Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.6 LAccepted-AOC | 1 | Accepted-AOC Single bid |
Tender Value
₹7.6 L
EMD Value
₹19,100
Closing Date
6 Oct 2020, 6:00 pmClosed
Executive Engineer
Executive Engineer, Minor Irrigation Division, 4th Floor, Civil Station, Kakkanad, Ernakulam Pin682030.
Mace of L I S 2019-20
2020_Irrig_379275_2
EE/MIDVN/EKM/14/ET/2020-21/S Tender
Open Tender
Civil Works - Others
Item Rate
90 days
Kunnukara
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,006
Yes
online
₹19,100
Yes
18 May 2021
4 Sept 2020
8 Oct 2020
4 Sept 2020
6 Oct 2020
4 Sept 2020
Amount
Part - A - Dismantling of motor pump , pipe , panel etc
od22056/2019_2020/IA : Charges for dismantling the 500 mm MS suction and delivery side pipe ,MS bent,valve etc of 50 HP new motor pump sets piece by piece after providing scaffonding without further damages and stacking at station compound
od22057/2019_2020/IA : Charges for dismantling the 300 mm MS suction and delivery side pipe,MS Bend, valve etc of 50 HP old motor pump sets piece by piece after providing scaffonding with out further damages and stacking at station compound
od22059/2019_2020/IA : Charges for lowering down the lifted 50 HP old, 50 HP New Motors and 5HP Vaccum Motor, Dismantling the corresponding pump sets along with base plate from the foundation after disconnecting all wire leads,then with the help of manpower by lifting,dragging, pulling and pushing using sleepers, rope etc taken it out of the Pump House without any damage, loading it to the vehicle using crane as per the direction of departmental officers at site.
od22103/2019_2020/IA : Charges for demolishing the existing concrete floor to took out the cable laid under the floor from startor to motors using special tools and deposite the demolished concrete bloks outside the pump house
od63348/2019_2020/IA : Charges for dismantling the KSEB metre board,DOL starter, Slipring Motor Starter, LDB etc. from the existing wall after disconnecting all wire leads and placing to the floor of the shed conveniently.
od8354/2020_2021/IA : Charges for dismantling the MSB /soft starter panel board, from the existing floor of the pump room after disconnecting all cables ,Keep it safely,at the floor of the pump house. If necessary covered with tarpoline sheet to protect it from moisture etc
od19759/2020_2021/IA : Charges for conveying the motor and accessories in above item No 3 to 6 from pump house to a convenient location and then unloading it using crane and then with the help of manpower by dragging, lifting, pulling and pushing using sleepers, rope etc placed it at a convenient location as per the direction of departmental officers at site, if necessary covered with tarpoline sheet to protect it from moisture etc
Part - B - Refitting of motor pump , pipe , panel etc,Renewal of pipe
od24278/2019_2020/IA : Charges for refitting the 500 mm MS suction , delivery pipe of 50 HP New motor pump sets piece by piece after providing scaffonding using fresh rubber packing bolts nuts etc .
90.14.5 : Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
od24374/2019_2020/IA : Charges for painting the rusted suction/discharge side pipe by Scrapping, cleaning and painting with Anticorrossive bituminous black paint over a coat of zinc rich primer
od25503/2019_2020/IA : Supply , conveying and erecting the 500 mm dia MS pipe in suction/ delivery side having sheet thickness 6 mm and cutting in to required length, facing the cutting edges,painting two coats of synthetic best quality enamel paint over a coats red oxide primer, including conveyance charges to pumphouse and labour charges for loading, unloading,etc.
od25505/2019_2020/IA : Supply , conveying and erecting the 300 mm dia MS pipe in suction/ delivery side having sheet thickness 6 mm and cutting in to required length, facing the cutting edges,painting two coats of synthetic best quality enamel paint over a coats red oxide primer, including conveyance charges to pumphouse and labour charges for loading, unloading,etc.
od19825/2020_2021/IA : Supply, fabrication, conveying and erecting the 300 mm dia 1 mtr /required length MS pipe bend by using having 6 mm sheet thickness,facing the cutting edges ,painting two coats of synthetic best quality enamel paint over a coats red oxide primer etc at complete.
od26557/2019_2020/IA : Supply and providing MS – Flanged joint with 12 mm thick flange, for 500mm dia MS pipe - with suitable bolt holes fixing the flange in position with required welding around the flange, pipe joint, grinding for smoothing the welded portion, including painting with 2 coats of synthetic enamel paint over a coat of red oxide primer etc., complete. Including providing necessary bolts & nuts, rubber packing, grease etc as required.
od26559/2019_2020/IA : Supply and providing MS – Flanged joint with 12 mm thick flange, for 300mm dia MS pipe - with suitable bolt holes fixing the flange in position with required welding around the flange, pipe joint, grinding for smoothing the welded portion, including painting with 2 coats of synthetic enamel paint over a coat of red oxide primer etc., complete. Including providing necessary bolts & nuts, rubber packing, grease etc as required.
od19957/2020_2021/IA : Supply and fabrication conveyance and installation of angle iron frame work forsupporting MS pipe
od19958/2020_2021/IA : Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand: 6 graded stone aggregate 20 mm nominal size) for supporting MS pipe
14.7 : Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
od63383/2019_2020/IA : Charges for conveying back the 50HP old and 50HP New motors,5HP Vaccum motor pump set, KSEB metre board,MSB/ soft starter panel board,DOL starter, Slipring Motor Starter, LDB etc. in the above item 1.3 and 1.6 to kunnukara pump house:- with the help of manpower by lifting,dragging, pulling and pushing using sleepers, rope etc taken it out of the Pump House without any damage, loading it to the vehicle using crane ,Unloading the above items at newly constructed kunnukara pump house with the help of crane and then with the help of manpower by lifting,dragging, pulling and pushing using sleepers, rope etc. placed it conveniently on the shed.
od6270/2020_2021/IA : Charges for refitting the 50 HP old and 50 HP New Motor pump along with base plate to the newly constructed pump room foundation reconnecting all wire leads coupling with pulley, checking correct alignment, giving connection to starter,regulator, testing and trial run on full load.
od6271/2020_2021/IA : Charges for refitting the KSEB meter Board, DOL Starter, slip ring motor starter in position and 5 HP Vacuum motor pump set to the foundation.
od8355/2020_2021/IA : Charges for refitting the MSB /soft starter panel board, connecting the cables, testing and trial run the motor pump set at full load.
Part - C Electrification works
90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.17.11 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.34 : Supplying and fixing brass batten/ angle holder including connection etc. as required.
2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
od21966/2019_2020/IA : Blank plate 1 M
od21968/2019_2020/IA : Supply and providing 12W LED Bulb in the existing Holder
90.3.19.4 : 1200 mm 2X20W LED Lamp with box type fixture
od21969/2019_2020/IA : Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover suitable for 9 W CFL to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
od20286/2020_2021/IA : supply and providing test joint for the earthing system using 2 No.s of the 2x25x3mm size tinned copper strips including cutting and bending to shape drilling necessary holes and fixed to the watering pipe etc as required.
od20287/2020_2021/IA : supply and providing the 300x 300x6mm size cast iron gully trap with covering at the top of the inspection chamber of earth pit as required
od24357/2019_2020/IA : Supply conveyance installation testing and commissioning of the street light fittings with 20W LED street light with asymetricbeam angle 130*50 degree with luminaire efficiency more than 15 lm/W rugged aluminium alloy housing with all accessories complete(OSRAM STARDA Plus/equivalent) on existing pipe and giving connection with 24/.20 3 coreflex wire as required
od24464/2019_2020/IA : Supply and drawing 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the size 4 sq mm 3 run
od25414/2019_2020/IA : Supply and laying 15 mm class B GI pipe as earth lead protection in 0.6 Mtr below ground
od25442/2019_2020/IA : Supply and laying bare earthing conductors of the SIZE 4 SWG laid 0.6 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil).
90.16.5.6 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
od25469/2019_2020/IA : supply of superior quality copper earth socket for 14SWG (2mm)sizes of earth conductor including crimping etc. as required.
od25479/2019_2020/IA : Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required 25 x 6mm brass bolt & nut
od25480/2019_2020/IA : Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required 25 x 3mm brass bolt & nut
90.12.24.7 : Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
90.12.6.31 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.
90.12.24.10 : Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
90.12.39.10 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.
90.12.40.10 : Supply & laying of one No. PVC insulated and PVC sheathed armoured copper power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.
9.1.10 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 35 sq. mm (28mm)
9.1.24 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
5.18 : Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
5.19 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
od12087/2020_2021/IA : supply, installation testing and commissioning of FN 125A TPN Switch Disconnector unit in sheet Enclosure for operating the 50HP Slip Ring Induction motor
od12088/2020_2021/IA : supply, installation testing and commissioning of FN 32A TPN Switch Disconnector unit in sheet Enclosure for operating the 5HP Vaccum motor pump set.
od12125/2020_2021/IA : supply, installation testing and commissioning of Push Button, for operating the 50HP Squirrel cage induction motor
1.17.8 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.8 x 1.5 sq. mm
KSEB CHARGES
od8353/2020_2021/IA : Charges for KSEB meter shifting and reconnection charges as per actuals against submission of original bills/receipt.
Bidder Name
KEYAS ELECTRICALS
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_542619.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .