Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-AOC | ₹3.5 L | L1 | Accepted-AOC L1 |
| 2 | L2₹3.7 LRejected-AOC | ₹3.7 L | L2 | Rejected-AOC L2 |
Tender Value
₹4.2 L
EMD Value
₹10,588
Closing Date
18 Feb 2026, 6:00 pmClosed
Assistant Executive Engineer
O/o The Assistant Executive Engineer PWD Electrical Sub Division Chembukavu,Thrissur-20
GENERAL-Electrification of First Floor and Second Floor of Govt. N. B. High School Kodakara , Thrissur.-Electrification of Govt. N. B. High School Kodakara , Thrissur-General Electrical Work
2026_PWD_835321_1
ESDT(ET)133/AEE/25-26
Open Tender
Electrical Works
90 days
Thrissur
Please refer Tender documents.
10 documents required · 10 mandatory
₹935
₹10,588
21 Mar 2026
10 Feb 2026
21 Feb 2026
10 Feb 2026
18 Feb 2026
10 Feb 2026
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD291408/2025-2026:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable through existing medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD291421/2025-2026:Supply, conveyance, installation, testing and commissioning the light fittings made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
OD291422/2025-2026:Supply, conveyance installation testing and commissioning the light fittings made of CRCA sheet with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD291554/2025-2026:Supply of 450 mm sweep, 1400 rpm Heavy Duty Exhaust fan working on 230 V A/C.
OD291555/2025-2026:Supply, Conveyance,Testing and Commissioning of 225 mm sweep Light Duty Exhaust fan in plastic frame working on 230 V A/C in the existing opening using suitable size anchor bolt / Screws etc and giving connection as required.(Crompton or its equivalent).
90.4.9:Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.
OD291489/2025-2026:Supplying PVC batten/ angle holder .
OD291512/2025-2026:Supply of 9 W LED bulb B22 base type.wipro/philips/Hallonix/crompton/approved make
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
OD291414/2025-2026:Supply, installation testing and commissioning of single phase 1.5 HP open well horizontal type submersible motor pump set at 21-42 m head range 1.5 HP 25D PLANO150 HOWS 1PH 3M CRI/equivalent make (ISI marked) delivery size 40 mm having discharge 145/20 lpm using leak proof materials as required and laying in the existing sump including fixing delivery pipe connected one by one to the motor up to the bottom of the well using leak proof materials as required with necessary supports on both sides of the motor including giving connection as per the direction at site. [ CRI/Aquatex/KSB /Kirloskar/Texmo ]
OD291393/2025-2026:Supply and providing steel connector with clamp suitable for 40 mm PVC pipe for connecting with motor pump set etc as required
OD291401/2025-2026:Supply and providing of 32/40 mm/nearest size3 duro flex/cano flex PVC flexible pipe as delivery pipe from well to ground level etc as required.
OD291405/2025-2026:Supply and providing 32/40 mm dia G.M Non return valve (ISI)
OD291409/2025-2026:Supply and providing 15mm/nearest size nylon rope submarine blue make for hanging the motor pump set
OD291399/2025-2026:Supply and providing 32/ 40 mm dia MS Flange set
OD291407/2025-2026:SITC of Motor starters of the following ratings Submersible pump controllers with ammeter,single phase up to 1.5 HP submersible motor pumps (DOL) giving necessary connections etc as required(L&T MRG2 DOL Controller)
90.6.6.3:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1405446.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.05 MB
Tendernotice_2.pdf
PDF • 0.02 MB
Tendernotice_3.pdf
PDF • 0.16 MB
Tendernotice_4.pdf
PDF • 0.05 MB
Tendernotice_5.pdf
PDF • 0.06 MB
Tendernotice_6.pdf
PDF • 0.27 MB
viewnit.pdf
Tender Documents • 0.03 MB
viewsbd.pdf
Tender Documents • 1.73 MB
BOQ_1405446.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid