EXECUTIVE ENGINEER(E)
BSNL ELECTRICAL DIVISION, 2ND FLOOR NEW TE BLDG, VIDYANAGAR, HUBLI
Providing of EMI for NFS Project Package 1B at IAF STATION1 BIDAR SH AFD SYSTEM.
2020_BSNL_53874_1
ENIT20/EEE/ED/HBL/2020-21
Open Tender
Electrical Works
Item Rate
60 days
IAF STATION1 BIDAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
BSNL
₹8,611
27 Aug 2020
27 Jul 2020
26 Aug 2020
27 Jul 2020
24 Aug 2020
27 Jul 2020
90 days
Amount
AFS (ADDRESSABLE FIRE ALARM SYSTEM)
Supplying, installation, testing & commissioning of Microprocessor based 2 wire fault tolerant, Networkable type fire alarm/detection 2 loop control panel (each loop to suit minimum 99 nos. of fire detectors and 99 nos. of modules/devices). The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF the respective control module whenever any alarm is triggered. The panel shall have rectifier, Loop cards, 80 character LCD unit to indicate Fire/Fault Signal with address and analog output, with provision for adding external/inbuilt printer to log all fire or fault events complete in all respects. The Panel shall be sheet steel powder coated, sealed to IP: 30. The panel shall have LED Indicators for indication of various signal. The panel should have TCP/IP connectivity and should have the facilty to view remote access with similar view of FACP PMI (Honeywell Morley/Siemens/Notifier/Cooper make). The panel shall have a built in power supply and battery charger along with maintenance free 7 AH, 2x12 volt SMF Lead acid batteries capable of running for a minimum of 4 ½ hours with battery charger and conforming to BS:5839 standards and duly approved by EN54/LPCB/VDS/UL as per specifications complete in all respect etc. complete as required.
Supplying, installation, testing & commissioning of Intelligent Analog Addressable Multi sensor Type Smoke Detector complete with single/ twin LED, Hard Addressable having rotary decade Address switches from 01-99, with mounting base conforming to BS:5839 standards and duly approved by EN54/UL/FM/LPCB/VDS etc. complete as required. (Installed on real ceiling/on false ceiling/on false floor)
Addressable Heat Detector: Supply Installation Testing and Comissioning of EN54/UL/FM/LPCB/VDS Intelligent Analogue addressable ROR Heat detector with junction box etc. as required.
Response Indicator: SITC of Response indicator having twin LEDs for mounting on false ceiling / wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors etc. as required.
Supplying installation testing & commissioning of Intelligent Analog Addressable Type Manual Call Point having Surface or flush mounting Option fully compliant to EN54 having Rotary Decade Switches for Addressing from 01-99 with Back Box for Mounting as required conforming to BS5839 Standards and Duly Approved by EN54/LPCB/VDS/UL as required.
Supplying, installation, testing & commissioning of Addressable type Loop Powered Hooter complete with mounting Base conforming to BS: 5839 Standards and duly approved by EN54/LPCB/VDS/UL etc. complete as required.
Supplying, installation, testing & commissioning of Addressable type Fault Isolator for isolating shorted, de-linked and loose circuits between two successive fault isolators with automatic resetting arrangement to be interconnecting to loop cable and conforming to BS:5839 standards and duly approved by EN54/LPCB/ VDS/ UL/BSA etc. complete as required.
Supply and installation of addressable control modules for providing tripping contacts for the Air Conditioning system/AHUs. (This shall be wired in the loop and located near the AHUs) etc. as required.
Medley Fire Systems
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .