Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹70.6 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹71.3 L+₹70,012.30 (0.99%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹74.3 L+₹3.7 L (5.30%)Rejected-Finance HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD PIN 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹76.0 L+₹5.4 L (7.71%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹77.3 L+₹6.7 L (9.48%)Rejected-Finance 10 RAJAN KUNJ ROORKEE ROAD MEERUT 250001 | MEERUT | UTTAR PRADESH | 250001 | L5 | Rejected-Finance Not Lowest |
Tender Value
₹94.9 L
EMD Value
₹1.7 L
Closing Date
16 Aug 2021, 6:00 pmClosed
CWE (AF) Bareilly
CWE (AF) Bareilly
PROVN OF DG SETS AGAINST BER AT AF STATION BAREILLY
2021_MES_461216_1
81266/E8
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
Bareilly
As per NIT
8 documents required · 8 mandatory
₹1,000
GE (AF) Bareilly
₹1.7 L
Yes
10 Sept 2021
20 Jul 2021
18 Aug 2021
20 Jul 2021
16 Aug 2021
11 Aug 2021
20 Jul 2021 - 4 Aug 2021
Amount
M&L for taking down of existing BER DG Sets of various capacity and disconnecting of cable of any type and any size from panel to DG Set and to be deposited in the E/M store of GE AF Bareilly complete all as specified and directed.
Supply, installation, testing and commissioning of factory assembled 200 KVA silent diesel engine driven generating Set specially designed to meet stringent noise pressure level of 75 dB (A) at a distance of 1 meter from the enclosure as per CPCB norms under free field conditions , with Micro- processor based Gen Set controllers display a host of Genset parameters and controls , fuel tank of suitable capacity (capacity shall not be less than 10 Hrs consumption),, designed to have optimum serviceability, air inlet louvers specially designed to operate at rated load, powder coated for long lasting service life and superior finish , use of special hardware for longer life, insulation material as per IS 8183, specifications for better sound attenuation, flush styling- no projections, Fluid drains for lube oil and fuel, fuel filling point etc. PCC foundation as per manufacturers drawings complete all as specified and comprising the following :-
(A) Prime Mover: Prime mover (Diesel Engine) suitable for driving 200 KVA capacity alternator, 3 phase 4 wire of 415 V, 50 Hz comprising of water cooled, direct injection, turbo charged, four stroke confirming to BS -5514 rated for continuous running capable of taking 10% over load for any one hour in 12 hours running complete with Engine control panel and including following accessories :- (i) Heavy flywheel and flywheel housing complete with starting gear ring and to suitable coupling duly covered with gaurd. (ii) Air cleaner dry type. (iii) Fan and water pump assembly. (iv) Mechanical FIP. (v) Electronic Governor. (vi) Starting motor - Electric battery charging alternator (v) Maintenance free batteries 12 Volt (vii) 01 set Anti vibration pad.( viii) first filled lubricating oil and coolent Make : Cummins/Greaves Cotton/ Kirloskar Oil Engines Ltd/Cater Pillar
(B) Alternator :- Alternater suitable for 200 KVA continious operation at 1500 RPM, 415 volt, 0.8 PF (lag) suitable for 50 Hz, 3 phase, 4 wire system, confirming to IS 4722. The alternator is brushless type, self excited, self regulated, Salient pole revolving field . The alternator has the following features :- (a) +1.0% voltage regulation (max) in static conditions. (b) IP 23 protection (c) class H insulation limited to temperature rise of class H (d) Permissible overload of 10% for one hour in 12 hour of operation. Make: Stamford/ Cromption Greaves/ KOEL
(C) Control & Metering Circuit :- The control panel is manufactured with 1.6 mm CRCA sheet & is podwer coated for a weather proof & longlasting finish. the control panel consists of the following parts :- (i) Microprocessor based Genset controller with AMF feature, Monitoring features Phase Voltages ,Currents, Frequency , reverse power , Genset KVA , KW , Kwh, KVAr, PF, Canopy temperature , RPM , Run houres , lube oil pressure , Engine Temperature , Number of starts , fuel level , Auto/ manual stop , Battery charge condition , and diagnostic feature as battery charging failure,over/under voltage, over current , Mains under voltage , Earth fault trip, Fuel usage alarm etc all as specified and directed. Note : Silent DG Set will be factory assembled of reputed manufacture : Sudhir Power/ M/s KOEL / M/s Jackson/ M/s Geaves Power.
(D) AMF Panel : Supply, installation, testing and commissioning for microprocessor based factory fabricated AMF control panel indoor type system suitable for 200 KVA DG set with and including internal wiring, free standing, floor mounted type, vertical type, front operated, dust & vermin proof fabricated out of 14 SWG MS CRCA sheet duly undergoing with pretreatment covering degreesing water rinsing, derusting/phosphating, After pre treating sheet metal shall be sprayed with high corrison resistance primer and finally epoxy polyester podwer coating of flint grey shade. The panel consisting the following :-
(i) Aluminium bus bars TPN 500Amp with SMC/DMC support (ii) MCB for protection of control system (iii) Digital Multifunctional energy meter , 96 mm x 96mm digital type with CT s ---- 01 Set . (iv) lamp indicator set of three(LED type) ----- 01 No. (v) Battery charging indicator lamp ----- 01 No. (vi) Auto / Manual /Test switch ------- 01 No. (vii) Battery charging Amp meter and volt meter digital type ------ 01 No. (viii) MCCB, 04 pole with capacity 320 Amp ICU 36 KA for 415 volt , Micro processor based release for overload and short circuit protection three phase AC supply ------ 02 Nos Make: Legrand / Siemens/ ABB. (ix) Uder/over voltage relay suitable for 3 phase 415 volt AC Supply - (x) Electronic timer (xi) Battery charger . (xii) Bypass arramgement with rotary type bypass change over switch of capacity 320 Amp AC on load to isolate the AMF panel at the time of low voltage. Make: Legrand/ Siemens/Schinder /L&T . (xiii) Four pole power contactor with standard coil voltage of 415 volt 50 Hz and auxiliary contact having AC three phase rating 320 Amp. Make : Siemens/ Schinder/ Legrand ------- 02 No. Note :- Cost of control wiring from AMF panel to DG set control panel deemed to be included in unit rate Make : M/s Sudhir Power/ M/s KOEL / M/s Greaves Power/ C&S / BCH
(E) Civil Works : As per manufacturer,s instruction (quated rates are deemed to be included in the item rates). All type of civil work like fundation, base plate with anti-vibration pad of Make: Dunlop or equivalent ISI marked for engine and alternator and shock vibration absorption material including PCC plateform ( 1:2:4) type B-1 using 20 mm graded aggregate and brick work in CM 1:4 all around the foundation including finishes for resting of DG set and sound proof enclosures. complete all as specified and directed. Note : Silent DG Set will be factory assembled of reputed manufacture : Sudhir Power, M/s KOEL, M/s Jackson, M/s Geaves Power
Supply, installation, testing and commissioning of factory assembled 100 KVA silent diesel engine driven generating Set specially designed to meet stringent of 75 dB (A) at a distance of 1 meter from the enclosure as per CPCB norms under free field conditions , with Micro- processor based Gen Set controllers display a host of Genset parameters and controls , fuel tank of suitable capacity (capacity shall not be less than 10 Hrs consumption),, designed to have optimum serviceability, air inlet louvers specially designed to operate at rated load, powder coated for long lasting service life and superior finish , use of special hardware for longer life, insulation material as per IS 8183, specifications for better sound attenuation, flush styling- no projections, Fluid drains for lube oil and fuel, fuel filling point etc. PCC foundation as per manufacturers drawings complete all as specified and comprising the following :-
(A) Prime Mover: Prime mover (Diesel Engine) suitable for driving 100 KVA capacity alternator, 3 phase 4 wire of 415 V, 50 Hz comprising of water cooled, direct injection, turbo charged, four stroke confirming to BS -5514 rated for continuous running capable of taking 10% over load for any one hour in 12 hours running complete with Engine control panel and including following accessories :- (i) Heavy flywheel and flywheel housing complete with starting gear ring and to suitable coupling duly covered with gaurd. (ii) Air cleaner dry type. (iii) Fan and water pump assembly. (iv) Mechanical FIP. (v) Electronic Governor. (vi) Starting motor - Electric battery charging alternator (v) Maintenance free battery 12 Volt (vii) 01 set Anti vibration pad.( viii) first filled lubricating oil and coolent Make : Cummins/Greaves Cotton/ Kirloskar Oil Engines Ltd
(B) Alternator :- Alternater suitable for 100 KVA continious operation at 1500 RPM, 415 volt,0.8 PF (lag) suitable for 50 Hz, 3 phase, 4 wire system, confirming to IS 4722. The alternator is brushless type,, self excited, self regulated, Salient pole revolving field . The alternator has the following features :- (a) +1.0% voltage regulation (max) in static conditions. (b) IP 23 protection (c) class H insulation limited to temperature rise of class H (d) Permissible overload of 10% for one hour in 12 hour of operation. Make: Stamford/ Cromption Greaves/ KOEL
(C) Control & Metering Circuit :- The control panel is manufactured with 1.6 mm CRCA sheet & is podwer coated for a weather proof & longlasting finish. the control panel consists of the following parts :- (i) Microprocessor based Genset controller with AMF feature, Monitoring features Phase Voltages ,Currents, Frequency , reverse power , Genset KVA , KW , Kwh, KVAr, PF, Canopy temperature , RPM , Run houres , lube oil pressure , Engine Temperature , Number of starts , fuel level , Auto/ manual stop , Battery charge condition , and diagnostic feature as battery charging failure,over/under voltage, over current , Mains under voltage , Earth fault trip, Fuel usage alarm etc all complete all as specified and directed.
(D) AMF Panel : Supply, installation, testing and commissioning for microprocessor based factory fabricated AMF control panel indoor type system suitable for 100 KVA DG set with and including internal wiring, free standing, floor mounted type, vertical type, front operated, dust & vermin proof fabricated out of 14 SWG MS CRCA sheet duly undergoing with pretreatment covering degreesing water rinsing, derusting/phosphating, After pre treating sheet metal shall be sprayed with high corrison resistance primer and finally epoxy polyester podwer coating of flint grey shade. The panel consisting the following :-
(i) Aluminium bus bars TPN 320AMP with SMC/DMC support (ii) MCB for protection of controlsystem (iii) Digital Multifunctional energy meter , 96 mm x 96mm digital type with CT s - 01 Set .(iv) lamp indicator set of three(LED type) - 01 No. (v) Battery charging indicator lamp - 01 No. (vi) Auto/ Manual/Test switch - 01 No. (vii) Battery charging Amp meter and volt meter digital type - 01 No. (viii) MCCB, 04 pole with capacity 160 amp ICU 36 KA for 415 volt,Micro processor based release for overload and short circuit protection three phase AC supply - 02 Nos Make: Legrand/ Siemens/ ABB. (ix) Under/over voltage relay suitable for 3 phase 415 volt AC Supply - . (x) Electronic timer type (xi) Battery charger . (xii) Bypass arramgement with rotary type bypass change over switch of capacity 160 Amp AC on load to isolate the AMF panel at the time of low voltage. Make: Legrand/ Siemens/ Schinder /L&T . (xiii) Four pole power contactor with standard coil voltage of 415 volt 50 Hz and auxiliary contact having AC three phase rating 160Amp. Make : Siemens/ Schinder/ Legrand - 02 No. Note :- Cost of control wiring from AMF panel to DG set control panel deemed to be included in unit rate Make : M/S Sudhir Power / M/s KOEL/ M/s Greaves Power/ C&S / BCH
(E) Civil Works : As per manufacturer,s instruction (quated rates are deemed to be included in the item rates). All type of civil work like fundation, base plate with anti-vibration pad of make: Dunlop or equivalent ISI marked for engine and alternator and shock vibration absorption material including PCC plateform ( 1:2:4) type B-1 using 20 mm graded aggregate and brick work in CM 1:4 all around the foundation including finishes for resting of DG set and sound proof enclosures. complete all as specified and directed. Note : Silent DG Set will be factory assembled of reputed manufacture : Sudhir Power, M/s KOEL, M/s Jackson, M/s Geaves Power
Supply, installation, testing and commissioning of factory assembled 62.5 KVA silent diesel engine driven generating Set specially designed to meet stringent of 75 dB (A) at a distance of 1 meter from the enclosure as per CPCB norms under free field conditions , with Micro- processor based Gen Set controllers display a host of Genset parameters and controls , fuel tank of suitable capacity (capacity shall not be less than 10 Hrs consumption),, designed to have optimum serviceability, air inlet louvers specially designed to operate at rated load, powder coated for long lasting service life and superior finish , use of special hardware for longer life, insulation material as per IS 8183, specifications for better sound attenuation, flush styling- no projections, Fluid drains for lube oil and fuel, fuel filling point etc. PCC foundation as per manufacturers drawings complete all as specified and comprising the following :-
(A) Prime Mover: Prime mover (Diesel Engine) suitable for driving 62.5 KVA capacity alternator, 3 phase 4 wire of 415 V, 50 Hz comprising of water cooled, direct injection, turbo charged, four stroke confirming to BS -5514 rated for continuous running capable of taking 10% over load for any one hour in 12 hours running complete with Engine control panel and including following accessories :- (i) Heavy flywheel and flywheel housing complete with starting gear ring and to suitable coupling duly covered with gaurd. (ii) Air cleaner dry type. (iii) Fan and water pump assembly. (iv) Mechanical FIP. (v) Electronic Governor. (vi) Starting motor - Electric battery charging alternator (v) Maintenance free battery 12 Volt (vii) 01 set Anti vibration pad.( viii) first filled lubricating oil and coolent Make : Cummins/Greaves Cotton/ Kirloskar Oil Engines Ltd
(B) Alternator :- Alternater suitable for 62.5 KVA continious operation at 1500 RPM, 415 volt,0.8 PF (lag) suitable for 50 Hz, 3 phase, 4 wire system, confirming to IS 4722. The alternator is brushless type,, self excited, self regulated, Salient pole revolving field . The alternator has the following features :- (a) +1.0% voltage regulation (max) in static conditions. (b) IP 23 protection (c) class H insulation limited to temperature rise of class H (d) Permissible overload of 10% for one hour in 12 hour of operation. Make: Stamford/ Cromption Greaves/ KOEL
(C) Control & Metering Circuit :- The control panel is manufactured with 1.6 mm CRCA sheet & is podwer coated for a weather proof & longlasting finish. the control panel consists of the following parts :- (i) Microprocessor based Genset controller with AMF feature, Monitoring features Phase Voltages ,Currents, Frequency , reverse power , Genset KVA , KW , Kwh, KVAr, PF, Canopy temperature , RPM , Run houres , lube oil pressure , Engine Temperature , Number of starts , fuel level , Auto/ manual stop , Battery charge condition , and diagnostic feature as battery charging failure,over/under voltage, over current , Mains under voltage , Earth fault trip, Fuel usage alarm etc all complete all as specified and directed.
(D) AMF Panel : Supply, istallation, testing and commissioning for microprocessor based factory fabricated AMF control panel indoor type system suitable for 62.5 KVA DG set with and including internal wiring, free standing, floor mounted type, vertical type, front operated, dust & vermin proof fabricated out of 14 SWG MS CRCA sheet duly undergoing with pretreatment covering degreesing water rinsing, derusting/phosphating, After pre treating sheet metal shall be sprayed with high corrison resistance primer and finally epoxy polyester podwer coating of flint grey shade. The panel consisting the following :-
(i) Aluminium bus bars TPN of Rating 200 Amp with SMC/DMC support (ii) MCB for protection of controlsystem . (iii) Digital Multifunctional energy meter , 96 mm x 96mm digital type with CT s - 01 Set . (iv) lamp indicator set of three(LED type) --- 01 No. (v) Battery charging indicator lamp --- 01 No. (vi) Auto/ Manual/Test switch --- 01 No. (vii) Battery charging Amp meter and volt meter digital type --- 01 No. (viii) MCCB, 04 pole with capacity 100 amp ICU 36 KA for 415 volt,Micro processor based release for overload and short circuit protection three phase AC supply --- 02 Nos Make: Legrand/ Siemens/ ABB. (ix) Uder/over voltage relay suitable for 3 phase 415 volt AC Supply - . (x) Electronic timer type (xi) Battery charger . (xii) Bypass arramgement with rotary type bypass change over switch of capacity 100 Amp AC on load to isolate the AMF panel at the time of low voltage. Make: Legrand/ Siemens/ Schinder /L&T . (xiii) Four pole power contactor with standard coil voltage of 415 volt 50 Hz and auxiliary contact having AC three phase rating 100Amp. Make : Siemens/ Schinder/ Legrand - 02 No. --- 01 No. Note :- Cost of control wiring from AMF panel to DG set control panel deemed to be included in unit rate . Make : M/S Sudhir Power / M/s KOEL / M/s Greaves Power / C&S / BCH.
(E) Civil Works : As per manufacturer,s instruction (quated rates are deemed to be included in the item rates). All type of civil work like fundation, base plate with anti-vibration pad of make: Dunlop or equivalent ISI marked for engine and alternator and shock vibration absorption material including PCC plateform ( 1:2:4) type B-1 using 20 mm graded aggregate and brick work in CM 1:4 all around the foundation including finishes for resting of DG set and sound proof enclosures. complete all as specified and directed. Note : Silent DG Set will be factory assembled of reputed manufacture : Sudhir Power, M/s KOEL, M/s Jackson, M/s Geaves Power.
Supply, installation, testing and commissioning of factory assembled 30 KVA silent diesel engine driven generating Set specially designed to meet stringent of 75 dB (A) at a distance of 1 meter from the enclosure as per CPCB norms under free field conditions , with Micro- processor based Gen Set controllers display a host of Genset parameters and controls , fuel tank of suitable capacity (capacity shall not be less than 10 Hrs consumption),, designed to have optimum serviceability, air inlet louvers specially designed to operate at rated load, powder coated for long lasting service life and superior finish , use of special hardware for longer life, insulation material as per IS 8183, specifications for better sound attenuation, flush styling- no projections, Fluid drains for lube oil and fuel, fuel filling point etc. PCC foundation as per manufacturers drawings complete all as specified and comprising the following :-
(A) Prime Mover: Prime mover (Diesel Engine) suitable for driving 30KVA capacity alternator, 3 phase 4 wire of 415 V, 50 Hz comprising of water cooled, direct injection, turbo charged, four stroke confirming to BS -5514 rated for continuous running capable of taking 10% over load for any one hour in 12 hours running complete with Engine control panel and including following accessories :- (i) Heavy flywheel and flywheel housing complete with starting gear ring and to suitable coupling duly covered with gaurd. (ii) Air cleaner dry type. (iii) Fan and water pump assembly. (iv) Mechanical FIP. (v) Electronic Governor. (vi) Starting motor - Electric battery charging alternator (v) Maintenance free battery 12 Volt (vii) 01 set Anti vibration pad.( viii) first filled lubricating oil and coolent Make : Cummins/Greaves Cotton/ Kirloskar Oil Engines Ltd
(B) Alternator :- Alternater suitable for 30 KVA continious operation at 1500 RPM, 415 volt,0.8 PF (lag) suitable for 50 Hz, 3 phase, 4 wire system, confirming to IS 4722. The alternator is brushless type,, self excited, self regulated, Salient pole revolving field . The alternator has the following features :- (a) +1.0% voltage regulation (max) in static conditions. (b) IP 23 protection (c) class H insulation limited to temperature rise of class H (d) Permissible overload of 10% for one hour in 12 hour of operation. Make: Stamford/ Cromption Greaves/ KOEL
(C) Control & Metering Circuit :- The control panel is manufactured with 1.6 mm CRCA sheet & is podwer coated for a weather proof & longlasting finish. the control panel consists of the following parts :- (i) Microprocessor based Genset controller with AMF feature, Monitoring features Phase Voltages ,Currents, Frequency , reverse power , Genset KVA , KW , Kwh, KVAr, PF, Canopy temperature , RPM , Run houres , lube oil pressure , Engine Temperature , Number of starts , fuel level , Auto/ manual stop , Battery charge condition , and diagnostic feature as battery charging failure,over/under voltage, over current , Mains under voltage , Earth fault trip, Fuel usage alarm etc all as specified and directed. .
(D) AMF Panel : Supply, istallation, testing and commissioning for microprocessor based factory fabricated AMF control panel indoor type system suitable for 30 KVA DG set with and including internal wiring, free standing, floor mounted type, vertical type, front operated, dust & vermin proof fabricated out of 14 SWG MS CRCA sheet duly undergoing with pretreatment covering degreesing water rinsing, derusting/phosphating, After pre treating sheet metal shall be sprayed with high corrison resistance primer and finally epoxy polyester podwer coating of flint grey shade. The panel consisting the following :-
(i) Aluminium bus bars of TPN 100Amp with SMC/DMC support (ii) MCB for protection of controlsystem . (iii) Digital Multifunctional energy meter , 96 mm x 96mm digital type with CT s ----- 01 Set .(iv) lamp indicator set of three(LED type) ----- 01 No. (v) Battery charging indicator lamp ----- 01 No. (vi) Auto/ Manual/Test switch ------ 01 No. (vii) Battery charging Amp meter and volt meter digital type ----- 01 No. (viii) MCCB, 04 pole with capacity 63 amp ICU 36 KA for 415 volt,Micro processor based release for overload and short circuit protection three phase AC supply ------ 02 Nos Make: Legrand/ Siemens/ ABB. (ix) Under/over voltage relay suitable for 3 phase 415 volt AC Supply (x) Electronic timer type (xi) Battery charger . (xii) Bypass arrangement with rotary type bypass change over switch of capacity 63 Amp AC on load to isolate the AMF panel at the time of low voltage. Make: Legrand/ Siemens/ Schinder /L&T . (xiii) Four pole power contactor with standard coil voltage of 415 volt 50 Hz and auxiliary contact having AC three phase rating 63Amp. Make : Siemens/ Schinder/ Legrand - 02 No. -- 01 No. Note :- Cost of control wiring from AMF panel to DG set control panel deemed to be included in unit rate Make : M/S Sudhir Power / M/s KOEL / M/s Greaves Power / C&S / BCH
(E) Civil Works : As per manufacturer,s instruction (quated rates are deemed to be included in the item rates). All type of civil work like fundation, base plate with anti-vibration pad of make: Dunlop or equivalent ISI marked for engine and alternator and shock vibration absorption material including PCC plateform ( 1:2:4) type B-1 using 20 mm graded aggregate and brick work in CM 1:4 all around the foundation including finishes for resting of DG set and sound proof enclosures. complete all as specified and directed. Note : Silent DG Set will be factory assembled of reputed manufacture : Sudhir Power, M/s KOEL, M/s Jackson, M/s Geaves Power.
Supply, laying, jointed and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core, laid in trenches/ drawn through pipe/ poles or laid under road / drains / path complete all as specified and directed.
Supply, laying, jointed and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core, laid in trenches/ drawn through pipe/ poles or laid under road / drains / path complete all as specified and directed.
Supply, laying, jointed and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core, laid in trenches/ drawn through pipe/ poles or laid under road / drains / path complete all as specified and directed.
Supply, laying, jointed and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4.0 core, laid in trenches/ drawn through pipe/ poles or laid under road / drains / path complete all as specified and directed.
M & L for laying of course sand free from sharp materials as in filling in trenches for cable protection, laid to a uniform thickness of 23 cm (15 cm under the cable and 8 cm over the cable) and gently punned down to 18 cm thickness as required complete all as specified and directed.
M&L for sub class 'B' old size brick for covering to under ground cable laid dry flat transversally width equal to the length of the cable all as specified and directed.
Excavation in trenches (manually) not exc. 1.50 m wide and not exc. 1.50 m in depth for laying cables or foundation of electric pole / Stay assembly and getting out in soft / loose soil including trimming sides and forming bottom surface to the required level / slope etc complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm in each layer as in soil complete all as specified and directed.
Removal of excavated soil to a distance not exceeding 50 Mtr depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed.
Horizontal boring under Road, pavement, hard standing complete for inserting GI pipe light grade of size 50/80mm dia all as specified and directed. Note :- GI pipe shall be measured and paid seperately
M & L for 80mm dia of Tubes light grade galvanised with all fitting laid in trenches or inserting in horizontal boring complete all as specified and as directed.
Design, supply, erection, testing and commissioning of outdoor type LT Feeder Pillar of overall size not less than 1200 mm (width) X 1000 mm (height) (Without Canopy & Base Channel) x 400mm Depth, M.S. Channel Base Frame mounted (to be mounted on the 3 side covered brick. pedestal of height 450 mm above ground level) , suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bars of rating 600 amps insulated , the Feeder Pillar shall be duly fabricated in a approved fabrication house who posseses type test certificate from CPRI for similar type of Feeder Pillar and having modern fabrication and testing facility which includes atleast seven (07) tanks pre-treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032 (SIEMENS GRAY). The Feeder Pillar shall be provided with suitable rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-54 and general construction conforming to IS : 13947. The feeder pillar shall be made out of 3.15mm thick CRCA mild steel sheet and 3.15mm thick gland plate and having compartmentalized construction for individual switchgears and Bus Bars and having front opening facility (with double layer shutter) and rear opening facility with single layer shutter with locking facility and 2 side slanting canopy type roof on top and mild steel channel (MC-75) base frame at bottom, suitable for mounting on the brick pedestal through grouting bolt, The panel board shall be provided with ventilation facility in the form of louvers for better heat dissipation. The feeder pillar shall be comprising of the followings :-
PROVISION FOR CABLE ENTRY :- The provision for cable entry / exit shall be provided from the bottom for both incoming and outgoing cables through and including cable gland made of Brass CONTROL WIRING :- All control wirings shall have to be carried out with 1100 volts rated FRLS grade PVC insulated (Gray Colour) multi-flexible type copper wire of cross sectional area 1.50 Sq mm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size & type of tinned copper lugs and shall be wrapped with PVC spring type flexible pipes near the door hinges.
INCOMING :- (i) Supply and fix MCCB 320 Amp with 4 Pole,36KA with microprpcesor based release for O/l , Short circuit - 01 No. OUTGOING :- (i) Supply and Fix MCCB 125 Amp 25 KA, 4 Pole Thermal magnetic release with adjustable O/L and S/C - 01 No. (ii) Supply and Fix MCCB 80 Amp 25 KA, 4 Pole Thermal magnetic release with adjustable O/L and S/C - 04 No. Make of switchgear : Siemens / legrand / ABB
MISCELLANEOUS ITEMS :- (a) SP MCB 6 Amps 10 KA (For Control Wiring) - 01 No. Make : LEGRAND /SCHNEIDER / ABB INSTRUMENTATION SYSTEM :- LED Phase Indicating light, shrouded type, 22mm, with cluster LED - 01 set of 3 lamps (RED,YELLOW & BLUE) Digital Multifunction meter with C.T having Ratio 500/5, resin cast,- 01 No. Make : L&T / AE/ CONZERV / ELMEASURE Note :- Cost of disconnecting existing panel deemed to be included in unit rate : (ii) Existing panel retrieved to be taken on charge .
Design, supply, erection, testing and commissioning of outdoor type LT Feeder Pillar of overall size not less than 1200 mm (width) X 1000 mm (height) (Without Canopy & Base Channel) x 400mm Depth, M.S. Channel Base Frame mounted (to be mounted on the 3 side covered brick. pedestal of height 900 mm above ground level) , suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bars of rating 400 amps insulated , Provision of Spreader link to both incoming and outgoing side of MCCBs for termination of cables the Feeder Pillar shall be duly fabricated in a approved fabrication house who posseses type test certificate from CPRI for similar type of Feeder Pillar and having modern fabrication and testing facility which includes atleast seven (07) tanks pre-treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032 (SIEMENS GRAY). The Feeder Pillar shall be provided with suitable rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-54 and general construction conforming to IS : 13947. The feeder pillar shall be made out of 3.15mm thick CRCA mild steel sheet and 3.15mm thick gland plate and having compartmentalized construction for individual switchgears and Bus Bars and having front opening facility (with double layer shutter) and rear opening facility with single layer shutter with locking facility and 2 side slanting canopy type roof on top and mild steel channel (MC-75) base frame at bottom, suitable for mounting on the brick pedestal through grouting bolt, The panel board shall be provided with ventilation facility in the form of louvers for better heat dissipation. The feeder pillar shall be comprising of the followings :-
PROVISION FOR CABLE ENTRY :- The provision for cable entry / exit shall be provided from the bottom for both incoming and outgoing cables through and including cable gland made of Brass CONTROL WIRING :- All control wirings shall have to be carried out with 1100 volts rated FRLS grade PVC insulated (Gray Colour) multi-flexible type copper wire of cross sectional area 1.50 Sq mm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size & type of tinned copper lugs and shall be wrapped with PVC spring type flexible pipes near the door hinges.
INCOMING :- (i) Supply and fix MCCB 160 Amp with 4 Pole,36KA with microprpcesor based release for O/l , Short circuit - 01 No. OUTGOING :- (i) Supply and Fix MCCB 80 Amps 25 KA, 4 Pole Thermal magnetic release with adjustable O/L and S/C - 02 No. Make of switchgear : Siemens / legrand / ABB
MISCELLANEOUS ITEMS :- (a) SP MCB 6 Amps 10 KA (For Control Wiring) - 01 No. Make : LEGRAND /SCHNEIDER / ABB INSTRUMENTATION SYSTEM :- LED Phase Indicating light, shrouded type, 22mm, with cluster LED --- 01 set of 3 lamps (RED,YELLOW & BLUE) Digital Multifunction meter with C.T having Ratio 200/5, resin cast ---- 01 No. Make : L&T / AE/ CONZERV / ELMEASURE Note :- Cost of disconnecting existing panel deemed to be included in unit rate : (ii) Existing panel retrieved to be taken on charge .
M&L for Earthing complete with Copper earth plate electrode 600 x 600 x 3.0mm buried directly in ground (earth pit not less than 2.25 deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to copper earth lead by means of copper earth strip of 25X3 mm , by means of copper/brass bolts, nuts, check nuts and washers, and connected to equipments as directed, including funnel with GI med grade watering pipe 20mm bore, wire mesh, charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with concrete pit in PCC 1:3:6 type C1, 50 mm thick pre-cast RCC 1:2:4 type B-1 cover slab reinforced with 8mm dia deformed bar 15 cm C/C and suitable handle of 10mm dia round bar, GI medium grade pipe for earth lead protection including necessary excavation earth work in soft/ loose soil and disposal of soil to a distance n.exec 50 m and necessary testing complete all as shown on electrical plate no 3 of MES SSR Part-I 2009 and connected to earth test point including testing complete all as specified and directed. Note: (i) Cost of Earthing lead/strip and protection pipe upto 7.5 m shall be included in cost of above item. (ii) Rate of earth work for earthing shall be deemed to be included in the rate quoted.
Vijaypower Generators Limited
national engineering
BRITE INDUSTRIES
SA construction co.
Leo Air and Power Solution pvt Ltd.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .