Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 LAccepted-AOC | ₹8.5 L Quoted ₹8.8 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹9.7 L+₹95,986 (11.0%)Rejected-Finance | ₹9.7 L+₹95,986 (11.0%) | L2 | Rejected-Finance Being L2 |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
23 Jan 2021, 6:00 pmClosed
GE I R AND D Chandigarh
DIHAR Base Lab, Near 3 BRD (AF), Industrial Area Phase-II, Ramdarbar, Chandigarh
REPAIR AND PERIODICAL MAINT OF FIRE ALARM SYSTEM/ FIRE FIGHTING SYSTEM AND CONNECTED WORKS IN OTM AND MD ACCN AT CHANDIGARH TBRL RANGE RAMGARH
2020_MES_403399_1
GE I R AND D/CHD-71/2020-21
Open Tender
Civil Works
Item Rate
330 days
Ramgarh
All as per tender documents
8 documents required · 8 mandatory
₹500
GE I R AND D Chandigarh
₹24,000
Yes
12 Feb 2021
26 Dec 2020
25 Jan 2021
26 Dec 2020
23 Jan 2021
9 Jan 2021
Amount
SECTION - I (CHANDIGARH AREA ) Testing / Servicing / Comprehensive maintenance and repair including renewal/ replacement of defective parts of all existing fire protection system complete of following fire protection system installed at various location once in a month for 100% serviceability of the complete including checking of fire detectors, cleaning of detector by removing dust or dirt, cleaning of heavy greasy deposit if any, checking the connection of batteries, specific gravity of electrolyte, wiring connection of detectors/hooter/response indicator and the alarm function of control panel and indicating eqpt be checked by the operation of trigger device of the fire alarm system installed in the following buildings and replacing the defective / unserviceable parts complete all as specified and directed by Engineer-in-Charge. NOTE:- (i) Cost of new components/parts shall be paid for separately under relevant item of Schedule 'A' Sec l item 02 to 11. (ii) Contractor's rep will visit minimum once in a month to every panel and take serviceability certificate duly signed by the users. Additional visit as and when required will not be paid as extra. Fire Alarm Panels installed in HQ SASE Him Parisar Bldg Sec 37A Chandigarh.
Fire Alarm Panels installed in HQ TBRL Bldg Sec 30 Chandigarh
Supply Only smoke detector (Ceiling mounted) with base, Ionization type dual chamber as per approved specification. The smoke detector should be matchable with existing system in the building complete all as specified and directed by Engineer-in-Charge.
Supply, Only heat detector with base Ionization type dual chamber as per approved specification. The heat detector should be matchable with existing system in the building complete all as specified and directed by Engineer-in-Charge.
Suppply only response indicator LED type complete all as specified and directed by Engineer-in-Charge.
Supply only wall mounted fire alarm manual call point complete all as specified and directed by Engineer-in-Charge.
Supply only fire alarm hooter for conventional fire alarm system operated on 100V AC/ 24V DC with suitable audible range 80DB complete all as specified and directed by Engineer-in-Charge.
Supply only lead acid battery 12 volts 7 AH suitable for conventional fire alarm panel complete all as specified and directed by Engineer-in-Charge.
Supply only fire protection system consisting of micro controller based main fire control panel cum PA system of 2 to 48 zone expandable type 230 volt AC standby supply 24/36V DC and output 24V DC complete all as specified and directed by Engineer-in-Charge.
Supply only fire alarm panel of 04 zones with LCD display facility and advanced micro controller based circuit complete all as specified and directed by Engineer-in-Charge.
Supply only FRLS flexible copper cable 1.5 sqmm, 2 core , 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply only FRLS flexible copper cable 2.5 sqmm, 2 core , 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of canvas hose pipe 63mm dia with male female coupling 15 mtr long reinforced rubber lined hose pipe conforming to IS 636-1962 Part-A with gun metal male & female coupling complete all as specied and directed incl dismantling of old one.
Supply and fixing for swining Hose reel Hydraulic Rubber braided hose of 36mtr long and dia 20mm with ABS Nozzle PVC, wall bracket with U Shaped CI reel carier finished in Red and black enamelled paint incl taking dismantling of old one complete all as specified and directed.
All as per item No 13.00 herein before but reel drum 30 mtr long.
Supply and fixing for single headed landing valve brass ISI marked with 80mm dia flanged inlet & 63mm dia female out let with cap chain spring release type lug and accessories as per IS ; 5290-1983 complete including dismantling of old one complete all as specified and directed.
Supply and replacement of gun metal sprinkler 20mm dia complete all as diected and specified.
Supply and fixing for cast iron double flanged type sluice valve 80 mm dia bore class PN 1.6 , ISI marked complete with nuts , bolts and washers and rubber sheet packing incl dismantling of old one complete all as specified and directd.
Material and labour for painting to MS ERW pipe lines/ GI pipe line, fire stands,fire buckets,hydrants, hose box, hose reel etc with two coats of synthetic enamel paint of red colour after preparation of old surfaces complete all as specified and directed by Engr-in-Charge.
Supply and fixing for galvanised steel tubing heavy grade to walls and laying on floor etc all as specified and directed by Engr-in-charge for the following Make- TATA/JINDAL /Prakash (a) 100 mm dia
All as per serial item No 19.00 above but 25 mm dia
Supply and fix of gun metal gate valves (ISI marked) 50 mm dia heavy duty suitable for fire fighting system with iron wheel head screwed both end for iron pipe including taking down old existing gate valve complete all as specified.
All as per serial item No 20.00 here in before but of size 25 mm
Taking down old defective non return valve and supply and fix non return valve 100 mm dia heavy duty suitable for fire fighting system with by pass arrangement working pressure 10 kg per sq cm confirming to IS- 5312 including jointing by means of rubber gasket 3 mm thick ,MS nut bolt,washers etc including testing.
Taking down old unserviceable sluice valve, supply and fix sluice valve 100 mm dia heavy duty suitable for fire fighting system with flanged ends as per IS-784 PN-1.6 including brass spindle and iron wheel all as per specified class II , ISI marked with nut bolts and jointing material i.e. rubber gasket and testing complete.
Supply and fix for pressure gauges 100 mm dia pressure 0-20 Kg/sqcm type suitable for existing suction and discharge water supply pipe line including suitable fixing arrangment all as directed.
Taking down the defective Electric induction motor Cap 5HP of any make 415 volt 3 phase by dismantling the electrical connections, removing the motor from bed by decoupling with pump transporting to workshop, dismantling it completely, removing the burnt out winding, rewinding the same with super enameled copper wire of same gauge and with necessary insulating material, varnishing, backing and re assembling the motor completly and transporting back to site and alignment with the pump with all connections as directed by Engr-in-charge for following capacity. Note : (i) Burnt out removed winding wire shall be property of contractor through schedule of credit.
Taking down fire extinguisher cylinder from the fire stand/wall and refilling of Gas cylinder with multi purpose dry powder suitable for class ABC, cylinder capacity 6 Kg including hydraulic pressure testing of cylinder.
Taking down fire extinguisher cylinder from the fire stand/wall and refilling of Gas cylinder with multi purpose dry powder suitable for class ABC, cylinder capacity 9 Kg including hydraulic pressure testing of cylinder.
Supply and fixing for portable fire extinguisher cylinder filled with mono ammonium phosphate dry powder MAP90 suitable for all types of Fire class A,B, C and bulk range discharge two metre minimum and Capacity 06 Kg ISI marked complete all as specified and directed.
Supply and fixing for portable fire extinguisher cylinder filled with mono ammonium phosphate dry powder MAP90 suitable for all types of Fire class A,B, C and bulk range discharge two metre minimum and Capacity 09 Kg ISI marked complete all as specified and directed.
Supply and replacement of fire bucket made of 24 gauge steel sheet, Capacity 9 Ltr.
Supply and fixing foot valve size 80 mm dia with gasket including nut, bolt & washer Complete.
Cleaning of under ground water sump of capacity 100000 Ltr after emptying & removal of silt / Rubbish out side the premises.
Supply and fixing MCCB, 4-pole, rating 100 Amps, breaking capacity 25 KA, 415 volts, complete all as specified and directed.
Supply and fixing MCCB, 4-pole, rating 63 Amps, breaking capacity 25 KA, 415 volts, complete all as specified and directed.
Supply and Fixing in replacement 2500 Ltr capacity rotational moulded polythlene water storage Tanks double layer (Cyclindrical vertical and closed top) ISI maked placed on plateform on roof all as specified in SSR Part - 1 complete including wash out pipe of 50mm dia GI Medium grade pipe 50cm long complete all as directed and specified by Engr-in-Charge.
SECTION - II (RAMGARH AREA ) Testing / Servicing / Comprehensive maintenance and repair including renewal/ replacement of defective parts of all existing fire protection system complete of following fire protection system installed at various location in TBRL Range Ramgarh once in a month for 100% serviceability of the complete including checking of fire detectors, cleaning of detector by removing dust or dirt, cleaning of heavy greasy deposit if any, checking the connection of batteries, specific gravity of electrolyte, wiring connection of detectors/hooter/response indicator and the alarm function of control panel and indicating eqpt be checked by the operation of trigger device of the fire alarm system installed in the following buildings at TBRL Range Ramgarh and replacing the defective / unserviceable parts complete all as specified and directed by Engineer-in-Charge. NOTE:- (i) Cost of new components/parts shall be paid for separately under relevant item of Schedule 'A' Sec ll item 48 to 58. (ii) Contractor's rep will visit minimum once in a month to every panel and take serviceability certificate duly signed by the users. Additional visit as and when required will not be paid as extra. Fire Alarm Panel of 06 Zone in Library Section Dec Bldg.
Fire Alarm panels of 04 zones in Directorae Bldg Zone-1
Fire Alarm panels of 04 zones in Telephone Exchange Bldg Zone-I
Fire Alarm panel of 06 zones in J-2 Bldg Zone-I
Fire Alarm panel of 06 zones in Auditorium Bldg Zone-I
Fire Alarm panel of 04 zones in VAJRA Bldg Zone-I
Fire Alarm panel of 04 zones in B-15 Bldg Zone - III
Fire Alarm panel of 04 zones in Data Analysis Centre Zone - III
Fire Alarm panel of 02 zones in Contro room Zone – VI
Fire Alarm panel of 04 zones in Block House Zone – VII
Fire Alarm panel of 04 zones in HMX Plant Bldg Zone-II
Fire Alarm panel of 02 zones in PBX Bldg Zone-II
Fire Alarm panel of 06 zones in Octal plant Bldg Zone-II
Supply only fire alarm panel of 06 zones with LCD display facility and advanced micro controller based circuit complete all as specified and directed by Engineer-in-Charge.
Supply only fire alarm panel of 04 zones with LCD display facility and advanced micro controller based circuit complete all as specified and directed by Engineer-in-Charge.
Supply only fire alarm panel of 02 zones with LCD display facility and advanced micro controller based circuit complete all as specified and directed by Engineer-in-Charge.
Supply only FRLS flexible copper cable 1.5 sqmm, 2 core , 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply only FRLS flexible copper cable 2.5 sqmm, 2 core , 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply only smoke detector (Ceiling mounted) with base, Ionization type dual chamber as per approved specification. The smoke detector should be matchable with existing system in the building complete all as specified and directed by Engineer-in-Charge.
Supply only heat detector with base Ionization type dual chamber as per approved specification. The heat detector should be matchable with existing system in the building complete all as specified and directed by Engineer-in-Charge.
Suppply only response indicator LED type complete all as specified and directed by Engineer-in-Charge.
Supply only wall mounted fire alarm manual call point complete all as specified and directed by Engineer-in-Charge.
Supply only fire alarm hooter for conventional fire alarm system operated on 100V AC/ 24V DC with suitable audible range 80DB complete all as specified and directed by Engineer-in-Charge.
Supply only lead acid battery 12 volts 7 AH suitable for conventional fire alarm panel complete all as specified and directed by Engineer-in-Charge.
Taking down fire extinguisher cylinder from the fire stand/wall and refilling of Gas cylinder with multi purpose dry powder suitable for class ABC, cylinder capacity 2 Kg including hydraulic pressure testing of cylinder.
Taking down fire extinguisher cylinder from the fire stand/wall and refilling of Gas cylinder with multi purpose dry powder suitable for class ABC, cylinder capacity 6 Kg including hydraulic pressure testing of cylinder.
Taking down fire extinguisher cylinder from the fire stand/wall and refilling of Gas cylinder with multi purpose dry powder suitable for class ABC, cylinder capacity 9 Kg including hydraulic pressure testing of cylinder.
Taking down carefully old unserviceable sub main wiring complete all as specified and directed by Engineer-in-charge.
Material and Labour for sub main wiring with two runs of single core, PVC insulated, unsheathed ,multi standard copper conductor cable of size 1.5 Sqmm, 1100 volts grade and one run of 1.5 Sqmm PVC insulated earth continuity copper conductor cable drawn through and inculding suitable size of PVC concealed conduit with all necesary accessories such as bends, tees, junctions boxes, elbows etc complete with all in coming and out going cable connections complete all as specified and directed. (Note : Two runs of 1.5 Sqmm cable, one run of 1.5 Sqmm continuity earth wire and one run of PVC conduit with all necessary accessories will be measured as unit length).
Supply and fixing for MCCB, 4-pole, rating 100 Amps, breaking capacity 25 KA, 415 volts, complete all as specified and directed.
Supply and fixing for MCCB, 4-pole, rating 63 Amps, breaking capacity 25 KA, 415 volts, complete all as specified and directed.
Supply and fixing for portable fire extinguisher cylinder filled with mono ammonium phosphate dry powder MAP90 suitable for all types of Fire class A,B, C and bulk range discharge two metre minimum and Capacity 02 Kg ISI marked complete all as specified and directed.
Supply and fixing portable fire extinguisher cylinder filled with mono ammonium phosphate dry powder MAP90 suitable for all types of Fire class A,B, C and bulk range discharge two metre minimum and Capacity 06 Kg ISI marked complete all as specified and directed.
Supply and fixing for portable fire extinguisher cylinder filled with mono ammonium phosphate dry powder MAP90 suitable for all types of Fire class A,B, C and bulk range discharge two metre minimum and Capacity 09 Kg ISI marked complete all as specified and directed.
shree balaji builders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .