Vikas Dhiman
Municipal Corporation Yamunanagar
Supplying, installation, testing and commissioning of Silent Generator Set 25 KVA at M.C office Jagadhri near Jhanda chowk in Municipal Corporation Yamunanagar-Jagadhri Recall
2026_HRY_548124_1
202658B71F76 F474 4744 AC77 70C58432976B288ULB
Open Tender
Civil Works
Works
55 days
Jagadhari
2 documents required · 2 mandatory
₹1,000
₹18,500
Yes
16 Sept 2026
16 Sept 2026
26 Sept 2026
16 Sept 2026
25 Sept 2026
16 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | [23.28.31.1]Supplying, Installation, Testing and Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV plus or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system, including testing at factory and site with fuel, load for test and other necessary arrangements with rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Deg C, 50% RH and at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV plus or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018. (B) Engine mounted Instrument Panel fitted with and having digital display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication and Voltage indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lubrication Oil trip indication
(ix) Engine Running Hours indication (x) Fuel Level
(C) Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH and at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
(D) Base Frame and Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
(E) FUEL TANK: Daily service fuel tank of suitable liters capacity, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications and accessories as required as per specifications.
(F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.
(G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set.
H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof and dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV plus or better norms etc. and.
(I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering and protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase and Total), KW and provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software etc. as per approved by Engineering in charge and including the following: 1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C and E/F and shunt trip.
2. Auto/Manual/Test/Off selector switch
3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering
5. Energy analyser unit to indicate current, Voltage( LN and L_L), kW, kVA (Phase and Total), Frequency, KWH, PF.
6. LED Indicating lamps for load on mains and load on set
7. Fuse/ MCB for instruments
8. Battery charger, complete with transformer/ rectifier,
D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.
9. Main supply failure monitor
10. Supply failure timer
11. Restoration timer
12. Control unit with three impulse automatic engine start/stop and failure to start lockout.
13. Impulse counter with locking and reset facility.
14. ON/OFF/Control circuit switch with indicator
15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning
16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories
17. Maintenance notification based on Engine Run Hour and due date.
18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.
19. Suitable rating of AC contactors/ ATS / ACB with control wiring. 1. 25 KVA [Rate] | 1 | Each | 4,15,436 | ₹4,15,436 |
| 1.02 | [23.32.1.1]Automatic Power Factor Correction (APFC) System
Supply, Installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel, indoor type floor mounted free standing totally enclosed, extendable, IP 42, of following capacity for 3 phase, 415 V plus 10 %, 50 Hz AC System for Ambient temperature -5°C to plus 40°C, fabricated in compartmentalized designed made of CRCA sheet steel of 2.0mm thick for framework and covers, 3 mm thick for gland plate i/c cleaning and finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitor and reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminum alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 and 2) APFC Panel shall be in compliance with IS :16636 and CPWD Specifications etc. as per below details
(A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set along with required Instruments and accessories with extended rotary handle and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.
(B) Instruments and Indications i) 3-Phase current sensing APFC microprocessor relay/controller , advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR and above) with Communication Ethernet/RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT`s accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.
i) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.
ii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V and I, Frequency.
iii) Suitable rating control transformer shall be provided for control and indication circuit.
i) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB`s.
ii) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS 1100 V grade, PVC insulated multi stranded copper control wire.
(B) Bus Bars
1.3 Amp per Sq.mm, TPN, Electrolytic grade Aluminum bus bar of capacity 1.25 times of incomer rating as per CPWD specification.
(C) Outgoings (APFC Section)
Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor, the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and other features as per CPWD Specifications and relevant IS Code having following:
(i) Capacitor bank ratings and stages shall be as per
(ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism.
(iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.
(iv) 14% Detuned Reactor of class H insulation and 150% linearity in series with Capacitor. 1. 50 KVAR [Rate] | 1 | Each | 1,37,302 | ₹1,37,302 |
| 1.03 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate] | 6 | Each | 2,721 | ₹16,326 |
| 1.04 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate] | 6 | Each | 652 | ₹3,912 |
| 1.05 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate] | 20 | Metre | 96 | ₹1,920 |
| 1.06 | [24.11.40]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING AND ERECTION/LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR CABLE 0.75 METER BELOW GROUND LEVEL COVERED WITH SAND AND BRICKS INCLUDING EXCAVATION AND REFILLING OF TRENCHES 40. 35 Sq mm 4 core (Arm.) [Through Rate] | 120 | Metre | 428 | ₹51,360 |
| 1.07 | [24.7.1]RCC FOUNDATIONS FOR DG SET 1. 30 to 40 KVA DG Set [Through Rate] | 1 | Each | 15,711 | ₹15,711 |
| 1.08 | [36.5.1]Fabrication, supplying, Installation testing and commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable
alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth
terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump and diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3
phase, 50Hz Ac Supply with enclosure protection class IP 42 as required: 1. INCOMING 250A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter (0-250 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A OUTGOING (Note: All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 125 A, 50KA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Jockey Pump 63 ?, 50?? ?PN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/Low Lub. Oil pressure, HighWater Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers.Sensors, annunciation window for fault indication,complete as per specification [THROUGH RATE] | 1 | Each | 2,97,027 | ₹2,97,027 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.91 MB
BOQ_627821.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .