Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.1 CrAdmitted-Finance 245 2 RAJPUR ROAD OPPOSITE HOTEL MADHUBAN DEHRADUN | ₹3.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.1 CrAdmitted-Finance | ₹3.1 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Modern Electric Company L1 | AR ENTERPRISES L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, erection, testing and commissioning of 230V, single phase 2 wire AC to 24V DC Batteries charger with semiconductor/IGBT full wave rectifier with auto /manual float cum boost facility complete with 24V DC, 200 AH sealed maintenance free batteries including one no. distribution board having 63 Amps DP MCCB as incomer and 12 Nos. 20/16A DP MCB's (D.C. duty) as outgoing complete as required and as per technical specifications. | 1 | Set | 2,13,425 ₹2.1 L | 2,15,560 ₹2.2 L |
| 2.00 | Design, manufacture, supply, installation, testing and commissioning at site of 630 kVA, 11/0.433KV, 3 phase, 50 Hz, delta/star connected, Oil type transformer complete with all fittings and accessories, On Load Tap Changer, with RTCC panel, AVR relay, diagram & rating plate, winding temperature & oil temperature indicator and wiring upto marshalling box, lifting lugs, HT Busduct box, LT cable connection etc. including all accessories required and as per Technical specification. The losses of the transformer shall be as per IS 1180, Level 1. Voltage Ratio : 11/0.433KV Vector Group : Dyn11 Tap Range (On Load] : +5% to -15% step of 1.25% Insulation Class : 'A' Terminal arrangement (HV) : 3C x 240 Sqmm (11 kV), Terminal arrangement (LV) : LT Cable Box (Suitable for 4 Nos.Run 3.5C x 300 Sqmm.) | 1 | Set | 21,90,000 ₹21.9 L | 22,30,000 ₹22.3 L |
| 3.00Two Pole structure with GODO switch ply, erection, testing and commissioning of Two Pole (double pole) structure in position complete with 8M long ISMB 200 and necessary anti climbing devices including painting with one coat of primer and two coats of aluminium paint as required. The poles to be erected shall be two meter deep in cement concrete foundation of 1:3:6 with collar including excavation in soil as per site condition and making good complete as required.Set-01, Supply, erection, testing and commissioning of steel work in position including clamps frame work of flats, angle channel with fabrication work including cutting, bending, welding, drilling bolting etc. as per required design and drawing with one coat of primer & two coats of aluminium paint as required. 1200 Kg Supply, erection, testing and commissioning of Stay Set complete with 19mm dia 1.8 metre long stay rod, stay clamps, turn buckle (19mm x 600mm), 7/4.00mm dia stranded G.I. stay wire and strain insulator etc. G.I. anchor plate of size 300 x 300 x 6.4mm thick in cement concrete 1:3:6 foundation including excavation of soil and refilling of the same after casting of foundation for anchor plate. 02 Set Supply & erection of Disc Insulator suitable for 11 KV complete with GI bolts, nuts, straps etc. as required for fixing (Set of three discs). Set- 01 , Supply & erection of Pin insulator suitable for 11 KV complete with GI spindle and nuts as required. Each 3 Supply, erection, testing and commissioning of 11 KV, 3 phase, 200 Amps gang operated switch complete with arcing horns, arcing contacts, vertical drop out fuses, 32 mm dia. G.I. down rod with operating handle and locking devices, necessary MS channel/angle iron brackets, clamps insulators & connections etc. and all hardware as required, complete with earthing of system & conforming to IS: 19813. 01 Set | |||||
| 4.00 | Supply, erection, testing & commissioning of 11 KV distribution class non-linear resistor type lightning arrestor conforming to latest I.S. Code, including connection of lightning arrestor from earthing pit and as well as with 11 KV line including supply and installation of jumper connection complete as required. Each 3, Supply, erection, testing and commissioning of 32mm x 6mm G.I. earth strip including clamps and binding etc. as required as per drawings. 100 mtr Supplying and erecting of the 150mm dia. 'B' class G.I. pipe complete with clamps and all accessories as required for fixing for support & protection of HT cable on Two Pole Structure. 8 mtr Providing and laying of 600 x 600 x 6.3 mm thick GI plate electrode, with 2 nos. 50 X 6 mm GI strips from earth plate electrode to inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 1000 X 500 mm with concrete base CI manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit upto permanent moisture level but not less than 3 meters and back filling as required.(for body earthing of 8 metre pole and lightning arrester) 02 nos Two Pole Structure-11 KV as per State Electricity Board | 1 | Job. | 9,08,000 ₹9.1 L | 9,06,000 ₹9.1 L |
| 5.00 | SITC of HT Metering Panel (SEB's) The instrument and relay panel fitted with: 1- digital voltmeter scaled 0-12000 volt with 3 way and OFF selector switch. 1- digital Ammeter scaled 0-100 amps with 3 way and OFF selector switch. 1- Triple pole I.D.M.T. overcurrent & earth fault relay with two outer elements connected for overcurrent protection and the middle element for earth fault protection overcurrent setting 50% - 200% Earth fault setting 20% - 80% (51 and 51N) 1 No. SEB approved digital Trivector meter with MDI in KVA of accuracy class - 0.5. Note: The contractor shall get the Trivector meter, CTs' & PT tested by SEB and the charges for liasioning for the same will be paid extra. One Set of Phase Indicating Lamps. 1- set of Red/Green indicating lamps for close and open position 1- Amber indicating lamp for auto trip 1- clear indicating lamp for trip circuit healthy 1- set of white indicating lamps one per phase 1 - blue indicating lamp for spring charged 2 Nos. indoor cable end box suitable for 3C x 240 sq.mm. 11 KV(E), aluminium conductor XLPE Ar. cable (Incoming & Outgoing cable). Note: The contractor shall ensure that the above panel meets the requirement as insisted by State Electricity Board (Uttarakhand) authorities for satisfactory operation and as per the Drawings SITC Rate for 11 kV HT metering Panel as per specification & as described above | 1 | Job. | 6,04,806 ₹6.0 L | 6,12,800 ₹6.1 L |
| 6.0011 KV HT PANEL BOARD (SINGLE BREAKER I/C cum O/G) (One incomers, and Two out goings) Design, manufacture , supply, installation, testing and commissioning of 800 Amps., 11 KV, 26.3 KA breaking capacity (500 MVA) VCB panel board fabricated out of 2mm sheet steel, dust tight, vermin proof, totally enclosed and fully interlocked, IP 4X protection, cubical type, floor mounting, extensible on both sides, suitable for indoor operation at 11 KV, 3 phase, 50 Hz, AC supply complete with rack in - rack out mechanisms, switches, plugs & sockets and all required accessories, cable termation box at back with bottom cable entry for cable size upto 3 core 240 sq.mm. armoured cable for each section, internal copper wiring, earth terminals , painting etc. as required , as per specifications & SLD with the following equipped switch gears and accessories complete in all respect. | |||||
| 7.00Incomers - 1 Set. Each feeder shall consist of : 800 Amps., 11KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete.11 KV / 110 volt PT of class 1.0 accurancy & 100 VA burden. Set of dual core dual ratio CTs of 150/75/5/5 Amps. of 15 VA burden and accurancy class 1.0 for metering and class 5 P 10 for protection. 96mm x 96mm type 800 Amp ammeter Digital type with ASS 96mm x 96mm square Digital type Voltmeter protected by HRC fuses / MCBs with inbuilt VSS Digital Trivector Meter (Smart Controller) having 30 days memory, Class 0.5 with MDI & RS 485 port. Frequency meter Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete. Master trip & trip circuit supervision relay, Antipumping Relay, Auxiliary Relay etc. Limit Switch for tests and service position, circuit breaker control switch (T/N/C). Trip coil operation at 24 Volts DC through battery bank. Limit switch for tests & service position, circuit breaker control switch (T/N/C) Trip / Closing coil operation at 24 Volts DC through battery bank, Busbar 800A TP Copper bus bar | |||||
| 8.00 | OUT GOING Each feeder shall consist of : 800 Amps., 11KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete. Set of dual core CTs of 150/ 5 Amps.CT for 630 KVA TRF, of 15 VA burden & accurancy class 1.0 for metering and class 5 P 10 for protection. 96mm x 96mm square Digital Ammeter with inbuilt ASS Micro processor based feeder protection numerical relay with adjustable O/L, E/F and short circuit protection with communication port. (O/L Setting 50-200% and E/F setting 20-80%) Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete. Annunciator window (with minimum 6 window) for feeder alarm / tripping annunciations with electronic hooter Master trip & trip circuit supervision relay, Antipumping Relay, Auxiliary Relay complete. Limit switch for tests & service position, circuit breaker control switch (T/N/C) Trip and closed coil operation at 24 Volts DC through Ppower pack Complete in all Respects. 11 KV HT PANEL BOARD (SINGLE BREAKER I/C cum O/G) | 1 | Job | 10,28,000 ₹10.3 L | 10,40,750 ₹10.4 L |
| 9.00 | DG SET (500KVA) Designing, Supply, testing, commissioning & Installation of 500 KVA DG set with cpcb4+ compliance both for noise and emissions, radiator cooled, 3 phase, 4 wire, 50 cycles 415 +(-)1% volts AC alternator with AREP winding coupled directly on a common MS fabricated base frame with diesel engine with STD isolator breaker(MCCB) panel inside canopy , fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. Fuel Tank: Daily service fuel tank of standard capacity fabricated out of 2 mm thick M.S. Sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with residential exhaust silencer. Starting System: 12v/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 nos. of batteries (160 Amp. Hour capacity lead acid type) as required as per specifications.Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. Tools, standard panel Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT's) Metering set 60/5A/11 OV (Amp. Meter, Volt Meter) Overload protection for DC-1 No. Battery Charger 24V DC Complete in all respect. | 1 | Set | 72,55,000 ₹72.5 L | 73,32,000 ₹73.3 L |
| 10.00 | DG SET (160KVA) Designing, Supply, testing, commissioning & Installation of 160 KVA DG set with cpcb4+ compliance both for noise and emissions, radiator cooled, 3 phase, 4 wire, 50 cycles 415 +(-)1% volts AC alternator with AREP winding coupled directly on a common MS fabricated base frame with diesel engine with STD isolator breaker(MCCB) panel inside canopy , fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. Fuel Tank: Daily service fuel tank of standard capacity fabricated out of 2 mm thick M.S. Sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with residential exhaust silencer. Starting System: 12v/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 nos. of batteries (160 Amp. Hour capacity lead acid type) as required as per specifications.Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. Tools, standard panel Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT's) Metering set 60/5A/11 OV (Amp. Meter, Volt Meter) Overload protection for DC-1 No. Battery Charger 24V DC Complete in all respect. | 1 | Set | 23,20,947 ₹23.2 L | 23,37,000 ₹23.4 L |
Tender Value
₹3.1 Cr
EMD Value
₹6.1 L
Closing Date
3 Feb 2026, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
External Electrification and Allied works for Academic Blocks at Patwadangar in Kumaun University Campus Nainital, Under MERU Scheme
2026_BRID3_91144_2
147/BRIDCUL/1043/26 Dated 17.01.2026
Open Tender
Electrical Works
540 days
Nainital
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹6.1 L
BRIDCUL Dehradun
6 Feb 2026
20 Jan 2026
3 Feb 2026
20 Jan 2026
3 Feb 2026
28 Jan 2026
27 Jan 2026
Supply, erection, testing and commissioning of 230V, single phase 2 wire AC to 24V DC Batteries charger with semiconductor/IGBT full wave rectifier with auto /manual float cum boost facility complete with 24V DC, 200 AH sealed maintenance free batteries including one no. distribution board having 63 Amps DP MCCB as incomer and 12 Nos. 20/16A DP MCB's (D.C. duty) as outgoing complete as required and as per technical specifications.
Design, manufacture, supply, installation, testing and commissioning at site of 630 kVA, 11/0.433KV, 3 phase, 50 Hz, delta/star connected, Oil type transformer complete with all fittings and accessories, On Load Tap Changer, with RTCC panel, AVR relay, diagram & rating plate, winding temperature & oil temperature indicator and wiring upto marshalling box, lifting lugs, HT Busduct box, LT cable connection etc. including all accessories required and as per Technical specification. The losses of the transformer shall be as per IS 1180, Level 1. Voltage Ratio : 11/0.433KV Vector Group : Dyn11 Tap Range (On Load] : +5% to -15% step of 1.25% Insulation Class : 'A' Terminal arrangement (HV) : 3C x 240 Sqmm (11 kV), Terminal arrangement (LV) : LT Cable Box (Suitable for 4 Nos.Run 3.5C x 300 Sqmm.)
Two Pole structure with GODO switch ply, erection, testing and commissioning of Two Pole (double pole) structure in position complete with 8M long ISMB 200 and necessary anti climbing devices including painting with one coat of primer and two coats of aluminium paint as required. The poles to be erected shall be two meter deep in cement concrete foundation of 1:3:6 with collar including excavation in soil as per site condition and making good complete as required.Set-01, Supply, erection, testing and commissioning of steel work in position including clamps frame work of flats, angle channel with fabrication work including cutting, bending, welding, drilling bolting etc. as per required design and drawing with one coat of primer & two coats of aluminium paint as required. 1200 Kg Supply, erection, testing and commissioning of Stay Set complete with 19mm dia 1.8 metre long stay rod, stay clamps, turn buckle (19mm x 600mm), 7/4.00mm dia stranded G.I. stay wire and strain insulator etc. G.I. anchor plate of size 300 x 300 x 6.4mm thick in cement concrete 1:3:6 foundation including excavation of soil and refilling of the same after casting of foundation for anchor plate. 02 Set Supply & erection of Disc Insulator suitable for 11 KV complete with GI bolts, nuts, straps etc. as required for fixing (Set of three discs). Set- 01 , Supply & erection of Pin insulator suitable for 11 KV complete with GI spindle and nuts as required. Each 3 Supply, erection, testing and commissioning of 11 KV, 3 phase, 200 Amps gang operated switch complete with arcing horns, arcing contacts, vertical drop out fuses, 32 mm dia. G.I. down rod with operating handle and locking devices, necessary MS channel/angle iron brackets, clamps insulators & connections etc. and all hardware as required, complete with earthing of system & conforming to IS: 19813. 01 Set
Supply, erection, testing & commissioning of 11 KV distribution class non-linear resistor type lightning arrestor conforming to latest I.S. Code, including connection of lightning arrestor from earthing pit and as well as with 11 KV line including supply and installation of jumper connection complete as required. Each 3, Supply, erection, testing and commissioning of 32mm x 6mm G.I. earth strip including clamps and binding etc. as required as per drawings. 100 mtr Supplying and erecting of the 150mm dia. 'B' class G.I. pipe complete with clamps and all accessories as required for fixing for support & protection of HT cable on Two Pole Structure. 8 mtr Providing and laying of 600 x 600 x 6.3 mm thick GI plate electrode, with 2 nos. 50 X 6 mm GI strips from earth plate electrode to inspection chamber, 50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 1000 X 500 mm with concrete base CI manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit upto permanent moisture level but not less than 3 meters and back filling as required.(for body earthing of 8 metre pole and lightning arrester) 02 nos Two Pole Structure-11 KV as per State Electricity Board
11 KV HT PANEL BOARD (SINGLE BREAKER I/C cum O/G) (One incomers, and Two out goings) Design, manufacture , supply, installation, testing and commissioning of 800 Amps., 11 KV, 26.3 KA breaking capacity (500 MVA) VCB panel board fabricated out of 2mm sheet steel, dust tight, vermin proof, totally enclosed and fully interlocked, IP 4X protection, cubical type, floor mounting, extensible on both sides, suitable for indoor operation at 11 KV, 3 phase, 50 Hz, AC supply complete with rack in - rack out mechanisms, switches, plugs & sockets and all required accessories, cable termation box at back with bottom cable entry for cable size upto 3 core 240 sq.mm. armoured cable for each section, internal copper wiring, earth terminals , painting etc. as required , as per specifications & SLD with the following equipped switch gears and accessories complete in all respect.
Incomers - 1 Set. Each feeder shall consist of : 800 Amps., 11KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete.11 KV / 110 volt PT of class 1.0 accurancy & 100 VA burden. Set of dual core dual ratio CTs of 150/75/5/5 Amps. of 15 VA burden and accurancy class 1.0 for metering and class 5 P 10 for protection. 96mm x 96mm type 800 Amp ammeter Digital type with ASS 96mm x 96mm square Digital type Voltmeter protected by HRC fuses / MCBs with inbuilt VSS Digital Trivector Meter (Smart Controller) having 30 days memory, Class 0.5 with MDI & RS 485 port. Frequency meter Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete. Master trip & trip circuit supervision relay, Antipumping Relay, Auxiliary Relay etc. Limit Switch for tests and service position, circuit breaker control switch (T/N/C). Trip coil operation at 24 Volts DC through battery bank. Limit switch for tests & service position, circuit breaker control switch (T/N/C) Trip / Closing coil operation at 24 Volts DC through battery bank, Busbar 800A TP Copper bus bar
OUT GOING Each feeder shall consist of : 800 Amps., 11KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete. Set of dual core CTs of 150/ 5 Amps.CT for 630 KVA TRF, of 15 VA burden & accurancy class 1.0 for metering and class 5 P 10 for protection. 96mm x 96mm square Digital Ammeter with inbuilt ASS Micro processor based feeder protection numerical relay with adjustable O/L, E/F and short circuit protection with communication port. (O/L Setting 50-200% and E/F setting 20-80%) Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete. Annunciator window (with minimum 6 window) for feeder alarm / tripping annunciations with electronic hooter Master trip & trip circuit supervision relay, Antipumping Relay, Auxiliary Relay complete. Limit switch for tests & service position, circuit breaker control switch (T/N/C) Trip and closed coil operation at 24 Volts DC through Ppower pack Complete in all Respects. 11 KV HT PANEL BOARD (SINGLE BREAKER I/C cum O/G)
DG SET (500KVA) Designing, Supply, testing, commissioning & Installation of 500 KVA DG set with cpcb4+ compliance both for noise and emissions, radiator cooled, 3 phase, 4 wire, 50 cycles 415 +(-)1% volts AC alternator with AREP winding coupled directly on a common MS fabricated base frame with diesel engine with STD isolator breaker(MCCB) panel inside canopy , fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. Fuel Tank: Daily service fuel tank of standard capacity fabricated out of 2 mm thick M.S. Sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with residential exhaust silencer. Starting System: 12v/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 nos. of batteries (160 Amp. Hour capacity lead acid type) as required as per specifications.Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. Tools, standard panel Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT's) Metering set 60/5A/11 OV (Amp. Meter, Volt Meter) Overload protection for DC-1 No. Battery Charger 24V DC Complete in all respect.
DG SET (160KVA) Designing, Supply, testing, commissioning & Installation of 160 KVA DG set with cpcb4+ compliance both for noise and emissions, radiator cooled, 3 phase, 4 wire, 50 cycles 415 +(-)1% volts AC alternator with AREP winding coupled directly on a common MS fabricated base frame with diesel engine with STD isolator breaker(MCCB) panel inside canopy , fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. Fuel Tank: Daily service fuel tank of standard capacity fabricated out of 2 mm thick M.S. Sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with residential exhaust silencer. Starting System: 12v/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 nos. of batteries (160 Amp. Hour capacity lead acid type) as required as per specifications.Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. Tools, standard panel Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT's) Metering set 60/5A/11 OV (Amp. Meter, Volt Meter) Overload protection for DC-1 No. Battery Charger 24V DC Complete in all respect.
Supplying & fixing exhaust gas piping of 200mm dia. Welded black MS, B class pipe confirming to IS:3589 cut to required lengthsand installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/rockwool, 50mm thick wiremesh & aluminium clading etc, as required as per specification.(500kVA DG Set)
Supplying & fixing exhaust gas piping of 100mm dia. Welded black MS, B class pipe confirming to IS:3589 cut to required lengthsand installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/rockwool, 50mm thick wiremesh & aluminium clading etc, as required as per specification. (For 160 kVA DG Set)
Fabrication, supply & erection of MS support for fixing of exhaust piping and MS structure including Angle / chanels / flats / beam as per approved drawings for supporting of DG exhaust stack from ground. floor level and above terrace level complete in all respect.
Providing and fixing in position following size of heavy duty stainless steel flanged expansion bellows with G.I. nut bolt washers for DG fume piping complete with GI nut bolt washers etc. complete as required. (for DG Sets) 200 mm dia
Providing and fixing in position following size of heavy duty stainless steel flanged expansion bellows with G.I. nut bolt washers for DG fume piping complete with GI nut bolt washers etc. complete as required. (for DG Sets) 100 mm dia
Day Oil Tank Supply, installation, testing & commissioning of 990 litres capacity day oil storage tank fabricated from 6 mm thick MS plates. Tank shall include 450 mm ID manhole cover, level indicator with duly calibrated scale and flanged connection for inlet, outlet, overflow drain and probe provision for level controller & breather.
Oil Piping Supply, installation, testing & commissioning of the following MS class ‘C’ pipes cut to required lengths and installed with all welded joints. Providing the necessary fittings like elbows, tees and reducers, sockets, hot dip galvanized supports and accessories including ceiling Hanger, Hardware complete as per site requirement. 20 mm dia MS pipes(For 500KVA DG Set)
SITC of Capacitor Panel (250 kVAR) INCOMER 1 No. 630A TPN mcCB (35KA) METERING & INDICATION1 set of phase indicating lamps 1 No. 16 step-Microprocessor APFC controller/Relay(Dual source purpose) shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel. Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.BUS-BAR 1 Set of 800A TPN Aluminium Bus Bar with colour coded PVC Sleeves OUTGOINGS 3 Nos.of 160A TP MCCB (25 KA) each with 3 Nos. 50 KVAR MPP Heavy Duty capacitor Bank each with capacitor duty contactor.3 Nos.of 80A TP MCCB (25 KA) each with 3 Nos. 25 KVAR MPP Heavy Duty capacitor Bank each with capacitor duty contactor. 1 Nos.of 63A TP MCCB (25 KA) each with 1 Nos. 20 KVAR MPP Heavy Duty capacitor Bank each with capacitor duty contactor. 1 Nos.of 32A TP MCCB (18 KA) each with1 Nos. 5 KVAR MPP Heavy Duty capacitor Bank each with capacitor duty contactor. Capacitor Panel (250 kVAR) as described above
FEEDER PILLAR(IP-65) Design, Fabrication, Supply, Erection, Testing and commisioning of Powder coated, Weather Proof Double door type Feeder pillar fabricated out of 14 guage CRCA sheet steel in cubical, free standing, dust and vermin proof, with reinforcement of suitable size angle iron, channel, T -iron or flats as required. Feeder pillar shall be treated with all anti-corrosive process before painting as per specification. Feeder Pillar shall be suitable for 415V, 3-Phase, Four wire, 50 Hz supply complete with earth bus and lifting hooks as required in case of large panels. Approval shall be taken for each panel before fabrication. (All hardwares like nuts and bolts used shall be Galvanized and Zinc passivated) INCOMER 1No. 63A FP MCB(10 KA) Metering & Indication 1 set of R,Y,B phase indicating lamps,1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB, 1 No. (0-63A) Ammeter with ASS with 3 nos. 63/5A CT's BUS-BAR1 Set of 100A TPN Aluminium Bus Bar with colour coded PVC SleevesOUTGOINGS:-2 nos 32 A TPN RCBO 30mA,10 kA with thermal magnetic releases each with Dual setting 24 hour calibrated time switch with automatic adjustments for seasonal variations based on site settable latitude for automatic operation of the supply, 32 amp TP Contactor for operation of the outgoing supply through the Time Switch and each with 12 nos 10/20 amp SPN 10 kA MCB's as outgoing. 2 nos 32 amp TPN MCB (10 kA) 2 nos 25 amp DP MCB (10 kA) 2 nos 16 amp DP MCB (10 kA) External Feeder Pillar as described above
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. 3cX4 sqmm Copper conductor
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. 4x10 sq.mm(25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. 3-1/2 x120 sqmm(45mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. 3-1/2 x185 sqmm(57mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. 3½ X 300 sq. mm (70mm)
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 3cX4 sqmm Copper conductor
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 10 sq. mm
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 120 sq. mm
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 185 sq. mm
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 300 sq. mm
Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. 10 sq. mm
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Laying of one number XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required Above 120 sq. mm and upto 400 sq. mm
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 240 sq. mm
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 240 sq. mm
Supply of following sizes of 11KV XLPE grade multicore stranded aluminium conductor (Earthed), XLPE insulated & PVC sheathed armoured cable conforming to IS: 7098 (Part-I) 1988 complete as required and as per specification encolsed. 3 Core, 240 Sq.mm
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe in ground from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. The strip in ground shall be 600mm deep.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe in ground from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. The strip in ground shall be 600mm deep.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supply & fixing of 6.5 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 155 mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect.
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 52 watt to 72 Watt. Confirming to IP66 Protection complete in all respect. AAA
Supply of totally enclosed min. 45 W Post Top Light luminaire, Efficiency not less than 110 lumens/watt with lenses, the operating CCT shall be 5700-6500K with CRI of ≥70. consisting of High-quality Pressure die-cast aluminum housing LM6 alloy, heat resistant toughened glass/polycarbonate cover, IP 66, with 4 kV surge protection minimum suitable for operation 230+/-10%, 50 Hz Ac supply with all accessories compete wiring from junction box to lights as required as required
SITC GATE LIGHT WITH 70 WATT SODIUM VAPOUR LAMP complete in all respect.
SITCof 6 MTR WIDE RFID BOOM BARRIER RFID base boom barier with 6 metre wide Strong aluminium arm with rubber guard, Strong aluminium arm with rubber guard, Manual lock release by key in case of power failure, Green light and red light indicating the position of the beam, Connections for infrared photocell, loop detector & IC system for other functions, Stop and reverse operation safety devices, Provision for connecting an RFTD system. Function Open the door by scanning the tag. After being stopped for a specific time, the system will automatically send a signal to close the barrier The system can be configured with an ro card reader, allowing addition and deletion of users. Technical Specification Clear opening width 6 mtr Power Supply- 230 V ~I 50 - 60 Hz Control Panel- 24V Opening Time- 1 - 2 s/90°Protection Rating- IP 54 Operating Temprature- -20 degreeto +50 degree Complete in all respect.
Supply and fixing of fire extinguisher, ABC Type 4.00 kg. Capacity (ISI Marked IS: 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of fire extinguisher, ABC Type 6.00 kg. Capacity (ISI Marked IS: 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of C02 type fire extinguisher 6.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge.
Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work
Supply and laying of 1800mm x 900mm x 12mm thick chequered rubber matting of tested quality.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
sbdexternalmerupatwadangerf.pdf
Tender Documents • 1.80 MB
BOQ_107965.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid