS: Forty Three
with outgoing tails, insulating tape etc. For following size cables. For 2 to 4 core x 4.0 Sq. mm only
Providing & fixing double compressed heavy duty flange type brass cable gland with rubber ring for P V C insulated armoured cable complete 12.00 Each 139.00 RS: One Hundred Thirty Nine
with outgoing tails, insulating tape etc. For following size cables.(For 3 1/2 core x 120.0 Sq. mm (Sigma, MCI, Comet Make Only)
Providing & Erecting Flexible PVC insulated multistrand multicore 1.1 kv grade ISI marked copper wires of following size to be erected as 50.00 Mtr. 96.00 RS: Ninty Six only
directed. For 3 core 2.5 sq.mm. PVC insulated round copper wire ISI mark.
providng and erecting Approved make. energy meter 3 phase 4 wire unbalanced load 500 V.50A / 100A complete erected as directed with 1.00 Each 2586.00 RS:
Two Thousand Five Hundred Eighty Six only
necessary earth wire. Cat-iii
Suitable set of 3 Nos CTS for 100A and above as required for Energy Meter including testing charges as required by Electrical Inspector. 2.00 Each 2085.00 RS: Two Thousand Eighty Five
Providing & Erecting Mains with ISI marked, 1.1 KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC 51.00 Mtr. 21.00 RS: Twenty One only
insulated conforms to IS:694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears,
motor starters & control wiring) with required size of copper lugs, nuts and bolts if required. For One Wire 1.5 sqmm
21b For One Wire 2.5 sqmm 50.00 Mtr. 34.00 RS: Thirty Four only
21c For One wire 4.00 sq. mm 50.00 Mtr. 46.00 RS: Forty Six only
For One wire 10.00 sq. mm 50.00 Mtr. 114.00 RS: One Hundred
For One wire 16.00 sq. mm 50.00 Mtr. 176.00 RS: One Hundred
Seventy Six only
For One wire 25.00 sq. mm 29.00 Mtr. 293.00 RS: Two Hundred
Ninty Three only
For One wire 35.00 sq. mm 30.00 Mtr. 373.00 RS: Three Hundred
21a Seventy Three only
For One wire 50.00 sq. mm 30.00 Mtr. 583.00 RS: Five Hundred
Eighty Three only
For One wire 70.00 sq. mm 28.00 Mtr. 829.00 RS: Eight Hundred
21c Twenty Nine only
Supplying & Erecting of TATA Blue scope GI sheet having 0.45 mm thickness with Zinc Alluminium alloy coating Fixed with galvanized iron J 25.00 Sq.mtr 977.38 RS:
Nine Hundred Seventy Seven and Paise Thirty Eight only
or L hooks, bolts and nuts.
Item Description Qty Unit Rate Amount (Rs.)
23 Desiging,fabricating,testing at panel manufacuturer workshop and Providing & erecting at site weather proof, dust & vermin proof, 3.00 sq.Mtr 21500.00 RS: 64,500.00only
Twenty One Thousand Five Hundred
floor mounted front operated indoor type cubical panel board having IP-54 made from 2 mm. thick CRCA M.S. sheet for outer
body,gland plate & doors, 1.6 mm. thick CRCA M.S. sheet for internal partitions with necessary supporting angles, flats including
skirting, bending, drilling, welding, riveting with internal partitions & cable alley,rubber gromets, rib, control wires, backelite control
fuses as per requirements,sufficient nos. of hinges for doors, door locking arrangement, rubber gasket complete with Required
Nos. heavy Duty Connector with Cadmium plated nut and bolt for Anti rusting and earthing Al.busbar, nuts/bolts,washer etc as per
instruction of engineer-In-Charge. Seperatly supplied item like switchgears, busbars and PVC FRLSH copper wire with suitable
size for power interconnection,measuring instruments, foundation flange-bolts-base plates. cost of C channel/angle iron stand (1ft
to 2ft height as per cable size)shall be excluded of panel fabrication. The panel shall be supplied with Seven Tank chemical
process. which shall be carried out before applying painting, painted with powder coating. (The rates excludes the cost of
switchgears, busbars, interconnecting mains & Copper / Aluminium strip, fuse, meters etc. The dimension shall be measured
excluding base beams.switchgear of approved brand and specification shall be used and erected at CPRI approved panel
manufacturers only. Busbar compartment must be separate for easy termination of tails/cables and to avoid least distance of
punching holes in busbar. Panel depth shall be 350 mm.
electrical meter calibration report. Agency should design the panel in such a way that there should not be any excess in panel area
(sq.mtr) & length of bus-bar (mtr), if any excess is need to be done agnecy has to draw attention to GSPHCL at the time of
approval of G.A. drawing.
Loading and unloading of above item shall be done by hydra and skill work force under supervision of electrical engineer and
guidelines given by manufacturer to avoid damage to the item.
Size of door and Ele. room / Pump room shall be measure and provide to panel manufacturer to prepare GA drawing considering
the size of electrical room/pump room door and also inside size of it. Agnecy has to co-ordinate with civil agency for giving proper
dimenssion of electrical room/pump room to accomodeted panel easily.[Including Necessary numbering / marking on PANEL done
with red colour radium sticker as per site requirement and instructions given by EIC on site. Font / number size given by EIC on site
as per requirement] (See attached details specification of panel & manufacture also while quoting rate. [Manufacturer must be of
Gujarat state so three stage inspection can be done if required and service support]
24 Supplying and erecting tripple pole & neutral 440V / 500 V Panel mounting Copper Busbars with four equal Nos. of electrolyte bus 1.00 Rmt 4861.00 RS: Four Thousand Eight Hundred Sixty4861.00
having current density not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly wraped with colour insulating tape
for phase sequence of following current carrying capacity, erected with necessary bus bar supports / insulators, main cable socket
to each bar, erected in existing cubical panel with necessary connections.For electrolyte copper busbars Suitable for 300 Amp.
25 Providing and erecting following additional parts for panel mounting MCCBs for Extended operating rotary handle with pad lock 3.00 Each 952.00 RS: Nine Hundred Fifty Two only
with three position trip,off,on suitable for 25A to 250 A panel mounting. Company must be same as Switchgear company.
26 SITC of ATS with controller for 250 Amp of ampere capacity in existing housing with internal wiring and required accessories etc. 1.00 Nos. 83301.50 RS:
Eighty Three Thousand Three Hundred One and Paise Fifty
The switch has automatic transfer switch consists of an intelligent controller and a modular load break switch which automatically
transfers the load to the emergency power source when it detects the normal power source under/over voltage, under/over
frequency, or phase loss. The switch has three operational positions (Source I, Center-off, Source II). The switch has technical
specification as mentioned:
1. Rated insulation voltage:800 V
2.Rated impulse withstand volate: 8KV
3.Rated frequency:50/60HZ
4. Operational Volatge: 415 V
5.auxilary contact: 4 max
(socomec, schneider make or EIC)
27 Supplying and Erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 50 K.A. at 415 V. 3.00 Nos. 27477.00 RS:
Twenty Seven Thousand Four Hundred Seventy Seven on
having normal current rating 400 A. with Variable thermal & magnetic release suitable to work on A.C.supply 50 c/s. with all internal
connections spreader tinned copper & complete erected in existing 16 G.M.S. housing. housing. ICS=100% of ICU only
28 Providing and erecting Meter cover made from multi chamber hollow PVC sections of 20 mm thick having all the corner joints with 2.00 sq mtr 3306.00 RS: Three Thousand
PVC solution angles without using any screws, nails shutters having required size of eye glass and with necessary locking Three Hundred Six
arrangement hinged with box. The back of meter box should be fixed with timber. Hold fast for holding screws or nut bolts. only
Item Description Qty Unit Rate Amount (Rs.)
29 Providing and fixing of ABC Type Store Pressure Fire Extinguisher Having capacity 6 kg Filled with Mono Ammonium Phosphate 2.00 Each 1991.00 RS: One Thousand
Powder 50% confirms to IS 4308, Stored Pressure Type, UGTS Pressure Gauge, Can Height 530 mm, Diameter 150 ± 10mm, Nine Hundred Ninty One
Discharge Time 24 Sec, Controllable discharge mechanism, Jet Range 5 Meters, Average Discharge is 92%, applicable on Class only
A,B & C and electrically started Fire, Fire Rating 4A:144B, Can Construction : Deep drawn & CO2 Mig welded, EPDM(Ethylene
Propylene Diene Monomer) Rubber Hose with both end Aluminum clamped, Internal Coating - Epoxy Powder coating, External
Coating - Pure Polyester Powder coating (UV Resistant),Brass forged CE Marked valves with NRV & Auto Safety Release with
safety Pin is of SS material, Made up from 1.6mm thick sheet, Extinguishers confirmed to IS 15683:2018 and ISI marked.
Referance Weight:-Gross Weight 8.9 Kg, Empty Weight 2.9 Kg, 1. Necessary certificate & and guarantee must be attached,
OEM has to provide wall mounting heavy duty bracket/clamp, screw, hardware for installation. 3.Following printed marking
Manufacturing Date and Expiry Date must be mention on Extinguisher 4. Refilling period must be of 3 Years. Following Printed
marking on equipment must be required:- Model No, Capacity, Gross Weight, Content, Fire Rating, Batch No, Serial no, Mfg
Month, Refilling Due. [with necessary numbering / marking with oil paint by painter as instructions given by G.S.P.H.C.L engineer]
(Make: KANEX, MINIMAX,CEASEFIRE)
30 Providing and fixing of CO2 type High Pressure Portable 4.5 kg Fire Extinguisher, filled with Co2 Gas as per IS 15222, Control 2.00 Each 6526.00 RS: Six Thousand
discharge mechanism fitted with 1 Meter Wire Braided Hose & Electrical non-conductor Polyethylene Flat Horn with Diffuser Nozzle Five Hundred Twenty Six
for dispersed discharge of CO2, Discharge Time 12 Sec, Average Discharge is 95%, Applicable on Class B, C and electrically only
started Fire, Fire Rating 55B, Internal coating is not applicable & External coating is of enamel spray painting, Powder Coated
Handle, Valve Confirm to IS 3224 ISI Marked, CO2 Cylinder construction: hot spinning by seamless pipes & bearing ISI mark, Body
confirms to IS 7285 and PESO ( Petroleum and Explosives Safety Organization) APPROVED, Minimum Wall Thickness 4 to
mm, Extinguishers confirmed to IS 15683:2018 and ISI marked. Referance Weight:-Gross Weight 16.4, empty weight 11.9 Kg,
Necessary certificate & and guarantee must be attached, 2. OEM has to provide wall mounting heavy duty bracket/clamp, screw,
hardware for installation. 3.Following printed marking Manufacturing Date and Expiry Date must be mention on Extinguisher
Refilling period must be of 5 Years. Following Printed marking on equipment must be required:- Model No, Capacity, Gross Weight,
Content, Fire Rating, Batch No, Serial no, Mfg Month, Refilling Due. [with necessary numbering / marking with oil paint by painter
as instructions given by G.S.P.H.C.L engineer] (Make: KANEX, MINIMAX,CEASEFIRE)
Item Description Qty Unit Rate Amount (Rs.)
31 Providing and fixing of Automatic type 5 kg Fire Extinguishers Mono Ammonium Phosphate powder 50% Confirms to IS 4308, 2.00 Each 5240.00 RS: Five Thousand
Applicable fire classes A,B & C, UGTS Pressure Gauge, Can Height 370mm, Diameter 230 ± 10mm, Made up from 2 mm thick Two Hundred Forty
sheet, Body Construction Deep Drawn with MIG Welding technology, Brass forged sprinkler valves with Nozzle is specially only
designed to give more than 99% discharge. Together with orifice characteristic to cover adequately fire risks with scattering cone of
40 to 45° Angle. External Pure polyester (UV resistant) and Internal Epoxy polyester powder coated, Heat Sensitive Glass bulb of
68 °C. Area covered will be 2-2.5 m2 and volume of coverage is 7 m3. Referance Weight:-Empty Weight 2.64 kg, Full weight
kg, 1. Necessary certificate & and guarantee must be attached, 2. OEM has to provide heavy duty wall/ Ceiling mounting
Bracket/ clamp, screw, hardware for installation. 3.Following printed marking Manufacturing Date and Expiry Date must be mention
on Extinguisher 4. Refilling period must be of 3 Years. Following Printed marking on equipment must be required:- Model No,
Capacity, Gross Weight, Content, Fire Rating, Batch No, Serial no, Mfg Month, Refilling Due. [with necessary numbering / marking
with oil paint by painter as instructions given by G.S.P.H.C.L engineer] (Make: KANEX, MINIMAX, CEASEFIRE)
Total Electrical Amount In Rs.
Assistant Engineer (Elect.) Dy. Ex. Engineer (Ele) Executive Engineer (Elect.)
G.S.P.H.C.Ltd. G.S.P.H.C.Ltd. G.S.P.H.C.Ltd.
Ahmedabad Vadodara Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. DG-L- barrack- VOLUME 1 - OK.pdf
2.DG-L barrack- VOLUME 2-OK.pdf
3.DG-L barrack- VOLUME 3-OK.pdf
4.DG-L barrack- VOLUME 4-OK.pdf
5. DMO_2941_01-Apr-2026_744.pdf
6. COMMON CONDITION-OK.pdf
7. DG Set and ELE condition.pdf
8.Make List.pdf
L Barrack-125 KVA DG SET-SCH-B - R1 FINAL.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .