Er. Rahul Dhiman EE
JSV Division Nagrota Bagwan
Providing Separate WSS to Vill Serathana Rounkhar and Jassour in Tehsil Nagrota Bagwan SH-Laying jointing of Rising main and Errection of Submersible pumping machinery
2022_HPIPH_61472_1
NGB-KNG01-773
Open Tender
Civil Works - Others
Item Wise
180 days
Nagrota Bagwan
Please refer Tender documents.
10 documents required · 10 mandatory
₹800
₹87,250
Yes
6 Oct 2022
6 Jun 2022
15 Jun 2022
6 Jun 2022
15 Jun 2022
6 Jun 2022
Amount
Excavation in foundation trenches etc. (in pipes and pits) in all kinds of soil such as pick work, jumper work, blasting work soft /hard rock, chiesling soft /hard rock where blasting is prohibited, slushy, daldal and saturated soil I/c pumping or bailling out water with in all heights stacking the excavated soil with 15cm layer when required into plinth ,sides of foundations etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus earth as per direction of Engineer-in-Charge with in all lead and lifts .
Laying, jointing & testing of bevelled ended GI pipe Medium Class with MS Flange of following Table (6%) flange joint & other Pipe (94%) circumfrential butt welded joints by electrical arc welding (welding thickness shall be equal to pipe wall thickness) and testing of GI pipe of following dia meters conforming to IS 1239-2004 (Part-II), having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers , all short pieces, bends etc. as per site requirement made from parent tubes . The laying of pipe shall also include welding of flanged joints wherever required duly welded in three layers (two inner & one outer) and all operations such as cutting, welding, jointing, fabrication of bends, tees, making bevelled pipe ends suitable for butt welding , lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (Earth work in trenches will be measured and paid for separately) . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes ( If damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts.
100 mm dia MS Flange of Table - 28
100 mm dia MS Flange of Table - 17
100 mm dia MS Flange of Table - 5
80 mm dia MS Flange of Table - 28
80 mm dia MS Flange of Table - 17
80 mm dia MS Flange of Table - 5
Providing MS flanges (In pairs) for the joints of GI pipes mentioned as below and same shall conform to BIS 6392-1971 ( latest with up to date amendments) including the cost of nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets conforming to relevant BIS standards and it shall also include carriage of materials within all leads and lifts complete in all respect to the best satisfaction and direction of Engineer in charge, The cost of laying, jointing and welding shall be paid separtely.
100 mm dia MS Flange of Table - 28
100 mm dia MS Flange of Table - 17
100 mm dia MS Flange of Table - 5
80 mm dia MS Flange of Table - 28
80 mm dia MS Flange of Table - 17
80 mm dia MS Flange of Table - 5
For WSS Serathana - Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Total Head = 185.10
Discharge required from each pump. = 4.70 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation = The altitude of place is 800 mtrs above MSL
Type of current = AC Three phase supply with
Rate Voltage = 415+ 10%
Type of water and its source = Clear water from T/Well
Charactristics of water = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3)= -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Dia of Bore = 200 mtrs
Static head in Mrs = 164.00 mtrs.
Length of R/Main = 1670 mtrs.
Dia of Rising main = 100 mm (M)
No of working hours per day = 8 Hours
Limit of pump operation = (-) 15 % (+) 10% of total head
R.P.M. of pumping set = 2900 RPM ( or to be specified by the tenderer)
Test run = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of required rating automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Variable frequency drive starter of required Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Power and Control wiring and Busbar
Installation, Commissioning and Software Development
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system
SMPS 4.5 Amps to energise PLC system
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Control MCB for Automation System
Level Sensor to indicate the water level of tank remotely
Shielded Data Cable for Communication of Level Sensor with PLC
Installation, Commissioning and Software Development
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged sluice valve of Class ASA-150 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-150 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia(mtrs)
Delivery pipe = 100 mm dia (mtrs) NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For WSS Rounkhar :- Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Total Head = 232.38
Discharge required from each pump = 4.52 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation = The altitude of place is 800 mtrs above MSL
Type of current = AC Three phase supply with
Rate Voltage = 415+ 10%
Type of water and its source = Clear water from T/Well
Charactristics of water = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Dia of Bore = 200 mtrs
Static head in Mrs = 193.00 mtrs.
Length of R/Main = 1450.00 mtrs
Dia of Rising main = 80 mm (M)
No of working hours per day = 8 Hours
Limit of pump operation = (-) 15 % (+) 10% of total head
R.P.M. of pumping set = 2900 RPM ( or to be specified by the tenderer)
Test run = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of required rating automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Variable frequency drive starter of required Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Power and Control wiring and Busbar
Installation, Commissioning and Software Development
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system
SMPS 4.5 Amps to energise PLC system
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Control MCB for Automation System
Level Sensor to indicate the water level of tank remotely
Shielded Data Cable for Communication of Level Sensor with PLC
Installation, Commissioning and Software Development
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 52 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 52kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 100 mm dia (mtrs)
Delivery pipe = 80 mm dia (mtrs) NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For WSS Jasour :- Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Total Head = 210.87
Discharge required from each pump = 3.48 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation =The altitude of place is 800 mtrs above MSL
Type of current = AC Three phase supply with
Rate Voltage = 415+ 10%
Type of water and its source = Clear water from T/Well
Charactristics of water = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Dia of Bore = 200 mtrs
Static head in Mrs = 150.00 mtrs.
Length of R/Main = 3850.00 mtrs
Dia of Rising main = 80 mm (M)
No of working hours per day = 8 Hours
Limit of pump operation = (-) 15 % (+) 10% of total head
R.P.M. of pumping set = 2900 RPM ( or to be specified by the tenderer)
Test run = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of required rating automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Variable frequency drive starter of required Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Power and Control wiring and Busbar
Installation, Commissioning and Software Development
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system
SMPS 4.5 Amps to energise PLC system
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Control MCB for Automation System
Level Sensor to indicate the water level of tank remotely
Shielded Data Cable for Communication of Level Sensor with PLC
Installation, Commissioning and Software Development
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 52 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 52kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 100 mm dia(Mtrs
Delivery pipe = 80 mm dia (Mtrs) NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For WSS Setathana :- Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Total Head = 146.93
Discharge required from each pump. = 3.85 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 800 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 415+ 10%
Type of water and its source = Clear water from T/Well
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Dia of Bore = 200 mtrs
Static head in Mrs = 115.00 mtrs.
Length of R/Main = 1560 mtrs.
Dia of Rising main = 80 mm (M)
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of required rating automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Variable frequency drive starter of required Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES/ L&T and any other make approved State Level Technical Committee JSV.
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Power and Control wiring and Busbar
Installation, Commissioning and Software Development
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system
SMPS 4.5 Amps to energise PLC system
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Control MCB for Automation System
Level Sensor to indicate the water level of tank remotely
Shielded Data Cable for Communication of Level Sensor with PLC
Installation, Commissioning and Software Development
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged sluice valve of Class ASA-150 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make and any other make approved State Level Technical Committee JSV Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-150 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter)
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 100 mm dia(mtr)
Delivery pipe = 80 mm dia (mtrs) NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
KULBINDER SINGH GOVT CONTRACTOR
SS ENGINEERING WORKS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .