Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹3.0 LAdmitted-Finance H 123 GYAN MANDIR ROAD GALI NO 3 JAITPUR EXTENSION BADARPUR NEW DELHI 110044 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110044 | L1 | Admitted-Finance |
Tender Value
₹2.8 L
EMD Value
₹5,517
Closing Date
18 May 2026, 3:00 pmClosed
Assistant Engineer (E) SD-III
O/o The Assistant Engineer (E), PWD, EMSD-3 (M-South), Ishwar Nagar near Kalka More, New Delhi-110065
Supply , Installation, Testing and Commissioning of Split Type AC with Stabilizer at Various Offices under M-South Electrical Maintenance Division
2026_PWD_291139_1
15/EE(E) /EMD South Elect. Divn./PWD/2026-27
Open Tender
Electrical Works
Works
30 days
New Delhi
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹5,517
Yes
4 Jun 2026
11 May 2026
18 May 2026
11 May 2026
18 May 2026
11 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only | |||||
| 1.1 | 1.5 TR with 5 Star BEE Rating | 5 | Nos. | 43,539 | ₹2,17,695 |
| 2 | Supplying and fixing voltage stabilizer input power 160-290v, output; 230+/- 8%, Intelligent Time Delay system-Gives the Compressor proper balancing When Mains On Returns, Digital Display with high/low voltage protection i/c suitable for 1.5Ton Air-Conditioners (minimum 4 KV)and Thermal overload protection etc. complete as required. | 5 | Nos. | 6,428 | ₹32,140 |
| 3Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for Split AC, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for suction and Liquid lines, all accessories as per specifications etc. as required : i/c credit of old dismental material as and where basis etc. | |||||
| 3.1 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation | 35 | Mtrs. | 256 | ₹8,960 |
| 3.2 | 12.7 mm dia (OD) (Softdrawn) with tube thickness 1.2 mm with 19 mm thick insulation | 35 | Mtrs. | 487 | ₹17,045 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.89 MB
BOQ_386340.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .