Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.4 LAccepted-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L1 | Accepted-AOC LOWEST REASONABLE BID | |
| 2 | L2₹23.7 L+₹1.3 L (5.75%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L2 | Rejected-Finance NOT LOWEST |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
13 Mar 2024, 6:00 pmClosed
CWE ARMY JODHPUR
CWE ARMY MULTAN LINE ARMY AREA JODHPUR-342010
REPAIR / MAINT TO HT OVER HEAD LINE AND POLES OF 33 KV AND 11 KV, POWER AND DISTRIBUTION TRANSFORMERS, HT PANELS , EARTHING AND OTHER CONNECTED WORKS AT RALAWAS UNDER GE BANAR
2024_MES_641553_1
82324/108/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
RALAWAS
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE BANAR
₹60,000
Yes
10 Jun 2024
9 Feb 2024
21 Mar 2024
9 Feb 2024
13 Mar 2024
23 Feb 2024
10 Feb 2024 - 22 Feb 2024
Amount
Supply and fix in repair straight through joint heat shrinkable type suitable for 11 KV 3 core PVC /XLPE cable of cross sectional area 120 Sqmm to 185 Smm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , Indoor termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 Sqmm to185 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 33 KV grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 240 Sqmm to 300 Sqmm complete all as specified and directed by Engr-in-charge.
Supply and fix in repair cable jointing kit for 33 KV grade out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 240 Sqmm to 300 Sqmm complete all as specified and directed by Engr-in-Charge.
M&L for checking , tightening & Replacement of jumpers , clamps connectors of 33 KV bus bar for the Power transformer in the yard / sub station complete all as specified and directed by Engr-in-Charge.
M&L for resagging of overhead conductor section of 33 KV including binding/re-binding of conductor with suitable size of wire and providing of jumpers at the ends as per site requirements complete all as specified and directed by Engr-in-Charge.
M&L for replacement of rusted/broken GI earth wire of 4 mm dia for guard on Overhead line by providing reels and clamps and any other items required for fixing as per site requirement complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down HT pole of old ACSR conductor complete all as specified and directed by Engr-in-Charge.
M&L for Replacement of old ACSR conductor with new ACSR conductor including binding of wire and providing jumpers at the end as per site requirement complete all as specified and directed by Engr-in-Charge.
Fixing and restringing of old serviceable (ACSR) conductor obtained from items No 10 here in before including binding complete all as specified and directed.
Taking out old unserviceable 33 KV pin insulator incl taking out 33 KV OH ACSR conductor and supply and fix 33 KV pin type, porcelain, vitreous, insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut for fixing of insulator on HT pole incl refixing the OH ACSR conductor at the same place incl binding the conductor to insulator with new binding wire complete all as directed.
M&L for replacement of defective/damaged Disc insulators suitable for 33 KV overhead conductors including removing/providing jumpers with line conductors as per required at site complete all as specified and directed by EIC.
M&L for straightenig of cross arms with clamps including tightening of nut bolts , washers complete all as specified and directed by Engr-in-Charge
M&L for Servicing, testing the functioning of all the existing 33 KV panels,Indoor/Outdoor VCBs & all other connected accessories and carrying out necessary maintenance such as applying grease, gel etc., including calibration of VCBs, carrying out necessary repairs along with making arrangements for testing of equipment, and necessary instruments required for testing of relays installed over the panels all as specified and as directed by Engr-in-charge.Note: (i) Spare parts shall be measured and paid separately under relevent schedule items. (ii) Calibration report submitted after completion of work
M&L for Servicing, testing the functioning of all the existing 11 KV panels, VCBs & all other connected accessories and carrying out necessary maintenance such as applying grease, gel etc., including calibration of VCBs, carrying out necessary repairs along with making arrangements for testing of equipment, and necessary instruments required for testing of relays installed over the panels all as specified and as directed by Engr-in-charge Note: (i)Spare parts shall be measured and paid separately under relevent schedule items (ii) Calibration report submitted after completion of work
Supply and fix Over Current and Earth fault protection relay suiable for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge. Model SLR 140 C of CG or its equivalent.
Supply and fix Master Trip relay operating viltage 110V AC and 24V DC suiable as per existing make for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix announciator panel 12 window type as per existing make and capacity complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Buch, WTI , OTI Trip relay suitable existing size for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Digital Volt meter suitable for HT VCB Panel complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Digital Ammeter suitable for HT VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Auxialiary relay for Buch, WTI,OTI Alarm suitable for HT VCB Panel all as specified and directed by Engr-in--Charge.
Supply ,fixing and testing in replacement of 12V 2Ah battery 55 Nos for output 110 V DC ( 55 Nos battery for 2 Ah in series connection installed on iron rack suitable for battery holding in three compartment) maintence free battery complete connected to existing HT VCB Panel of 33/11 KV complete all as specified and directed by Engr-in-Charge.
Taking out old unsv stay assembly and Supply and fix stay assembly complete comprising of MS galvanized stay plate 30cm x30cmx6mm , MS galvanized stay rod 20 mm dia with nut 180 cm long , MS galvanized stay bow 40cm long with 2 Nos galvanized thimbles with and including all fittings iNote:- Excavation, PCC for foundation (PCC 1:3:6) , loop type insulator, shackle & clamp shall be measured and paid separately under relevent schedule items
Taking out old stay strand wire and Supply and Fix GI stay strand wire of size 7/4mm complete all as specified and directed by EIC.
Supply and topping of transformer oil with adequate dielectric strength as mentioned in relevent IS as and when required to top up as replacement /evaporation ,leakage all as specified and directed by Engineer-in-Charge. Make : Apar , Power oil , servo
Dehydration of Transformer oil (mounted on plateform/ poles etc) with the help of filtering and drying plant by mechanical machine of suitable capacity to achive dielectric strength of 50 KV complete all as specified and directed by EIC. Note : a) The filteration of the transformer oil is to be carried out at different sub station in AGE E/M Nagtalao and also at Main receiving sub Station. (b) The report along with sample of oil before filteration & after filteration to be submited by contractor for approval by GE (c) The filteration is to be carried out on load i.e. without switching off supply. (d) Transformer oil for topping up will be paid separately under relevant item of Sch 'A'.
Taking out Old unserviceable indicator lamp from 11 KV VCB Panel and Supply and fix new phase indicating lamp neon type 24DCV/110DCV complete as per existing make and size with contct block & holder assembly of RYB Colour as directed
M&L cross arms, bracings, supports, clamp and back plates fabricated from structural steel section including nut/bolts washers, welding, bending, cold or hot drilling holes for bolts of any shape and size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including taking out old unserviceable complete all as directed.
Supply fixing and connecting and testing single pole zinc oxide (gaplesssurge type) heavy duty station class, self supporting outdoor type lighting arrester having rated voltage 30 KV (rms) discharge current 65 KA insulationlevel 35/75 KV/KVP (Peak) suitable for rated system voltage of 33 KV supplysystem with maximum continuous operating v oltage (MCOV) not less than17.05 KV (rms) with highly non linear ceramic resister made of zinc oxide inhermetically sealed container complete with metal base, base inculator andsuitable terminals for ground connections and pressure relieving arragementcomplete all as specified Note : The rate quoted against above itemshall include necessary fixing arrangement of lightening arresster on twopole/four pole structure as per recommendations of manufactures.
Dismantling old unserviceable LA and supply and fix lightening arrestor 11000 volts non linear resistor type conforming to IS-3070 Part I complete, line discharge class-2 nominal discharge current 10 KA & high discharge 65 KA assembly suitable for 11 KV incl. all clamps, nuts, bolts & washers & connecting to earth with GI earth wire complete all as specified and directed by Engr-in-Charge
Dismantling of existing defective HT 11 KV Gang operated air break switch and Supply and installation, commissioning and testing of HT 11 KV outdoor type triple pole gang operated air-break switch suitable for horizontal mounting rotating type with 9 insulator 200 amps current rating complete mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrangement, flat iron clamp 50x6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers complete all as directed by Engr-in-Charge
Dismantling of existing defective HT 33 KV Gang operated air break switch and Supply and installation, commissioning and testing of HT 33 KV outdoor type triple pole gang operated air-break switch double stack type suitable for horizontal mounting rotating type with 9 insulator 200 amps current rating complete mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrangement, flat iron clamp 50x6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers complete all as directed
Taking out old silica gel breather and Supply & fix new Silica Gel breather having threaded bore as per site required.
Taking out old Moisturised silica gel from breather and Supply & filling new silica Gel in the breathers in crystals complete.
Taking out old unserviceable PG Clamp and supply and fix new PG clamp in repair all as directed and specified.
Taking out old unserviceable HT cable and Supplying,laying, jointing, testing and commissioning of aluminium 95 sqmm XLPE insulated screened PVC bedded galvanised steel strip or wire armourred electric power cable (Heavy duty ) with aluminium conductor 11000 volts grade, cross sectional area 95 sqmm 3 core suitable for 11KV earthed systems all as specified and directed.
Taking out old unserviceable HT cable and Supplying ,laying, jointing, testing and commissioning of aluminium 120 sqmm XLPE insulated screened PVC bedded galvanised steel strip or wire120 sqmm 3 core suitable for 11KV earthed systems all as specified and directed.
Taking out old unserviceable HT cable and Supplying ,laying, jointing, testing and commissioning of aluminium 185 sqmm XLPE insulated screened PVC bedded galvanised steel strip or wire 185 sqmm 3 core suitable for 11KV earthed systems all as specified and directed.
Excavating in trenches n.exc 1.5 m width and n.exc 1.5m in depth for taking out cable and cable cover and getting out in any type of soil
Returning, filling in, including spreading levelling, watering and well ramming in layers n.exc 25 Cm
Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point
M&L for sand cushioning to PVC/ XLPE cables with low grade sand and punning to provide required cover to UG cables. Note :- For the purpose of payment only punned thickness will be measured
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as directed at site by Engineer-in-Charge.
M & L for laying / topping up of 40 mm stone aggregate in switch yard/electric installations/ two pole/ four pole structure and all as directed at site by Engineer-in-Charge.
M&L for Surface excavation n.exc 30 cm deep and averaging 15 cm and geeting out in any type of soil incl cutting, cleaning and removing of bushes/branches/vegitation complete from the site all as directed by Engineer-in- Charge.
Dismantling of existing PCC/Steel Pole and S&F Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-64 (12 metres long) complete all as directed by Engineer-in- Charge.
Dismantling of existing aluminium strip and Supply and fix aluminium strip 25X3.15 mm with saddles / porcelin insulator is to be tightend with pole by using suitable size of GI wire for pole and down conductors on the top of pole up to test point complete all as specified and directed by Engr-in-Charge.
Dismantling of existing test point and Supply and fix test point terminal block made of Gun metal or phosphorus bronze size 75X75X25 mm drilled and screwed including 3 nos 8 mm dia 25 mm long hex head screw complete all as specified and directed by Engr-in-charge.
Materail and labour for relacement of unserviceableexisting earthing with bore well earthing with the help of mechnical boring machine of 150mm dia 30 mtr depth excuting 50mm dia medium GI pipe duly drilled all around 150mm dia hole at a distance of 200mm from hole to hole upto min 20 mtr depth upto warer level including supply and fix 150mm dia (O.D) UPVC pipe 6 Kg/sqcm rating -06 mtr long with the help of suitable size clamps with nuts bolt and washer -01 Nos including charcoal dust,salt fill in bore well for earh conductivity M&L for providing 32X6 mm GI strip upto 10 mtr protected by GI pipe 40mm dia medium grade in ground and coonected to terminal block grounding of borewell withPCC(1:2:4) type B-1 / brick massonary pit of size 45X45X45Cm complete and give the minimum earth test result below 1 ohm complete all asspecified and directed by Engr-in-Charge Note:-(i) The charge for mechnical boring machine UPVC pipe 150mm dia length 6 mtr ,GI strip 32X6mm with protection GI pipe 40mm dia medium grade &PCC work is deemed to be include in above qouted rate . (ii) GI tubing 50mm dia medium grade deemed to be include in above qouted rate . (iii) Earthing shall be tested by contractor in presence of JE/Engr-in-Charge and record shall be maintained .
Dismantling of existing earthingand M&L for GI plate Electrode of size 60 Cm X 60 Cm X 6 mm thick burried directly in ground vertically at a depth not less than 2.25 mtr. below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr. below normal ground level , connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts and washers of galvanised iron , earth lead wire protected by means of 15 mm bore dia light grade GI pipe up to switch board / panel board , all as specified and shown in MES schedule Electrical Plate No:-5 of SSR Part I, including excavation and earth work in any type of siol , PCC 1 : 2 : 4 type C1 in chamber , RCC 1:2:4 type C1 40 mmthick cover slab with 6 mm dia MS bars at 100 mm centre to centre both ways,with 6 mm dia MS hook, Charcoal dust, salt , funnel for watering complete as shown on electrical plate No 2 of SSR Part I. all as specified and as directed.
Dismantling of existing copper strip and Supply & laid copper strip in repairs of size 25 mm X 3.15 mm as a ring conductor network buried in ground 1 mtr below from surface complete all as directed at site by Engineer-in -charge
Material and labour for cutting the branches/trees near the HT OH line upto clearance area 5mtr around OH line by cutting the branches and removing the wastage from site to disposal area and all as specified and direced, Note :-(i) The necessary man power tool and plant , cutting tools and JCB if required for cutting/ prunning of branches is deemed to incl in the rate quoted for the job (ii) Proper shut down will be taken from JE E/M only.
Dismantling of existing GI earthing and M&L for plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 metre deep below ground level) with the top edge of earth plate at a depth not less than 1.5 metre below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm in alternate layers on all sides and including GI earth strip of 32x 6 mm as earth electrode bolted with GI nuts, bolts & check nuts and rivetted to earth (Plate) electrode at one end and connected to Panel at the other, earth strip protected by and incl GI pipe 40 mm dia (medium grade) from top of electrode to Panel and also incl watering pipe GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B0 using 12 mm graded crushed stone aggregate, RCC cover with handle, funnel, wire mesh including necessary excavation & earth work, etc as shown on electrical plate No 3 of SSR Part I.
Dismantling of existing earth continuity and M&L for earth continuity conductor or main earthing lead fixed to wall on insulators or recess or chases or buried in ground or drawn in conduit/pipe for loop earthing etc. as required 32x6mm galvanized strip complete all as specified and as directed by EIC.
Preventive maintance /servicng and testing of power transformer 2.0 MVA of 33/11KV at MRSS Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Preventive maintance /servicng and testing for power transformer 1.0 MVA of 33/11KV at MRSS Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Preventive maintance /servicng and testing of distrubution transformer of various capacity upto 500 KVA at Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Supply and fix in repair Spring charging Motor 230V AC/DC universal type for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Gear assembly Big size for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Gear assembly small size for existing 11 KV VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Trip holding Shaft for existing 11KV VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Trip coil for existing VCB complete all as specified and dirtected by Engr-in-Charge
supply and fix in repair Close holding shaft for existing VCB complete all as specified and dirtected by Engr-in-Charge
supply and fix in repair Close coil for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Charging Spring for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Drum Switch for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Anti Pumping device 24V DC for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply only in repair Limit switch complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Insulating rubber matting ISI mark for 11KV 2.50mm thickness of matt confirming to IS:15652-2006 complete fixing on floor with suitable pasting material complete as per specification as directed by EIC
Supply only TNC switch for 11 KV VCB breaker as per existing make and specification and directed by EIC
Supply only Local remote switch for VCB breaker as per existing make and specification and directed by EIC
Supply and fix in repair 11 KV VCB trolly gear having 9 teeth complete all as specified and directed by Engr-in-Charge
Supply only in repair Service position switch for existing 11 KV VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Vaccum interruptor for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply only Local remote switch for existing11 KV VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Dual Core CT Indoor type suitable for 11000 volts for existing VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair 11 KV PT resin cast ration 11KV /110V 25VA class 0.2 for existing VCB complete all as specified and dirtected by Engr-in-Charge
M&L for painting with two coat alunium colours at 33 KV MRS Yard ( 14Nos ) Tower pole 12 mtr height horizental arms and other structures etc complete including all clamps,bars,iron item inside the yard as per site existing complete all as per directed by EIC
M&L for laying 40 to 50 mm thick quarry faced stone slab 25 to 30 cm wide and not exceeding 60 cm long laid dry abutting each other with gap between adjacent patties n.exc 10 mm for 33KV yard/sub stn protection for aggreagte complete all as specified and dirtected
Supply and Fix PVC insulated multicore FR PVC sheathed multistranded cables with bright annealed electrolytic bare copper conductor 1100 V 2.5 sqmm 12 core conforming to IS-694:2010
Supply and Fix PVC insulated multicore FR PVC sheathed multistranded cables with bright annealed electrolytic bare copper conductor 1100 V 2.5 sqmm 4 core conforming to IS-694:2010
M&L for Cleaning of Power transformer,distribution transformer,VCB outdoor body through cleaning agent and removing the dust by blower,remove corrosion take proper shut down complete as specified and dirtected by EIC
M&L for painting of power transformer/distribution transformer two coats of synthetic enamel paint over a coat of existing colour of transformer before painting properly scrab ,clean and then apply paint on transformer body complete using spray gun for shining as per specification and directed by EIC
M&L for painting with two coats of synthetic enamel paint over a coat of cross arms, bracing supports clamps,MS sheet from structural steel sections including steel poles/Tower poles and mud clay on RCC pole( 2 Pole & 4 Pole also including) before painting completely clean the rust on iron complete as directed .Note :- The item included in the painting 3 Nos 30 cm wide bands black & White synthetic enamel paint in alternate layer upto 1.0 mtr high above foundation and writing the pole No in 5 cm wide on base of Black colour with HT as per direction of Engr-in-Charge.
Supply and fix in repair 33 KV SRBP tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV Fibre glass tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV fibre tube with metal fitting on both ends only for dropout fuses as specified and directed by EIC
Supply and fix in repair 11 KV SRBP tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 11 KV Fibre glass tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 11 KV fibre tube with metal fitting on both ends only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV Male contact/moving contact blade as specified and directed by EIC
Supply and fix in repair 33 KV Female contact/fix contact jaw as specified and directed by EIC
Supply and fix in repair 33 KV Tinned copper flexible jumper 200A/400A as specified and directed by EIC
Supply and fix I n repair33 KV MS Jumper carrier as specified and directed by EIC
Supply and fix in repair 11 KV Male contact/moving contact blade as specified and dirtected by EIC
Supply and fix in repair 11 KV Female contact/fix contact jaw as specified and dirtected by EIC
Supply and fix 11 KV Tinned copper flexible jumper 200A/400A as specified and dirtected by EIC
Supply and fix in repair 11 KV MS Jumper carrier as specified and dirtected by EIC
Supply and fix in repair 12KV/250 Amp H.V brass set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix 1.1 KV/250 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix in repair 1.1 KV/400 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix in repair 1.1 KV/630 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Dismantling of chain link fencing wire mesh any type any size complete
S&F MS angle iron as in fencing posts and struts in fencing includling cutting tops to shape as dirtected drilling holes cut to length bent to shape ,notching for wire etc conforming to Fe-290 Gde E-165
S&F MS work confirming to Fe 310-O as in FI fillets for securing chain link fecing angle iron horns,posts etc cut to length bent to shape with necessary cuts drilling holes etc all as specified and directed by EIC
S&F Chain link fencing of MS GI wire mesh 3mm dia of GI wire mesh upto to into mattresses or cages lapped wired incl staple all fixing arragement complete all as dirtected by EIC
S&F MS round bar 10mm dia confriming to Fe 290 gde E-165 as line wire for chain link fencing type including cutting to length,bend to shape required as per site , welding ,binding with MS wire all complete as dirtected by EIC
S&F MS scew bolts(Machine made) with heagonal or square heads at one end and screwed the other or screwed both ends each screwed end to be fitted with washer and one hexagonal or square nut ex 5cm but not exceeding 10cm long and dia of shank 11 to 15mm all complete as per dirtected
M&L for concrete 1:4:8 type D-2(using 40mm grade stone aggregate) as in sub base foundation/flooring etc.as specified & dirtected by Engr-in-Charge
M&L for stone masionary squared rubble walling jodhpur type brought uptocoursewell bonded bedded and soliding hearted built will cement mortor 1:4 as per pecpcified as directed by Engr-in-Charge
M&L for rendered 10mm thick plaster wall/surface for two coat as per specified as dirtected
M&L for white washing on fresh plaster wall/surface for two coat as per specified as dirtected
M & L for PCC type B2 ratio 1:2:4 (using 20 mm graded stone aggregate ) as in platform, sub base for foundation etc. complete with quick setting cement complete all as specified and directed by Eng-in-Charge.
S&F in replacement of 3 Pole 12 Amp contractor confirming to IEC-60947-4-1 complete all as specified as dirtected .Make:- Siemes/L&T or equivalent
S&F in replacement of 3 Pole 12 Amp overload protection relay confirming to IEC-60947-4-1 complete all as specified as dirtected Make:- Siemes/L&T or equivalent
S&F in replacement of Electronic timer 03-30 sec 415V 50Hz with mounting kit suitable for as per site requirement all complete as specified as dirtected by EIC
S&F in repair expulsion fuse (drop out fuse) mounted on 2 Nos of HT insulators, single pole upto 50 Amps 11 KV with spring mechanism complete in all respects and connection as directed.
Supply and fixing in repair loop insulator vitreous procelain white,brown,green large size overall dimenssion 90mmx140mm clerance of hole 25.5mm complete as per directed by EIC
Anil Builders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .