Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-AOC 76 1 GURU SADAY DUTTA SARANI NORTH BHARAT NAGAR SILIGUR | L1 | Accepted-AOC lowest | |
| 2 | L2₹3.5 L+₹3,565.87 (1.03%)Rejected-Finance 53 BANKIM CHANDRA ROAD HAKIMPARA SILIGURI 734001 | SILIGURI | DARJEELING | WEST BENGAL | 734001 | L2 | Rejected-Finance 2nd lowest | |
| 3 | L3₹3.5 L+₹6,892.18 (1.98%)Rejected-Finance NANAK TOWER 3RD FLOOR SEVOKE ROAD SILIGURI | L3 | Rejected-Finance 3rd lowest |
Tender Value
Refer Docs
EMD Value
₹6,500
Closing Date
5 Mar 2025, 11:00 amClosed
The Executive Engineer, PMD,PHE.Dte
Office of the Executive Engineer Purulia Mechanical Division,PHE.Dte Ranchi Road,Purulia.
Supply delivery and fitting fixing of cable, main switch, earthing arrangement etc. and other allied work at Palashkhola water supply scheme under Purulia Mechanical Division, PHE, Dte.
2025_PHED_808943_1
16 /EE/PMD/PHED OF 2024-2025
Open Tender
MECHANICAL
Item Rate
30 days
Purulia
Please refer Tender documents.
5 documents required · 5 mandatory
₹6,500
Yes
12 Jun 2025
31 Jan 2025
7 Mar 2025
31 Jan 2025
5 Mar 2025
31 Jan 2025
Amount
S/D and fixing Switch disconnector Fuse unit 630 amps bolted type with SS eclosure with 3 fuse at site (Make-PHE Approve make)
S/D at site of 1.1 KV grade 240 sq mm XLPE insulated AL armoured 3.5 core cable as per IS 7098 PART-1 (Make-PHE Approve make)
Laying of cable above 3½ core 90 sqmm and upto 3½ core 240 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting
Excavation of earth for installition of earth electrode and filling and ramming A) for morum soil
Earthing with 50mm dia G.I pipe 3.64mm thick 3.04mtr long and 1 x 4 swg. G.I Hot Dip)with (4mtrs long)13mm dia x 80mm long GI bolts, double nuts,double washers including supplying and fixing 15mm dia G.I pipe protection (1mtr long)to be fitted with bitumen and salt partly under the ground level and partly above the ground level driven to an average depth of 3.65mtr below the ground level and restoring the surface duly rammed.As per direction of EIC.double earthing to be done for each pole. By ISI- Medium GI Pipe.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 6 nos. 12 mm dia holes on the GI pipe.
S/D and fitting fixing of kit kat rewirable type Fuse 500 Amp( Porcelain Fuse carrier & base)) on wooden base.
S/D and fixing cable entry box input /output, main swich box.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casingcapping and Switch board both on surface] Average run 5 mtr
Add GST @ 18%
Add CESS @ 1%
S P ENTERPRISE (BID ID -6183613)
MS P P ELECTRICALS (BID ID -6178291)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .