Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹40,000
Closing Date
29 Jun 2026, 6:10 pm
The E.E.(O&M), Sachin Division
Tenderization for ARC Work of Laying testing & commissioning of 11/22 KV UG XLPE CABLE with 11/22 KV Cable End Termination & ST joint Kits (to be Supplies by Agency) along with Erection of HT,LT & TC , Maintenance works under CFC and if required any other Sdn under jurisdiction of Sachin Division under ND and if Required Any other Scheme.
313786
SD/O&M/EXP/26/688 Date:09.06.2026
Open
Electrical Works
Surat
6 documents required · 6 mandatory
₹1,180
Online Payment in DGVCL Sachin Division Account
₹40,000
12 Jun 2026
12 Jun 2026
12 Jun 2026
29 Jun 2026
12 Jun 2026
The statement showing items of works to be carried out for erection work of HT/LT lines , T/C ,Laying Testing &
Commissioning of XLPE UG CABLE & maintenance of feeders for various scheme for Various sub division under
the control of Sachin (O&M) Division.
HT,LT &TC Revised as per Letter No DGCS/1408/01/2025 Approved Date: 27-01-2025
Ammendment HT,LT &TC Revised as per Letter No DGCS/0693/02/2025 Approved Date: 12-02-2025
Maintenance Revised as per Letter No DGCS/1410/01/2025 Approved Date: 27-01-2025
UG Cable Revised as per Letter No DGCS/1411/01/2025 Approved Date: 27-01-2025
Name of Work :- Rate contract for erection of HT/LT line & T/C , UG work for various scheme work for SDN office
under Sachin Division Office. ( For Works Up to 200 MTR UG + OH Works)
ITEM CODE Details of Works Qty Unit Amount
Labour charge for excavation of cable trench of 400mm
width x 1200mm depth, in any type of soil for laying of cable
1 9925000001 of size up to 240 mm2 (For additional cable 200 mm Meter 72
additional width shall be considered i.e. half trench length is
to be considered)
Labour charge for excavation of cable trench of 600mm
width x 1200mm depth, in any type of soil for laying of cable
2 9925000002 of size up to 240 mm2 (For additional cable 200 mm Meter 109
additional width shall be considered i.e. half trench length is
to be considered)
Labour charge for excavation of cable trench of 400mm
width x 1500mm depth, in any type of soil for laying of cable
3 9925000003 of size up to 240 mm2 (For additional cable 200 mm Meter 91
additional width shall be considered i.e. half trench length is
to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of
size up to 240 mm2 & preparation of sand layer 100mm
thick, in the cable trench & covering the cable with 150 mm
dia (Inner), thickness 25 mm, 1.0 meter long RCC half
round muffs and providing and fixing of 4inch width yellow
4 9925000004 colour polyethylene tape with printing "CAUTION Meter 171
ELECTRIC CABLE BELOW" at 0.75 m depth from ground
surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as
to protect cable from mechnical injuries, refilling the same,
as per Instruction of Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger machine
without damage to surface road at max 2.0 mtrs depth &
putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.
8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of
11KV/22KV XLPE cable of size up to 240 mm2 in HDPE
5 9925000005 pipe, as per Site Condition (excluding cost of pipe). The Meter 860
detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment for
HDD is must required to be submitted. HDD to be carried
out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and
as per instruction of EIC.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Labour charge for horizontal drilling manually without
damage to surface road at max 2.0 mtrs depth & putting of
6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV
XLPE cable of size up to 240 mm2 size, as per Site
Condition (excluding cost of pipe). The detail map and
excell sheet(hard and soft copy) indicating the respective
depth and distance from adjacent landmark for each
segment of cable to be submitted. Drilling to be carried out
at depth Minimum 1.2 mtrs to 2.0 mtrs as per site conditions
as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D.
8.5 mm thickness H.D.P.E. pipe confirms to IS 4984 and
BIS certification for laying of underground 11KV / 22KV
XLPE cable up to 240 mm2 size.
Labour work for RCC concreting on disputed location and
repairing of damage portion of road crossing for the work
carried out for roads crossing as well as concreting &
muffing of ploes including all materials (1:2:4)
Providing & fixing concrete stone route marker of 300 mm
width x 150 mm thick x 650 mm height embedded in earth at
least 300 mm below & 350 mm above ground level
respectively at distance approx 50 meters along the length
of cable. The RCC concreting (1:2:4)(all necessary
maeterials will be in bidder's scope) of route marker is to be
carried out 300 mm width x 150 mm thick x 300 mm below
9 9925000009 ground level as per instruction of EIC. The route marker No. 446
should be with name of company with approved yellow
colour-DGVCL. The distance from marker to cable and
cable depth with feeder name etc., marked with arrow sign
is to be painted on it.The route marker is to be fixed at
location near to any fixed permanent location (not
necessary to fix exact on top of cable) as per instruction of
Erection of D.P. (double pole) structure using 9 / 11 Mtr.
RSJ pole with cable connection arrangement along with
10 9925000010 fitting of necessary fabrication for 11KV cable including No. 2026
excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole
with cable connection arrangement along with fitting
11 9925000011 ofnecessary fabrication for 11KV/22 KV cable including No. 1047
excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC
pole with cable connection arrangement along with fitting of
12 9925000012 necessary fabrication for 11KV cable including excavation No. 1416
of pit & refilling of earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole
with cable connection arrangement along with fitting
13 9925000013 ofnecessary fabrication for 11KV/22 KV cable including No. 613
excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of
size up to 240 mm2 on DP Structure with fixing of 02 Nos
polymer cleats on top and middle part.Polymer cleats, nut
bolts etc. fixing material to be provided by contractor.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Providing & fixing of 6.11kg/cm2 , class-4,Green color,
110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to
IS 4984 and BIS certification on the erected DP structure for
the mechanical protection of cable by inserting the cable
15 9925000015 inside HDPE pipe. The HDPE pipe shall be erected in such Per Job 1461
a way that 300mm shall be below the ground level and the
rest 2700 mm shall be supported on the DP Structure with
01 No Polymer cleat.All materials including polymer cleat
and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia
class-B GI pipe with pit to be filled with salt & coke and
construction of chamber as per DGVCL Drg. No. dg /100 for
DP and cable. The earthing pit should be joined with cable
by G.I. strip of size 1” width & 2 mm thick. All material GI
pipe, Coke, Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations
17 9925000017 (outdoor) for upto 11kV 3C x 185 mm2 size XLPE cable No. 3635
as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations
18 9925000018 (outdoor) for upto 22 kV 3C x 185 mm2 size XLPE cable as No. 6231
per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor)
19 9925000019 for upto 11kV 3C x 185 mm2 size XLPE cable as per No. 3635
DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations
20 9925000020 (indoor) for upto 22 kV 3C x 185 mm2 size XLPE cable as No. 6231
per DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for
21 9925000021 upto 11kV 3C x 185 mm2 size XLPE cableas per DGVCL No. 6774
technical specification.
Supply & fixing of heat shrinkable straight through joint type
22 9925000022 for upto 22kV 3C x 185 mm2 size XLPE cable as per No. 11590
DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm
wide x 1200 mm deep joint pits for installation of 11kV /
22kV Straight through joints as per instruction of engineer-
in-charge & covering the cable with 150 mm dia (Outer),
thickness 25 mm, 1.0 meter long RCC half round muffs &
refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from
11KV/22KV XLPE cable after removal of semi conducting
layer and applying of PVC heat shrinkable anti-tracking core
insulating tubing (1.1KV), on both end terminal using
Aluminium long barrel heavy duty up to 240 sq mm lugs,
24 9925000024 Aluminium bus connector. Taping with PG- clamp for bus No. 1661
conductor as per drawing and as per instruction of EIC. The
Alluminium lugs and PG clamp shall be covered with
11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable
will be in scope of DGVCL while all other materials will be in
bidder's scope)
Testing of cable at various points and commissioning
25 9925000025 the feeder as per instruction of engineer-in-charge.Test No. 2125
result shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete
layout drawings with GIS mapping as per actual cable
routing showing road crossing, HDPE pipe sleeving, jointing
locations, markers etc.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Providing and fixing of Sign Board at junction point Made
out of 2 mm aluminium sheet size 750x300 mm (2.5 x 1ft)
rectangle, as per design, pre treated with phosphate
process and acid etching coated with one coat of epoxy
primer and two coats of best quality paints, refloctrorised
with Hi-Intensity retro – reflective sheeting as per the latest
and frame fabricated from suitable size iron angle. The Sign
27 9925000027 Board is to be fixed on the base prepared from channel and No. 10023
bracing angles which is grouted by means of cement
concreting of 1:2:4 for size of 300 mm dia x 800 mm height
(500 mm to be grouted in ground). The details to be
displayed on sign board will be given by In-charge
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on
Distribution Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft)
as per design, pre treated with phosphate process and acid
etching coated with one coat of epoxy primer and two coats
28 9925000028 of best quality paints, refloctrorised with Hi-Intensity retro- No. 2805
reflective sheeting as per the latest and frame fabricated
from suitable size iron angle. The Sign Board (Danger
Board is to be fixed at the location as per instruction of In-
charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x
mm (W) from 3 mm aluminium sheet along with 1.0 mm dia
aluminium binding wire for fixing of aluminium tag near end
29 9925000029 termination joint at DP structure for identifyng the cable. No. 83
The details of feeder i.e. 11 / 22 KV with feeder name
shound be punched on the tag by letter punch of size
mm as per instruction of In-charge Engineer.
Supply & fixing of heat shrink type end terminations
30 9925000030 (outdoor) for 11kV 3C x 240 mm2 size XLPE cable as per No. 4427
DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations
31 9925000031 (outdoor) for 22 kV 3C x 240 mm2 size XLPE cable as per No. 6231
DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor)
32 9925000032 for 11kV 3C x 240 mm2 size XLPE cable as per DGVCL No. 4338
technical specification)
Supply & fixing of heat & shrinkable end terminations
33 9925000033 (indoor) for 22 kV 3C x 240 mm2 size XLPE cable as per No. 6231
DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for
34 9925000034 11kV 3C x 240 mm2 size XLPE cableas per DGVCL No. 6829
technical specification.
Supply & fixing of heat shrinkable straight through joint type
35 9925000035 for 22kV 3C x 240 mm2 size XLPE cable as per DGVCL No. 11590
technical specification
Installation, Testing and commissioning of 11 KV,630 A
SCADA Compatible, RRL type- 3 Way RMU including Two
numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A
SCADA Compatible, RRLL type- 4 Way RMU including Two
numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Installation, Testing and commissioning of 22KV,630 A
SCADA Compatible, RRL type-3 Way, RMU including Two
numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A
SCADA Compatible, RRLL type-4 Way, RMU including Two
numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way (i.e Two
numbers of Isolator & One number of Breaker) Ring Main
40 9925000042 Unit as per DGVCL's technical specification mentioned in No. 28043.22
drawing no: Drg. 11kv-01. All required material will be
supplied by contractor.
Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main
41 9925000043 Unit as per DGVCL's technical specification mentioned in No. 32345.76
drawing no:Drg. 11kv-02.All required material will be
supplied by contractor.
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two
numbers of Isolator & One number of Breaker) Ring Main
42 9925000044 Unit as per DGVCL's technical specification mentioned in No. 32345.76
drawing no: Drg. 22kv-01. All required material will be
supplied by contractor.
Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main
43 9925000045 Unit as per DGVCL's technical specification mentioned in No. 37090.68
drawing no:Drg. 22kv-02.All required material will be
supplied by contractor.
Modifications e.g.Providing and fixing of Terminal protectors
i.e. Re-use able boot (HT Side 11/22KV, LT Side 1.1KV)
including 11/22 KV insulating taps and L.T.(1.1 KV)
insulating taps ,Busbar, Tapping from Bus Bar (11/22 KV
XLPE cable) through P.G. Clamp for H.T. Jumper to D.O.
Fuse to bushings of Transformer Center, providing & Fixing
of jumper and providing & fixing of Heat Shrinkable Anti
Tracking Core Insulating Tubing (Insulation Level 11/22 KV)
in H.T. jumper , Clamping arrangement of cable support
frame on both side of existing Over Head type Distribution
Transformer to utilize in Under Ground cable network as per
drawing & as per instruction of Engineer incharge. All live
parts i.e. PG-Clamp, connections of D.O.fuses, HT
bushings etc . shall be covered with fixinng of 11/22 KV HT
insulating tapes. ( 11/22 KV XLPE cable will be in scope of
DGVCL while all other materials will be in bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE /PILC Cable in per cable per
redaymade trench or in open space mtr
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM 70320
Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter
long RCC half round pipe
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Laying (Including Installation , Testing and Commissioning)
of various size of 11 KV XLPE Insulated alluminium
armoured cable in ground 1200 mm Deep , 300 mm Wide
Trench, Providing sand cushioning below (75 mm thick layer
of sand ) and above (75 mm thick layer of sand ) of the
cable and covering it with RCC Half round hume pipe (150
1 mm inner dia with thickness of 30 mm,1 meter length) Meter 335
before refilling pre-bonding / warning tap should provide
below 700 mm from the ground level and back filling the
same to make ground level as per original. As per
Specification and drawing og UGVCL. ( RCC Half Round
pipe should be provide thorughout on cable wihtout gap,
only cable will be supplied by DGVCL)
Laying (Including Installation , Testing and Commissioning)
of various size of Double Circuit 11 KV XLPE Insulated
alluminium armoured cable in ground 1200 mm Deep ,
mm Wide Trench, Providing sand cushioning below (75 mm
thick layer of sand ) and above (75 mm thick layer of sand )
of the cable and covering it with RCC Half round hume pipe
2 (150 mm inner dia with thickness of 30 mm,1 meter length) Meter 468
before refilling pre-bonding / warning tap should provide
below 700 mm from the ground level and back filling the
same to make ground level as per original. As per
Specification and drawing og UGVCL. ( RCC Half Round
pipe should be provide thorughout on cable wihtout gap,
only cable will be supplied by DGVCL)
Layingt of HDPE Pipe Confirming to IS 4984:1955
(Ammendment No 2) having diameter 160 mm and
minimum thickness 5 mm at a minimum depth of 1200 mm
below the road surface by push thorugh method by drilling
3 the road with HDD machine/manually without breaking the Meter 825
road surface and laying of any size of HT/LT XLPE
insulated alluminium armoured cable through the duct as
per the instruction of EIC and specifications. (Without cost
of HDPE Pipe , Cable will be supplied by DGVCL)
Supply of HDPE Pipe having 160 mm diameter , minimum
thickness 7.3 mm as per IS (ammendment no 2 - IS
4984:1995) of PE- 100 , 6 kg/cm2 , for laying of 11 KV
Proving and Fixing HT push on/heat shrink type End Indoor
termination kit Preferably 3m(m-seal) or Raychem make at
switchgear end boxes, transformer (PAD/Pole mounted) for
3 core 11 kV XLPE Aluminium Conductor Armoured cable
5 as specified with connection of leads including cutting, No. 5549
stripping of cable, insulations, providing compression type
terminal ,crimping of lugs with suitable crimping tool, indoor
For 300 mm2 HT XLPE Cable
Proving and Fixing HT push on/heat shrink type End
Outdoor termination kit Preferably 3m(m-seal) or Raychem
make at switchgear end boxes, transformer (PAD/Pole
mounted) for 3 core 11 kV XLPE Aluminium Conductor
6 Armoured cable as specified with connection of leads No. 6676
including cutting, stripping of cable, insulations, providing
compression type terminal ,crimping of lugs with suitable
crimping tool, outdoor application.
For 300 mm2 HT XLPE Cable
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Proving and Fixing HT push on/heat shrink type Straight
Joint Preferably 3m(m-seal) or Raychem make for 3 core
kV XLPE Aluminium Conductor Armoured cable as
7 specified with connection of leads including cutting, No. 8040
stripping of cable, insulations, providing compression type
terminal ,crimping of lugs with suitable crimping tool.
For 300 mm2 HT XLPE Cable
Erection Schedule B-1
HT TAPPING FROM THE EXISTING POLE INCLUDING
FIXING OF CROSS ARMS, CLAMPS ANTI-CLIMBING
DEVICES, DANGER BOARD, INSULATORS ETC.
1 9926000001 COMPLETE AND PAINTING OF FABRICATED No. 481
MATERIALS AND NUMBERING COMPLETE WITH COST
OF PAINTS AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF PSC POLES OF 8 *200 KG INCLUDING
EXCAVATION OF PIT AND REFILLING OF EARTH,
FIXING OFCROSS ARMS, TOP FITTING CLAMPS ANTI-
CLIMBING DEVICES, INSULATORS ETC. COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON
THE POLES AND NUMBERING WITH COST OF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLES OF 9 TO 11 METERS
INCLUDING EXCAVATION OF PIT AND REFILLING OF
EARTH, FIXING OFCROSS ARMS, TOP FITTING
CLAMPS ANTI-CLIMBING DEVICES, DANGER BOARD,
3 9926000003 INSULATORS ETC. COMPLETE AND PAINTING OF No. 1949
STEEL POLE, FABRICATED MATERIALS USED ON THE
POLEAND NUMBERING WITH COST OF PAINT AS PER
STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLE OF 13 METERS FOR
RAILWAY CROSSING ON BG/MG/NG LINE FOR
0.400/11/22KV OVERHEAD LINES I.E INCLUDING
EXCAVATION OF PIT & REFILLING OF EARTH, FIXING
CROSS ARMS, TOP FITTING CLAMPS,ANTI-CLIMBING
4 9926000004 DEVICES DANGER BOARD, INSULATORS ETC. No. 2325
COMPLETE AND PAINTING OF STEEL POLES,
FABRICATED MATERIALS USED ON THE POLES AND
NUMBERING WITH COSTOF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY
SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF
METERS 200 KG PSC POLES INCLUDING EXCAVATION
OF PITS & REFILLING OF EARTHING, FIXING OF
CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-
CLIMBING DEVICES DANGER BOARDS,INSULATORS
ETC.COMPLETE AND PAINTING OF FABRICATED
MATERIALS USED ON THE POLES AND NUMBERING
WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY
SETS AND EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE OF 9 TO
METERS.STEEL POLE INCLUDING EXCAVATION OF
PITS & REFILLING OFEARTH, FIXING OF CHANNELS,
SUPPORTING ANGLES, CLAMPS,ANTI-CLIMBING
DEVICES DANGER BOARDS, INSULATORS
ETC.COMPLETE & PAINTING OF POLES,FABRICATED
MATERIALSUSED ON THE POLES AND NUMBERING
WITH COST OF PAINTSAS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY
SET AND EARTHING.(WITHOUT AB SWITCH)
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
ERECTION OF DOUBLE POLE STRUCTURE WITH
MOUNTING OF AB SWITCH, HG FUSES OF 8 MTRS
KG PSC POLES INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH,FIXING OF CHANNELS
SUPPORTING ANGLES, CLAMPS, ANTI-CLIMBING
7 9926000007 DEVICES, DANGER BOARDS, INSULATORS,DOFUSES No. 3179
ETC. COMPLETE AND PAINTING OF FABRICATED
MATERIALS USED ON THE POLES AND NUMBERING
WITH COSTOF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDINGOF ERECTION OF
GUY SET AND EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH
MOUNTING OF AB SWITCH,HG FUSES, 9 TO
METERS STEEL POLES INCLUDING EXCAVATION OF
PITS AND REFILLING OF EARTH, FIXING OFCHANNEL,
SUPPORTING ANGLES, CLAMPS, ANTI-CLIMBING
8 9926000008 DEVICES , DANGER BOARDS, INSULATORS, ETC. No. 4171
COMPLETE AND PAINTING OF POLES FABRICATED
MATERIALS USED ON THE POLES AND NUMBERING
WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY
SET AND EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURES WITH
MOUNTING OFAB SWITCH, HG FUSES,
TRANSFORMERS, LIGHTENING ARRESTORS,
DISTRIBUTION BOX. OF 8 METERS 200 KG PSC POLES
INCLUDING EXCAVATION OF PITS AND REFILLING OF
EARTH, CARTING OF TRANSFORMERS FROMSTORES
TO SITE, FIXING OF CHANNELS, SUPPORTING
ANGLES,BRACINGS CROSS ARMS CLAMPS,
ANTICLIMBING DEVICES DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE
AND PAINTING OF FABRICATED MATERIALS USEDON
THE POLES AND NUMBERING WITH COST OF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE WITH
MOUNTING OF AB SWITCH,HG FUSES
TRANSFORMERS, LIGHTENING ARRESTORS,
DISTRIBUTION BOX 9 TO 11 METERS STEEL POLES
INCLUDING EXCAVATION OF PITS & REFILLING OF
EARTH CARTING OF TRANSFORMERS FROM STORE
TO SITE, FIXINGOF CHANNELS SUPPORTING ANGLES,
10 9926000010 BRACING, CROSS ARMS,CLAMPS, ANTICLIMBING No. 10609
DEVICES, DANGER BOARDS,CONDUCTOR AND CABLE
WIRING ETC. COMPLETE AND PAINTING OF POLES
FABRICATED MATERIALS USED ON THE POLES AND
NUMBERING AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTIONS OF GUY SETS AND
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
ERECTION OF GUY SET INCLUDING EXCAVATION OF
PITS & REFILLING OF EARTH AS PER STANDARD
SPECIFICATION WITH STAY CLAMPS, STAY WIRE,
ANCHOR ROD, TURN BUCKLE, EYEBOLT, GUY
INSULATOR, CEMENT CONCRETE BLOCK ETC. BUT
EXCLUDING CONCRETING.
CONCRETING OF POLES, GUYS, ETC. INCLUDING
12 9926000012 COST OF CEMENT SAND METAL (1:2:4) AND WATER CMT 8396
ETC. AS PER STANDARD SPECIFICATION.
ERECTION OF COIL TYPE EARTHING INCLUDING COST
OF COAL,SALT ETC. BUT WITHOUT COST OF GI WIRE
AS PER STANDARD SPECIFICATION(20kg solt+20kg
ERECTION OF GI PIPE/CI PLATE TYPE EARTHING
INCLUDINGCOST OF COAL SALT ETC. BUT WITHOUT
COST OF PIPE/GIPLATE GI WIRE AS PER STANDARD
SPECIFICATION.(20kg solt+20kg coal)
ERECTION OF STREET LIGHT FIXTURE COMPLETE
WITH CLAMPS, BRASS NIPPLE, BRASS HOLDER TECK
15 9926000015 WOOD BUSH,REFLECTORS FUSE, WIRING ETC. AS No. 359
PER STANDARD SPECIFICATION BUT EXCLUDING
COST OF MATERIALS.
STRINGING OF ALL TYPE OF CONDUCTOR (EXCEPT
DOG CONDUCTOR) FOR 11/22KV & LT LINES ONE COND
INCLUDING FIXING OF INSULATORS, BINDING PER KM
STRINGING OF GI WIRE 8 SWG INCLUDING BINDING
PROVIDING SINGLE PHASE SERVICE CONNECTION
WITH PVC 4MM TWIN CORE CABLE FROM TERMINAL
POLE TO METERING POINT INCLUDING FIXING OF
METER WITH METER EARTHING COMPLETE WORK AS
PER STANDARD SPECIFICATION BUT EXCLUDING
COST OF MATERIALS.
PROVIDING THREE PHASE 4 WIRE SERVICE
CONNECTION WITH PVC 4MM2/10MM2 FOUR CORE
CABLE FROM TERMINAL POLE TO METERING POINT
INCLUDING FIXING OF METER WITH METER EARTHING
COMPLETE WORK AS PER STANDARD SPECIFICATION
BUT EXCLUDING COST OF MATERIALS.
ADDITIONAL COST FOR EXCAVATION OF PIT IN HARD
ROCK AREA FOR ERECTION OF POLE/ GUY ETC. AS
PER STANDARD SPECIFICATION OVER & ABOVE
20 9926000020 NORMAL COST COVERED AGAINST EXCAVATION OF No. 359
PIT UNDER NORMAL SOIL FOR ERECTION OF
POLE,GUY, DOUBLE POLE STRUCTURE EARTHING
WITH THE APPROVAL OF SUPDT.ENGINEER.
PROVIDING GUARDING TO HT LINE ON ROAD/ RAIL
PROVIDING GUARDING OF LT LINES ON ROAD/RAIL
23 9926000023 LT LINE TAPPING- SINGLE PHASE No. 51
24 9926000024 LT LINE TAPPING- THREE PHASE No. 93
LAYING OF OVER HEAD LT CABLE FOR ROAD
25 9926000025 CROSSING,HT LINE CROSSING AND TELEPHONE LINE No. 263
CROSSING ETC.(PER SPAN)
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
ERECTION OF SINGLE POLE STRUCTURES WITH , HG
FUSES,TRANSFORMERS, LIGHTENING ARRESTOR,
DISTRIBUTION BOX. ON 8 METERS 200 KGAND PSC
POLE INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH, CARTING OF TRANSFORMERS
FROM STORES TO SITE, FIXING OF CHANNELS,
26 9926000026 SUPPORTING ANGLES,BRACINGS CROSS ARMS No. 4537
CLAMPS, ANTICLIMBING DEVICES DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON
THE POLE AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OFGUY SETS AND EARTHING.
ERECTION OF SINGLE POLE STRUCTURES WITH , HG
FUSES,TRANSFORMERS, LIGHTENINGARRESTOR,
DISTRIBUTION BOX. ON 9 to 11 METERS RSJ POLE
INCLUDING EXCAVATION OF PITS AND REFILLING OF
EARTH, CARTING OF TRANSFORMERS FROM STORES
TO SITE, FIXING OF CHANNELS, SUPPORTING
27 9926000027 ANGLES,BRACINGS CROSS ARMS CLAMPS, No. 5305
ANTICLIMBING DEVICES DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON
THE POLE AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OFGUY SETS AND EARTHING.
ERECTION OF PSC POLES OF 10 *270 KG INCLUDING
EXCAVATION OF PIT AND REFILLING OF EARTH,
FIXING OF CROSS ARMS, TOP FITTING CLAMPS ANTI-
CLIMBING DEVICES, INSULATORS ETC. COMPLETE
28 9926000028 AND PAINTING OF FABRICATED MATERIALS USED ON No. 2666
THE POLES AND NUMBERING WITH COST OF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SET AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF
METERS 270 KG PSC POLES INCLUDING EXCAVATION
OF PITS & REFILLING OF EARTHING, FIXING OF
CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-
CLIMBING DEVICES DANGER BOARDS,INSULATORS
ETC.COMPLETE AND PAINTING OF FABRICATED
MATERIALS USED ON THE POLES AND NUMBERING
WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY
SETS AND EARTHING.(WITHOUT AB SWITCH)
STRINGING OF 100MM2 ACSR/100MM2 AAAC
30 9926000030 CONDUCTOR FOR LT LINES INCLUDING FIXING 4861
OFINSULATORS, BINDING JUMPERING ETC.
STRINGING OF DOG CONDUCTOR FOR 11/22KV HT
31 9926000031 LINES INCLUDING FIXING OF INSULATORS, BINDING 4378
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
ERECTION OF DOUBLE POLE STRUCTURES WITH
MOUNTING OF AB SWITCH, HG FUSES,
TRANSFORMERS, LIGHTENING ARRESTORS,
DISTRIBUTION BOX. OF 10 METERS 270 KGAND PSC
POLES INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH, CARTING OF TRANSFORMERS
FROMSTORES TO SITE, FIXING OF CHANNELS,
SUPPORTING ANGLES,BRACINGS CROSS ARMS
CLAMPS, ANTI-CLIMBING DEVICES,DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON
THE POLES AND NUMBERING WITH COST OF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SETS AND EARTHING.
DISMENTALLING OF 8 MTR PSC POLE WITH
CREDITING OF FABRICATION AT STORE & STACKING
OF POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALLING OF 10 MTR PSC POLE WITH
CREDITING OF FABRICATION AT STORE & STACKING
OF POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR
PSC POLE) (WITH TRANSFORMER) WITH CREDITING
35 9926000035 OF FABRICATION & TRANSFORMER AT STORE & No. 3975
STACKING OF POLE SAFELY ON ROAD SIDE OR
CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR
PSC POLE) (WITHOUT TRANSFORMER) WITH
36 9926000036 CREDITING OF FABRICATION AT STORE & STACKING No. 2701
OF POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
STRINGING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM
INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
DESIGN SUSPENSION / TENSION CLAMP, FIXING OF
CROSS ARM, LT SHACKLE INSULATOR ETC. FOR
FIXING OF MESSENGER WIRE AND TO PROVIDE
SERVICE CONNECTION ON AERIAL BUNCH CABLE BY
INSULATED PIERCEING CONNECTORS THROUGH
SERVICE CONNECTION BOX COMPLETE AS
REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF LT ABC OF 3*50 SQ MM +1*25 SQ
MM+1*35 SQ MM INCLUDING FITTING OF ALL
ACESSARIES I.E. SPECIAL DESIGN SUSPENSION /
TENSION CLAMP, FIXING OF CROSS ARM, LT
38 9926000038 SHACKLE INSULATOR ETC. FOR FIXING OF KM 12330
MESSENGER WIRE AND TO PROVIDE SERVICE
CONNECTION ON AERIAL BUNCH CABLE BY
INSULATED PIERCEING CONNECTORS THROUGH
SERVICE CONNECTION BOX COMPLETE AS
REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM
INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
DESIGN SUSPENSION / TENSION CLAMP, FIXING OF
CROSS ARM, BINDING TO PIN INSULATOR,PREPARING
SHACKLE POINT,JUMPERS ETC. AS REQUIRED &
DIRECTED BY ENGINEER IN CHARGE
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
STRINGING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM
INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
DESIGN SUSPENSION / TENSION CLAMP, FIXING OF
CROSS ARM, BINDING TO PIN INSULATOR,PREPARING
SHACKLE POINT,JUMPERS ETC. AS REQUIRED AND
DIRECTED BY ENGINEER IN CHARGE
STRINGING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+
35 SQ MM INCLUDING FITTING OF ALL ACESSARIES
I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP,
FIXING OF CROSS ARM, LT SHACKLE INSULATOR ETC.
41 9926000041 FOR FIXING OF MESSENGER WIRE AND TO PROVIDE KM 9863
SERVICE CONNECTION ON AERIAL BUNCH CABLE BY
INSULATED PIERCEING CONNECTORS THROUGH
SERVICE CONNECTION BOX COMPLETE AS
REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
DISMENTALING OF RSJ (9/11 METER) POLE AND
CREDITING THE OLD MATERIAL TO STORE
DISMENTALING OF TRANSFORMER CENTER ON
10MTR,270KG PSC POLE(WITHOUT TRANSFORMER)
43 9926000043 WITH CREDITING OF FABRICATION AT STORE AND No. 2828
STACKING OF POLE SAFELY ON ROAD SIDE OR
CREDITING TO DEPARTMENTAL STORE
DISMENTALING OF TRANSFORMER CENTER ON
10MTR,270KG PSC POLE(WITH TRANSFORMER) WITH
44 9926000044 CREDITING OF FABRICATION AT STORE AND No. 5332
STACKING OF POLE SAFELY ON ROAD SIDE OR
CREDITING TO DEPARTMENTAL STORE
DISMENTLING OF 11KV ABC OF 3*95 SQ MM +80 SQ
45 9926000045 MM AND CREDITING FITTING OF ALL ACESSARIES KM 20515
AND FABRICATION TO DEPARTMENTAL STORE
DISMENTLING OF 22 KV ABC OF 3*70 SQ MM +95 SQ
46 9926000046 MM AND CREDITING FITTING OF ALL ACESSARIES KM 25643
AND FABRICATION TO DEPARTMENTAL STORE
DISMENTALING OF LT ABC OF 1*35 SQ MM + 1*25 SQ
MM AND CREDITING FITTING OF ALL ACESSARIES TO
DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 3*50 SQ MM +1*25 SQ
MM+1*35 SQ MM AND CREDITING FITTING OF ALL
ACESSARIES TO DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 2*50 SQ MM +1*25 SQ
MM+ 35 SQ MM AND CREDITING FITTING OF ALL
ACESSARIES TO DEPARTMENTAL STORE.
RESTRINGING OF ALL TYPE OF CONDUCTOR (EXCEPT
DOG CONDUCTOR) FOR 11/22KV & LT LINES ONE COND
INCLUDING FIXING OF INSULATORS, BINDING PER KM
RESTRINGING OF DOG CONDUCTOR FOR 11/22KV HT ONE COND
51 9926000051 LINES INCLUDING , BINDING JUMPERING ETC. 3129
LABOUR CHARGE FOR THE INSTALLATION OF NEW
DTR METER. (METER WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR THE REPLACEMENT OF DTR
53 9926000053 METER AND OLD METER SHOULD BE CREDITED TO No. 531
SDN STORE. (METER WILL BE PROVIDED BY DGVCL)
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
LABOUR CHARGE FOR PROVIDING CT COIL FOR DTR
54 9926000054 METER CONNECTION. (CT COIL WILL BE PROVIDED PER CT 85
LABOUR CHARGE FOR REPLACEMENT OF CT COIL
FOR DTR METER CONNECTION AND OLD CT SHOULD
BE CREDITED TO SDN STORE. (CT COIL WILL BE
PROVIDED BY DGVCL)
LABOUR CHARGE FOR FIXING OF MMB FOR DTR
METER (MMB WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR REPLACEMENT OF DTR METER
BOX. (METER WILL BE PROVIDED BY DGVCL)
PROVIDING / REPLACEMENT OF 1.5 SQ MM 10 CORE
58 9926000058 COPPER CABLE 3.5 METER (CABLE TO BE PROVIDED No. 1840
LABOUR CHARGE FOR PROVIDING/RECONNECTION
59 9926000059 OF TERMINAL CONNECTION WITH PROPER SIZE OF 15
LUGS. (LUGS COST IS BORNE BY AGENCY)
LABOUR CHARGE FOR THE SPOT READING OF DTR
METER WITH DETAIL SURVEY OF DEFECT IF ANY. A
DULY SIGN COPY BY SURVEYOR PERSON OF
AGENCY IN PRO-FORMA REPORT SHOULD BE
SUBMITTED TO SDN OFFICE.(* ONLY IF ALL
PARAMETER OF VOLTAGE, CURRENT & LOAD AS
SHOWN IN PER-FORMA IS FILLED) AS PER THE
INSTRUCTION OF ENGINEER IN-CHARGE.
LABOUR CHARGE FOR THE SPOT READING OF DTR
METER WITH DETAIL SURVEY OF DEFECT IF ANY. A
DULY SIGN COPY BY SURVEYOR PERSON OF
61 9926000061 AGENCY IN PRO-FORMA REPORT SHOULD BE PER DTR 30
SUBMITTED TO SDN OFFICE. (DULY FILL PER-FORMA
IN FAULT CONDITION IN WHICH READING PARAMETER
IS NOT SHOWN IN METER)
INSTALLATION OF DTR METER INCLUDING METER
BOX, PROVIDING & FIXING OF 1.5SQ MM SINGLE
STRAND 10 CORE ARMOURED COPPER CABLE
(3.5METER), TERMINATION IN METER & COIL ETC.
(METER, METER BOX, C.T./P.T. COIL WILL BE
PROVIDED BY DGVCL)
INSTALLATION OF DTR METER INCLUDING METER
BOX, TERMINATION IN METER & COIL ETC. (WITHOUT
10CORE COPPER CABLE) (METER, METER BOX,
C.T./P.T. COIL WILL BE PROVIDED BY DGVCL)
Binding of messanger Conductorat with a distance not more
64 9926000064 than 0.75 mtr with 6 turns minimum on XLPE Cable with No
single strand binding wire (including cost of binding wire)
Supply and Installation of 11/22 kV Distribution
Transformers HT Terminal protector (UV Resistance) with
using 95/120/150 sq.mm long barrel aluminum lug. (1Set =
3 Nos i.e. on R, Y, B)
Supply & Installation of HT EPR Tap on 11/22 kV
Distribution Transformer with replacement of bare conductor
by HT ABC conductor (DO bottom side to transformer) after
removal of semi conductor by HT ABC (6 inch both side).
HT ABC to be supplied by DGVCL. (1Set = 3 Nos i.e. on R,
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Supply, Installation, Testing and Commissioning of
Maintenance Free, Ready Capsule, Pipe-In-Cage (Pic)
67 9926000088 Type, Earth Electrodes for HT Feeder Pole Having 2000 No
mm Electrode Length as per the Tender Specifications and
Drawing. (All Materials Will Be Supplied By Agency)
Supply, Installation, Testing and Commissioning of
Maintenance Free, Ready Capsule, Pipe-In-Cage (Pic)
68 9926000089 Type, Earth Electrodes for HT Feeder Pole Having 3000 No
mm Electrode Length as per the Tender Specifications And
Drawing. (All Materials Will Be Supplied By Agency)
Supply and Installation of 25 X 3 mm GI Strip having hot
dip- galvanized-zinc coating of 80-100 microns without any
joints or welding. Both the end of the GI strip should be
connected with GI nut bolts and required fabrication work for
69 9926000090 giving separate earthing connections to(1) Neutral of the Meter
transformer(2) MS structures of the transformer center
(Approximately 25 meter GI strip per transformer centre- as
per requirement and instruction of Engineer in- charge) (All
Materials will be supplied by Agency)
Supply and Installation of uPVC standard make Pipe of
1.25" diameter for covering GI strip with UV protected Cable
Ties of 550 X 7.6 mm size to bind with pole
face(Approximately 25 meter uPVC pipe for GI strip
covering per transformer centre -as per requirement and
instruction of Engineer in-charge.
Supply & fixing of upto 33 kV Conductor sleeve for Busbar
to Drop out Fuse and Drop
71 9926000093 out fuse to Transformer H.T. including Busbar (12 mm Per TC
sleeve) as per technical
specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar
to Drop out Fuse and Drop
72 9926000100 out fuse to Transformer H.T. without Busbar (12 mm sleeve) Per TC
as per technical
specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar
to Drop out Fuse and Drop
73 9926000094 out fuse to Transformer H.T. including Busbar(15 mm Per TC
sleeve) as per technical
specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar
to Drop out Fuse and Drop
74 9926000101 out fuse to Transformer H.T. without Busbar(15 mm sleeve) Per TC
as per technical
specification. (All Materials will be supplied by Agency)
Supply & fixing of Disc type Red Color FRP(Non-
flammable) material with Weather
resistant, Non-conductive bird guard OD=300 MM, ID=33
MM, Width =1.25 MM, one
side cut from ID to OD. (All Materials will be supplied by
Providing and fixing of LT Terminal protectors i.e. Re-
useable boot (LT Side 1.1 kV) including LT (1.1 kV)
insulating taps. All live part at LT side shall be covered with
fixing of LT insulating taps.
77 Nylon Net around Transformer Center
77.1 9926000097 Nylon Net (12 * 15 ft) Per Net
77.2 9926000098 Nylon Dori Per TC
Labour charge for fitting Nylon Net (All fabricated material
for fitting nylon net shall be provided by DGVCL)
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Erection Schedule B2
1 9924000001 Cutting of Tree branches surounding HT/LT line Per Tree 57
Replacement of old jumpers & providing new double
jumpers with 8" binding & capsuling with PVC pipe etc
3 9924000005 Support pole for Stay PSC/STP/RSJ No. 633
4 9924000006 Pin binding of conductor 11/22kv Pin insulator No. 18
Pin binding of conductor 11/22kv Pin insulator per pole in
costle area with cleaning .
6 9924000008 Pin binding of conductor LT shakel insulator No. 14
7 9924000009 Replacement of one/both disc.insulator at strain pole No. 161
8 9924000010 Replacement of LT shackle insulator at cut point No. 31
9 9924000011 Refixing of V cross Arm No. 61
10 9924000012 Replacement of V cross Arm No. 210
11 9924000013 Refixing of Top fitting in proper position No. 41
12 9924000014 Replacement of Top fitting No. 51
13 9924000015 Replacement of LT cross Arm No. 105
Providing DO fuse on DP with carting & jumpuring(ONE DO
Numburing of pole with paint by preparing back ground of
15 9924000017 one colour and have lettering(height 3" * width 0.5") using No. 46
16 9924000018 Fixing of MMB(1PH.) at consumer end No. 86
17 9924000019 Fixing of MMB(3PH.) at consumer end No. 128
18 9924000020 Replacement of (1ph.) meter for Urban area No. 51
19 9924000021 Replacement of (1ph.) meter for Rural area No. 74
painting consumer no. on MMB (Urban) (with letter size
height 40mm* width 8mm)
painting consumer no. on MMB (Rural) (with letter size
height 40mm* width 8mm)
22 9924000024 Replacement of deteriorated Single phase Service line No. 93
Fixing of new dist. Box with complete wiring including
clamps,nut bolts etc.
Reparing of guarding involving reshaping of bearer wire
cross lacing binding etc.
Painting of steel fabricated material of RSJ DO DP structure
Painting of steel fabricated material of RSJ pole mounted
transformer double pole structure with paint
Painting of steel fabricated material of RSJ single pole with
painting of steel fabricated material of PSC Single pole (HT
line) with paint
painting of steel fabricated material of PSC DO DP double
pole with paint
painting of steel fabricated material of PSC double pole at
pole mounted transformer with paint
31 9924000033 Providing line seperater single phase No. 11
32 9924000034 Providing line seperater three phase No. 31
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Replacement / Providing of stay insulator along with
adjustment of tension in stay wire
Replacement of deteriorated /providing LT dist. Box with
new up to 100KVA capacity & crediting it to store.
Replacement of deteriorated /providing LT dist. Box with
new above 100KVA capacity & crediting it to store.
36 9924000038 Adjustment of tension in stay wire No. 158
37 9924000039 Refitting of LA No. 31
Converting pin point to Shackle point including dismentaling
& restringing etc.
replacement of 11KV Pin insulator with providing new
double pin binding
replacement of 22KV Pin insulator by new 11kv pin
insulator with spares & providing new double pin binding
Providing 11kv double disc insulators with binding &
Replacement of existing 11kv conductor (all size) with new
double pin binding
43 9924000046 Plumbing of PSC Pole with straightening at pin point No. 287
44 9924000047 Plumbing of PSC Pole with straightening at tension point No. 373
Plumbing of tilted DP structure (PSC/RSJ/STP) with refilling
of stone Murrum etc.
Providing new 11kv AB /GO switch with fabrication and
insulated colour code jumper, binding, lugs etc
Replacement of old 11kv AB /GO switch with providing new
insulated jumper, binding, lugs etc
Providing cage type loop guard in verticle LT line with using
PVC reel insulators etc
Labour charges for replacement /providing of MMB &
service with all accessories for three phase connection
Labour charges for replacement /providing of MMB &
service with all accessories for single phase connection
Dismentalling of existing Dist.X'mer center(RSJ /STP
51 9924000055 POLE) 25/63/100/200 KVA with all fabrication & creditig the No. 5528
old material to store
52 9924000056 Disconnection from LT pole 1 phase No. 46
53 9924000057 Reconnection from LT pole 1 phase No. 46
( payment after receipt of R/C charges)
54 9924000058 Disconnection from LT pole 3 phase No. 66
Reconnection from LT pole 3 phase
( payment after receipt of R/C charges)
Dismentaling & removing of service line from pole &
crediting to S/dn (1 ph.)
Dismentaling & removing of service line from pole &
crediting to S/dn (3 ph.)
Reconnection of service line complete with PVC cable (1
Reconnection of service line complete with PVC cable (3
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
Providing spiral type earthing by G.I. NO 8(weight 2kg -5mtr
in length) with salt and coal 10kg each, including pvc rigid
60 9924000064 pipe 20mm dia( 1.5mtr length) to pass exposed part of G.I. No. 816
wire at consumer end with all materials, earth resistance
should be less than 2 ohms
Providing and fixing of signle core 1.5 sq mm single strand
copper insulated cable with cable nail clip for spiral type
earthing at consumer end. The end of G.I. no 8 is to be
connected by connector with copper cable of which other
61 9924000070 per meter 30
end shall be connected to the earth terminal of meter box.
This item shall be used in location where there is more
distance between earth terminal and earthing terminal of
meter. (All materials supplied by contractor)
Stringing of LT ABC of 1*35 SQ MM + 1*25 SQ MM
including fitting of all acessaries i.e. special design
suspension / tension clamp, fixing of cross arm, LT shackle
insulator etc. for fixing of messenger wire and inclusive of
62 9924000065 dismantling charge of existing bare conductor and crediting KM 8922
in to store & dismentaling of service line from LT bare
conductor and to provide service connection on Aerial
Bunch Cable by insulated pierceing connectors through
service connection box complete as required & directed by
Engineer in Charge.
Stringing of LT ABC of 3*50 SQ MM +1*25 SQ MM+1*35
SQ MM including fitting of all acessaries i.e. special design
suspension / tension clamp, fixing of cross arm, LT shackle
insulator etc. for fixing of messenger wire and inclusive of
63 9924000066 dismantling charge of existing bare conductor and crediting KM 22303
in to store & dismentaling of service line from LT bare
conductor and to provide service connection on Aerial
Bunch Cable by insulated pierceing connectors through
service connection box complete as required & directed by
Engineer in Charge.
Stringing of 11KV ABC of 3*95 SQ MM +80 SQ MM
including fitting of all acessaries i.e. special design
suspension / tension clamp, fixing of cross arm, binding to
64 9924000067 pin insulator,preparing shackle point,jumpers etc. and KM 44608
inclusive of dismantling charge of existing bare conductor
and crediting in to store complete as required & directed by
Engineer in Charge
Stringing of 22 KV ABC OF 3*70 SQ MM +95 SQ MM
including fitting of all acessaries i.e. special design
suspension / tension clamp, fixing of cross arm, binding to
65 9924000068 pin insulator,preparing shackle point,jumpers etc. and KM 55019
inclusive of dismantling charge of existing bare conductor
and crediting in to store complete as required & directed by
Engineer in Charge
Stringing of LT ABC of 2*50 SQ MM +1*25 SQ MM+ 35 SQ
MM including fitting of all acessaries i.e. special design
suspension / tension clamp, fixing of cross arm, LT shackle
insulator etc. for fixing of messenger wire and inclusive of
dismantling charge of existing bare conductor and crediting
in to store & dismentaling of service line from LT bare
conductor and to provide service connection on Aerial
Bunch Cable by insulated pierceing connectors through
service connection box complete as required & directed by
Engineer in Charge.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
UG Work Up to 200 Mtr only in All Scheme to be
given in above work order for timely completion of
1.AS 300 Mm2 Cable Cost Data not Availble with DGVCL
and We have Proposed 300 mm2 Cable at Various
Location to Create Robust netwrok with RMU and SS
End Hence Cost Data of UGVCL Considered as Ref and
Rate Taken Accordingly as per Telephonic Instruction
GIven by Competent Authority from Circle Office
Total of Schedule B1 + B2 + B3 + B4 is Rs. TOTAL
1.DGVCL will provide key material like M.S.
materials,ABC/Bare conductors,PSC/RSJ
Poles,Insulators,Fabricated materials etc. to the contractor.
2.All fabricated items shall be fabricated as per DGVCL
approved drawing and by welding rods confirming to the
relevent ISI specification and as directed by Engineer in
3.Necessary electricity connection for fabrication items shall
be provided by DGVCL on payment of required charge for
connection & electricity bill of the same shall be paid by the
4.All the rates are inclusive of PF & Exclusive of GST
applicable time to time.
5.All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying
the paints on to the RSJ poles & steel fabricated materials
of RSJ/PSC poles is must required.
(b) Two coats of approved ISI mark red oxide (primer) is to
be properly painted for the RSJ poles & steel fabricated
materials of RSJ/PSC poles.
(c) Two coats of approved ISI mark silver paint (i.e. triple
mangoes or equivalent quality silver paint) is to be properly
painted on to the RSJ poles & steel fabricated materials of
1. Excavation, Drilling and Cable laying should be done
with all road safety measures such as hard barricading,
displaying “DANGER” sign and “DGVCL - Work in
Progress” on it with light reflective strips or paint. Proof of all
barricading and safety equipment need to submit.
2. Cable laying should be done through roller (not
through tractor or pulling by any other vehicles).
3. Ownership document regarding roller/pulling machine
and HDD machine need to submit or agreement with
agency of above narrated machine regarding work for this
tender required to submit.
4. Trail pit excavation and De-excavation should be done
simultaneously so that any chance of road accident can be
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Letter No: DGVCLSDUR/0262/06/2026 Approved Date: 12-06-2026
5. Three no of Polymer cleat should be provided on rising
cable for proper fitting and if it is not feasible to provide third
polymer cleat at the bottom than two nos of polymer cleat
Executive Engineer (Tech)
Technical on upper side and strap strip on bottom end required to
install for proper fitting of rising cable. DGVCL
Sachin Division
6. 100% videography of cable laying along with landmark
location of cable laying required to be done and submit Pen
drive to the concern engineer for their verification.
7. Aluminum strip required to use to connect end of cable
at cable rising location as per instruction of Engineer in
charge. Also no joints will be allowed in GI strip for cable
Earthing and strip will be connected through GI bolts only.
8. Issues regarding ROW on field should be resolved by
contractor itself.
9. Testing & measuring equipment: - 5 KV Digital
insulation testers, Digital Earth clamp meter for
measurement of Earthing and leakage current, Digital
Rodometer with NABL accredited agency valid test
10.Earthing value & Insulation Resistance (IR) value of all
location along with Geo tagged (longitude & latitude) wise
testing and measured value photograph need to submit with
11.Depth chart should be provided at every 100 meter with
mentioning landmark.
12. Partial Discharge test to be carried out on sample part of
cable before charging as decided by in charge engineer.
13. Qualified cable jointer with Minimum five years of
experience required with necessary certification regarding
qualification and specific experience.
14. Performance Bank Guaranty required to submit 5% of
tender value for two years against cable joint failure.
Moreover, cable joint failure or end termination failure will
have to repair within 24 Hrs for 2 years of guaranty period.
15. Fixing of mechanical protection HDPE pipe at rising
should be properly buried as per specification.
16. Fixing of Route marker strictly as per specification.
17. Minimum annual Turnover should be at least tender
estimated value and in addition to CVC guideline narrated in
tender for UG cable laying work.
18. Marking of feeder name, direction and location on cable
is compulsory during final scrutiny to declare work
19. End termination and straight joint kit should be of
premium quality as specified in Annexure-2. Technical
specifications for the same to be submitted along with bid.
20. Cable straight joint should be done with mid span joint
instead of long barrel Lug.
21. Agreement with vendor of cable joint kit and End
termination kit to supply for this tender for concern bidder
should be submit at the time of bidding.
File No: DGVCLSDUR/MSC/e-file/4523/2026/0739/Billing
Approved By: Executive Engineer,Technical,DGVCLDSRTU
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NOTICE INVITING TENDER.pdf
Schedule B1 B2 B3 B4.pdf
Technical Specifications.pdf
Tender 688.pdf
Download all tender documents and submit your bid