| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.9 LAccepted-AOC BAID COMPLEX R K CHOUDHURY ROAD KUMAR PARA GUWAHATI 781001 ASSAM | GUWAHATI | KAMRUP METRO | ASSAM | 781001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹39.9 L+₹3,687.20 (0.09%)Rejected-AOC AZARA BHARALIPARA NEAR AZARA PUBLIC HALL GUWAHATI 781017 ASSAM | KAMRUP METRO | ASSAM | 781017 | L2 | Rejected-AOC L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Due to non-enlistment in requisite category. | |
| 4 | Rejected-Technical | - | Rejected-Technical Due to non-enlistment in requisite category. |
Tender Value
Refer Docs
EMD Value
₹75,800
Closing Date
31 Aug 2022, 6:00 pmClosed
CWE (AF) Borjhar
HQ CWE (AF) Borjhar, Military Engineer Services, PO - Borjhar Airport, Guwahati (Assam) - 781015 Tele 0361 2841626
PROVN OF 140 KVA COMMERCIAL POWER SUPPLY AND PARKING SHED FOR SPECIALIST VEHICLE AT KUMBHIRGRAM (4th CALL)
2022_MES_521202_4
CWE(AF)/KUM/TOKEN-64 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Kumbhirgram
Please refer tender documents
8 documents required · 8 mandatory
₹500
Yes
AGE (I) (AF) Kumbhirgram
₹75,800
Yes
14 Oct 2022
11 Aug 2022
2 Sept 2022
11 Aug 2022
31 Aug 2022
18 Aug 2022
Amount
SCHEDULE 'A' PART - I: Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out in hard soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, complete all as specified and as directed.
PCC (1:3:6) type C-2 (using 40mm graded stone aggregates) as in foundations, fillings and mass concrete complete all as specified and as directed.
Rolled mild steel channel, angle, or tee sections, fixed independently as in post, without connecting plates, etc. including notching, drilling for holes, fitting, riveting and/or welding or connecting with bolts and nuts conforming to Fe - 410W (Gde E-250) complete all as specified and as directed.
Rolled mild steel channel, angle, or tee sections, fixed independently as in main beam and fixed with angle cleats or connecting plates etc. including notching, drilling for holes, fitting, riveting and/or welding or connecting with bolts and nuts conforming to Fe - 410W (Gde E-250) complete all as specified and as directed.
Rolled mild steel angle section of size 65x65x6mm as in Roof trusses (framed), trussed, purlins, including distance pieces, cleats etc.in post, without connecting plates, etc. including notching, drilling for holes, fitting, riveting and/or welding or connecting with bolts and nuts conforming to Fe - 290 (Gde E-165) complete all as specified and as directed.
Rolled mild steel plates (plain or chequered) as in gusset plates cut or notched (ordinary and counter sunk) forming holes, without any attachment conforming to Fe - 410W (Gde E-250) complete all as specified and as directed.
M&L for pre-painted galvalume aluminium zinc coating GI based plain steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screws, complete all as specified and directed.
M&L for pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screws, complete all as specified and directed.
Preparation of new steel surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
SCHEDULE 'A' PART-II : Materials and labour for flame proof point wiring with 1.50 sq.mm. HRFR, PVC insulated and sheathed multistranded copper conductor cable 1100 Volts grade, single core, drawn through and including stove enamelled steel conduit 20 mm dia (medium grade) complete with all fittings and accessories, fixed to walls/ceiling, including factory made sunk type mild steel terminal boxes 1.25 mm thick (wall thickness) conforming to IS-5133 (Part-I) with 3mm thick hylem sheet top cover for mounting switches/ sockets/regulator etc., including 1.50 sq.mm HRFR PVC insulated, sheathed multistranded copper conductor cable 1100 Volts grade, single core, green in colour for earth continuity conductor connected to common earth dolly for One light point/ One fan point/bell point controlled by one flame proof switch complete all as specified and directed.
Description as per item No 10 here-in before but for one flame proof 15 Amp socket outlet controlled by one flame proof switch complete on independent board complete all as specified and as directed.
Description as per item No 10 here-in before but for one one flame proof 5 Amp socket outlet controlled by one flame proof switch complete on independent board complete all as specified and as directed.
Switch piano flush type with terminal box single pole one way 5/6 amps, 230 V complete all as specified and as directed.
Socket outlet 2 in 1, 3 pin 5/6 Amp flush type complete all as specified and as directed.
Socket outlet 2 in 1, 3 pin 5 & 15 Amp flush type complete all as specified and as directed.
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
MCB DB , SPN 4 way, double door with 200 Amp rated bus bar, horizontal type IP-43 including earth and neutral link ,complete with fixing accessories all as specified and directed.
MCB SP 240 Volts, 'C' series, breaking capacity 10 KA of rating 6-32 Amps complete all as directed.
MCB SPN 240 Volts, 50 Hz, 'C' series Sp, breaking capacity 10 KA of rating 6-32 Amps complete all as specified and directed.
SCHEDULE 'A' PART-III : Supply and errect in true vertical position Steel tubular swaged poles 11 m long with GI base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.0 metres long) including internal surface painted with black bituminous paint & external surface painted with two coats of aluminium paint over one coat of red oxide primer from top of pole to 1.5 mtr above from top of PCC coping & from top of PCC coping to 1.5 mtr height portion of pole to be painted with black & white colour paint as in alternate strips complete all as specified and directed . (Note: Earth work and PCC foundation etc shall be measured and paid seperately under relevant item)
Supply, fixing and testing of lightning arrestors HT 11 KV grade, expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed.
Supply, install, connecting, testing and commissioning HT 11 KV outdoor gang operated air break switch, triple pole for current rating upto 200 Amps, mechanically operated, mounted on insulators and steel frame, with operating mechanism and operating rod made out of 25 mm bore GI pipe medium grade worked from ground level, with locking arrangement complete all as specified and directed.
Excavation in trenches in soft/loose soil etc n. exc 1.5 m wide and n.exc 1.5m in depth for foundation etc or for laying of pipe, cable etc and getting out complete all as specified and directed by Engineer-in-charge.
Description as per item No 23 here-in before exceeding 1.5m but not exceeding 3.00 metre in depth complete all as specified and as directed.
Returning, filling in soft/loose soil, including, spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed.
Removing excavated materials (soils) to a distance not exc 50 m and depositing where directed at a level not exc 1.50 m above the starting point, complete all as specified and as directed.
Material and Labour for dry sand cushioning with coarse sand in trenches for protection of underground electric cable 8cm deep before laying the cable and 15cm thick after laying & stretching of cable complete all as specified and as directed. (Note:- Only punned thickness of 18cm shall be measured and paid)
Supply and laying old size sub class 'B' bricks well burnt, best quality locally available, of size 230x115x75mm, laid flat with width equal to length of the brick in trenches over sand cushioning for UG cable protection complete all as specified and directed
M&L for horizontal boring across the existing road without disturbing the road surface for inserting 50 mm bore GI pipe, complete all as directed. Note: GI pipe shall be measured and paid for separately under respective item.
S&F 50 mm bore GI tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.
Description as per item No 30 here-in before but 80mm bore complete all as specified and as directed.
Supply, laying, jointing and testing of electric power cable, heavy duty 11KV (E) grade, XLPE insulated, screened, bedded, galvanised steel strip or wire armoured with aluminium conductor of cross sectional area of 95 sqmm, 3 core, laid in trenches/cable duct complete all as specified and directed.
Supply, jointing & testing cable jointing kit for 11KV (Earthed) grade cable, out door end termination heat shrinkable type joint with jointing material and accessories suitable for 95 Sqmm 3 Core, XLPE armoured aluminium conductor cable complete all as specified and directed.
Supply, jointing & testing cable jointing kit for 11KV (Earthed) grade cable, indoor end termination heat shrinkable type joint with jointing material and accessories suitable for 95 Sqmm 3 Core, XLPE armoured aluminium conductor cable complete all as specified and directed.
Supply, installation, testing and commissioning of outdoor type Transformer, capacity 160 KVA, double copper wound step down, conform to latest BIS Certification, HT 11 KV/0.433 KV, AC, 3 Phase, Oil immersed, C.R.GO Core type Naturally cooled built-up-with class-A insulation conforming to IS 1180 (Part-I) 2014 with latest ammendment and shall have energy efficient level-1 (3 Star rated) complete with standard fittings including all jointing materials, connecting with electrical system, earthing etc. including initial oil filling to appropriate level complete all as specified and directed. Note: 1. The Transformer shall be tested as routine test as per IS 2026:1977 in presence of AGE(I)/his rep. 2. The contractor shall submit Quality Assurance Programe within 15 days after placement of order for testing of Transformer at factory. Transformer shall be dispatch only after inspection clearance by inspecting officer as detailed by Accepting Officer. 3. The contractor/manufacturer shall furnish original MILL certificate (paid vouchers and test certificate) of the CRGO manufacturer. 4. The contractor/ manufacturer shall furnish the diameter of LV & HV copper winding and its total resistance. The stray losses shall be specified in percentage terms. The percentage of No load and Full load losses shall be as per IS 1180:2014 of Energy effieciency level 2. 5. The contractor shall get the approval of Accepting Officer for the make of the transformer. 6. Separate neutral bushing shall be brought out for earthing. 7. Necessery foundation shall be provided as per manufacturer's recommendation and quoted rate shall be deemed to be included accordingly. 8. Pre-commissioning test by EI/SEI will be carried out and all arrangement shall be done by the contractor at no extra cost.
Supply, laying, jointing and testing of XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured heavy duty aluminium conductor 1100 volt grade of cross sectional area 240 sqmm 3.5 core complete all as specified & directed. Note: Excavation, earth work, sand cushioning and covers shall be measured and paid separately.
Description as per item No 36 here-in before but cross sectional area 120 sqmm 3.5 core complete all as specified and as directed.
Description as per item No 36 here-in before but cross sectional area 50 sqmm 3.5 core complete all as specified and as directed.
Description as per item No 36 here-in before but cross sectional area 35 sqmm 3.5 core complete all as specified and as directed.
Description as per item No 36 here-in before but cross sectional area 25 sqmm 4 core complete all as specified and as directed.
Description as per item No 36 here-in before but cross sectional area 10 sqmm 2 core complete all as specified and as directed.
Material and Labour for mild steel cross arms, bracing, supports, clamps and back plates fabricated from structural steel section conforming to Fe - 290 (Gde E-165) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape/size as directed including painting with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer complete all as specified and as directed.
Material and Labour for PCC (1:2:4) type B2 (using 40 mm graded crushed stone aggregates) as in foundation, coping etc including necessary formwork complete all as specified and as directed.
Supply, installation, testing and commissioning of Servo controlled voltage stabilizer 150 KVA (Conforming to BIS 9815: Part-I : 1994) Three phase, Naturally oil cooled, indoor, Unbalanced Type, Copper wound, metalic body duly powder coated with 04 Nos lifting hook, digital display type, relay free smooth and silent operation with first filling of oil (ISI marked)up to required level of following specification: (a) Input vvoltage 360V to 480V (b) Output voltage stabilized at any designed/desired voltage 415V with accuracy of +/- 1% (c) Rated Frequency 50Hz (d) No Distortion in wave form (e) Response time not to exceed 20 mille second (f) Sensitivity +/- 1% (g) Rate of correctio 8 V/sec for single phase and 13 V/sec for phase to phase (h) Efficiency more than 95% (i) Type of load: Three phase unbalanced type (j) Digital display Voltmeter & Ammeter.
Supply installation, commissioning and testing LT Feeder Pillar Box of minimum size 1200 mm (height) x 1000mm (breadth) x 600mm (depth) factory made CPRI approved panel, weather, dust & vermin proof outdoor cubical compartmental type double door in front and single door in back side openable with providing rubber/PVC gasket of suitable size all sides of door with proper locking arrangement, made out of 3.15 mm thick mild steel CRCA sheet with 50 x 50 x 6mm size angle iron supporting, surfaces treated with coats of Poweder coated paint over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete connections of all outgoing/incomming existing cable of any size including100mm thick PCC (1:3:6) type C2 foundation of size as required and plastering the same in cement mortar 1:6 finished even and smooth without using extra cement complete all as specified and as directed comprising of the following fitment accessories:- (a) Busbar: 400 Amps rated copper busbar TPN duly insulated with coloured PVC sleeves having with maintained the colour code and rigidly mounted on bakelite/DMC insulator busbar support (Square/round) isulators of suitable size and good insulation resistance. INCOMING (a)TPN MCCB adjustable thermal magnetic release, 415 volots, breaking capacity 36KA, rating 250 Amps 3 Phase - 01 No OUTGOING (a) MCCB, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics=100%, 25 KA breaking capacity, rating 125 Amps, 50 C/S AC - 01 Nos (b) MCCB, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics=100%, 25 KA breaking capacity, rating 125 Amps, 50 C/S AC - 01 Nos (c) MCCB, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics=100%, 18 KA breaking capacity, rating 25 Amps, 50 C/S AC - 01 Nos (d) MCCB, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics=100%, 18 KA breaking capacity, rating 20 Amps, 50 C/S AC - 02 Nos
Supply, installation, testing and commissioning of outdoor type MCCB box of size (1.0 x 0.7 x 0.5)m, Pedastal Mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double shutter in front side and single shutter in rear side made out of 3.15 mm thick Mild steel CRCA sheet, with 50 x 50 x 6mm size angle iron legs of 0.5m long, duly fabricated and having proper locking arrangement in both front and rear door, surfaces to be painted with Poweder coated paint over exposed external & internal surfaces with heat process suitable for 500V, 50Hz, 3 Phase, 4 wire system, Slanting roof at top duly projected alround as approved comprising with and including the following accessories : INCOMMING/OUTGOING: (a) TPN MCCB of capacity 160 Amps, 415 Volts, 50 HZ, 3 Phase, Breaking Capacity 26KA - 01 No. (b) On load Changeover Switch 04 Pole Panel mounted of 160 Amps. (c) PCC foundation of 100mm thick, 1:3:6 type C2 shall be provided around 1m the panel board and quoted rate shall be deemed to be included accordingly.
Supply, installation, testing and commissioning of outdoor type MCCB box of size (0.5 x 0.4 x 0.3)m, Pedastal Mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double shutter in front side and single shutter in rear side made out of 3.15 mm thick Mild steel CRCA sheet, with 50 x 50 x 6mm size angle iron legs of 0.5m long, duly fabricated and having proper locking arrangement in both front and rear door, surfaces to be painted with Poweder coated paint over exposed external & internal surfaces with heat process suitable for 500V, 50Hz, 3 Phase, 4 wire system, Slanting roof at top duly projected alround as approved comprising with and including the following accessories : INCOMMING/OUTGOING: (a) TPN MCCB of capacity 160 Amps, 415 Volts, 50 HZ, 3 Phase, Breaking Capacity 26KA - 01 No. (b) On load Changeover Switch 04 Pole Panel mounted of 160 Amps. (c) PCC foundation of 100mm thick, 1:3:6 type C2 shall be provided around 1m the panel board and quoted rate shall be deemed to be included accordingly.
Earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground vertically at a depth not less than 2.25 m below normal ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level sourrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filled in alternate layers etc and connected to and including 32 x 6 mm GI strip upto 7.5 m by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 40 mm bore GI pipe connected to main control board and GI pipe medium grade 15 mm bore for watering and including funnel, wire mesh, charcoal salt etc RCC pit cover flush to earth pit 50 mm thick reinforced with 8 mm TMT bar 100 mm C/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20 mm graded aggregate) including excavation and earthwork, disposal of surplus soil to a distance not exceeding 50 m and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified and directed.
Ms N D Enterpise
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .