Central Kolkata Health Electrical Division P-12, C.I.T Road(1st floor) KOLKATA
Electrical work for Construction of Seven storied building for Institute of Neuroscience (with seven storied foundation), along with two storied Electrical Sub-station building, Kolkata-700 014 -- SITC of Fire Detection and Alarm System.
2026_WBPWD_991660_1
WBPWD/EE-I/CKHED/eNIT98/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
CENTRAL KOLKATA HEALTH ELECTRICAL DIVISION
Please refer Tender documents.
3 documents required · 3 mandatory
₹1.1 L
Central Kolkata Health Electrical Division
20 Jan 2026
20 Jan 2026
13 Feb 2026
20 Jan 2026
11 Feb 2026
28 Jan 2026
20 Jan 2026
SITC of Microprocessor based Intelligent, addressable fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable having requisite numbers of loop with 20% spare capacity with each loop capable of taking requisite number of devices as per latest IS/NBC, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software.
SITC of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost).
SITC of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost).
SITC of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required.
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved.
SITC of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required.
SITC of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required.
SITC of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc.
SITC of Repeater Panel ( VDS / UL / FM / ULC approved) which will act as an add-on device for remote display of FACP status information of the FDA operating front related to the detectors and decetors zones.Event messages are displayed via LED collective indicators and on the 2-Line LCD display with the associated detecors zone number and a programmable additional text. Each message is signalled via the built-in buzzer. The buzzer can be acknowledged by pressing a button. The requisite LCD indicator panel can be operated on as RS 485 bus.
SITC of Power supply 230 V AC to 24V DC with all other accessories.
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) with 20 mm NB PVC rigid conduit pipe on the surface of the wall.
Submission of 3 copy comprehensive Floor-wise Single Line Diagram (SLD) and Quantified List of the installed fire alarm system components upon completion of the commissioning proces. This documentation will mention the block/room names, specific locations of detectors, Manual Call Points (MCP), hooters, and the associated cable path lines. Autocad Soft Copies in .dwg format as well as printed hard copies of the SLD and List will be provided within three days of the commissioning date, ensuring timely and accurate documentation for all relevant as directed by EIC.
TERMS & CONDITIONS
a.The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
b. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
c. Auto CAD Drawing of whole FDA system & submission of 5 set hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
d. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
e. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. as applicable)
Defect Liability period : 1 year
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.20 MB
2911.pdf
Tender Documents • 0.50 MB
BOQ_2424614.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .