| Sl No | Description | Qty | Unit | HLP SOLUTION L1 |
|---|---|---|---|---|
| 1.00PART A REPAIR WORKS OF EXISTING PANELS & AVR | ||||
| 2.00HT PANEL | ||||
| 3.0011 KV VCB Incomer- 1 Nos and Outgoing - 2Nos | ||||
| 4.00 | Overhauling cleaning/servicing/rectification of existing 11 KV Kirloskar make VCB panel with 3 Nos. VCBs, totally enclosed & fully interlocked , 11 KV VCB Mechanism dismantling, 11 KV CT Spouts dismantling from Panel, VI Housing Rubbing, Cleaning by applying CRC, WD-40, Varnishing done by applying Red Insulation Varnish and Heating treatment done for IR Improvement, AC & DC control circuit rectification, closing circuit rectification, Racked IN inside Panel and power charging, checking all operational mechanism , functions,tripping action, proper operation of relays and meter via secondary current injection test by standard procedure as per IEC 62271-200, as amended up to date and additional specifications and as per special conditions complete as required.
Job includes following works to be carried out for keeping the HT Panel & breaker in servicable condition as per OEM guidelines and providing training to staff on operations of VCBs including Rack in and Rack out. | 1 | Job | 4,95,575 ₹4,95,575 Lowest |
| 5.0011 KV VCB INCOMER | ||||
| 6.00a) SITC of 1 no of power pack I/P:- 220V AC, O/P : 24 V DC | ||||
| 7.00b) SITC of 1 no of 8 Window Annunciator (Make : Minilec Model- MBAS 08 or equivalent) | ||||
| 8.00c) SITC of 1 no of 3 Phase Digital Ammeter (Make : Schneider or equivalent) | ||||
| 9.00d) SITC of 4 nos of 200W space heater (make : RECO, 230 V or equivalent) and 2 nos of Thermostat (Make: ELCON GOLD, Model : MM-106 or equivalent) along with connection | ||||
| 10.00e) SITC of 1 no of 25 Amp TNC switch (Make : Kaycee or equivalent) | ||||
Tender Value
₹35.7 L
EMD Value
₹1.1 L
Closing Date
23 Sept 2025, 10:00 amClosed
AGM(E-E)
AAI, Bagdogra Airport, Bagdogra, Dist. Darjeeling
Provision for the works for compliance of the observation by Aviation Safety at Katihar. Sub head- Rectification or repair of HT panel, AVR and provision of AVR cum Transformer and its associated works at Katihar MSSR station.
2025_AAI_246771_1
AAI/KIR/AGM-I/25-26/NIT/06/258
Open Tender
Electrical Works
Item Rate
150 days
AAI, Katihar ACs Station
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
₹1.1 L
25 Aug 2026
29 Aug 2025
24 Sept 2025
29 Aug 2025
23 Sept 2025
29 Aug 2025
29 Aug 2025 - 3 Sept 2025
Amount
PART A REPAIR WORKS OF EXISTING PANELS & AVR
HT PANEL
11 KV VCB Incomer- 1 Nos and Outgoing - 2Nos
Overhauling cleaning/servicing/rectification of existing 11 KV Kirloskar make VCB panel with 3 Nos. VCBs, totally enclosed & fully interlocked , 11 KV VCB Mechanism dismantling, 11 KV CT Spouts dismantling from Panel, VI Housing Rubbing, Cleaning by applying CRC, WD-40, Varnishing done by applying Red Insulation Varnish and Heating treatment done for IR Improvement, AC & DC control circuit rectification, closing circuit rectification, Racked IN inside Panel and power charging, checking all operational mechanism , functions,tripping action, proper operation of relays and meter via secondary current injection test by standard procedure as per IEC 62271-200, as amended up to date and additional specifications and as per special conditions complete as required. Job includes following works to be carried out for keeping the HT Panel & breaker in servicable condition as per OEM guidelines and providing training to staff on operations of VCBs including Rack in and Rack out.
11 KV VCB INCOMER
a) SITC of 1 no of power pack I/P:- 220V AC, O/P : 24 V DC
b) SITC of 1 no of 8 Window Annunciator (Make : Minilec Model- MBAS 08 or equivalent)
c) SITC of 1 no of 3 Phase Digital Ammeter (Make : Schneider or equivalent)
d) SITC of 4 nos of 200W space heater (make : RECO, 230 V or equivalent) and 2 nos of Thermostat (Make: ELCON GOLD, Model : MM-106 or equivalent) along with connection
e) SITC of 1 no of 25 Amp TNC switch (Make : Kaycee or equivalent)
OUTGOING-1
a) SITC of 1 no of power pack I/P:- 220V AC, O/P : 24 V DC
b) SITC of 1 no of 8 Window Annunciator (Make : Minilec Model- MBAS 08 or equivalent)
c) SITC of 1 no of 3 Phase digital Ammeter and voltmeter (Make : Schneider or equivalent)
d) SITC of 4 nos of 200W space heater (make : RECO, 230 V or equivalent) 2 nos Thermostat (Make: ELCON GOLD, Model : MM-106 or equivalent) along with connection for each panel
e) SITC of 1 no 25 Amp TNC switch (Make : Kaycee or equivalent)
f) Replacement of defective 1 no of TCS relay and SITC of 1 no of TCS relay (Make- EasunReyrolle, Model- XR351, Aux volt- 24 V DC or equivalent )
g) SITC of 1 no of Multi-Function Meter (Make: Schneider, Model: EM6400NG or equivalent)
h) SITC of 1 no of Auxiliary Relay for Trip supply (Make: EasunReyrolle, Model: B33X3, Aux. supply: 24 V DC or equivalent)
i) SITC of 1 no of Auxiliary Relay for Alarm supply (Make: EasunReyrolle, Model: B33X3, Aux. supply: 24 V DC or equivalent)
j) SITC of 1 no of closing coil for Kirloskar make or equivalent 11 KV Outgoing-1 VCB Coil Voltage: 24 V DC
k) SITC of 1 no of tripping coil for Kirloskar make or equivalent 11 KV Outgoing-1 VCB Coil Voltage: 24 V DC
l) SITC of 3 set of Current Transformer Ratio: 25/5+5 A, Core1: 7.5 VA, Class: 1.0 Core2: 7.5 VA, Class: 5P20 STC: 25 kA for 1 SEC, HSV : 12 KV, ILV : 28/75 KV
OUTGOING-2
a) SITC of 1 no of power pack I/P:- 220V AC, O/P : 24 V DC
b) SITC of 1 no of 8 Window Annunciator (Make : Minilec Model- MBAS 08 or equivalent)
c) SITC of 1 no of Electronic Buzzer
d) SITC of 6 nos of 200W space heater (make : RECO, 230 V or equivalent) 3 nos Thermostat (Make: ELCON GOLD, Model : MM-106 or equivalent) along with connection with each panel and Bus-Bar section
e) SITC of 1 no of 25 Amp TNC switch (Make : Kaycee or equivalent)
250 KVA AVR (9-12 KV/433V) Unit-"A","B","C"
Overhauling servicing/rectification of existing 250 KVA (9-12 KV/433 V) Brentford make AVR including oil filtration, testing of transformer oil (BDV Test) before and after filtration till reach of satisfactory di-electric strength of 50 KV or above, providing grouting material and grouting works, minor adjustment and reapir, replacement of wornout/defective parts like auxillariary contactor, PCB relay card,OTI, gaskets, oil seal for HT and LT busing , gasket change,arresting of any oil leakage,top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion etc complete as required. Job includes following works for keeping the AVR in servicable condition as per OEM guidelines and providing training to staff on operations of AVR
250 KVA AVR (9-12 KV/433V) Unit-"A"
a) Oil filtration and di electric strength test for A unit
b) Supply and fixing of transparent breather and replacement of silica gel as per site.
c) Supply and fixing of Cu Link (50 mm X5 mm) as per site.
d) SITC of 4 nos of 12 mm STUDD and 3 nos of 19 mm STUDD
250 KVA AVR (7-12 KV/11 KV) Unit-"B"
a) Oil filtration and di electric strength test for B unit
b) Supply and fixing of transparent breather and replacement of silica gel as per site.
c) SITC of 1 no of Control transformer 50VA, 240V/110V
d) SITC of 1 no of Aux contactor (4NO-4 NC) Make : Siemens/ABB or equivalent, Coil voltage : 110 VAC
e) SITC of 3 no of Aux contactor (3NO-2 NC) Make : Siemens/ABB or equivalent, Coil voltage : 220 VAC
f) SITC of 1 no of PCB Relay card
g) SITC of 6 Nos of Carbon Roller and Tag & Tail
h) SITC of 1 no of 1000VA UPS , Input: 230 V AC
i) SITC of 1 no of Catler Hammer Timer (Coil Volt- 220 V AC)
j) SITC of 6 Inch OTI with 2 nos micro switch and 5 mtrs capillary (Make- PTCI or equivalent)
250 KVA AVR (9-12 KV/433 V) Unit-"C"
a) Oil filtration and di electric strength test for C unit
b) Supply and fixing of transparent breather and replacement of silica gel as per site.
PART B SITC WORKS
AVR CUM TRANSFORMER
Design, supply,transportation, assembling, installing in position, testing and commissioning of copper wound 250 KVA oil immersed,naturally cooled, on load, stepless, Indoor type HT AVR Transformers having input voltage 9000V to 12000V 3 phase 50 Hz to get output stablized voltage at 415 V +- 1%, 3 phase, 50 Hz consist of main step down transformer unit having capacity 295 KVA, regulator unit capacity 50/+-415/415 and Buck/Boost unit capacity 45 KVA including civil foundation work in paved area with associated work as per specifications complete as required. Unit A- Main step down transformer completely independent unit complete with all fittings such as uni/bidirectional plain rollers,lifting lugs,earthing terminals,rating plate, filter valve,drain valve, oil filling hole, thermometer pocket, oil level gauge, silica gel breather, conservator, explosion vent, buchholz relay, marshalling box, Radiator Shut-off Valve, OTI, pressure release valve etc complete as required Unit (B & C) Buck boost & regulator in same base but separated by steel plate with all fittings such as uni/bidirectional plain rollers,lifting lugs,earthing terminals,rating plate, diagram plate, drain valve, oil filling hole, thermometer pocket, oil level gauge, marshalling box, Radiator Shut-off Valve, OTI etc complete as required. (The above transformer shall have losses as per ECBC compliant.)
PART C MISCELLENOUS WORKS
Top up the transformer with ISI marked Transformer oil during filtraion as per site requirement etc complete as required
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 120 sq. mm. X 3 core, 11 KV grade, XLPE aluminium conductor cable of 11 KV grade as required
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 120 sq. mm. X 3 core, 11 KV grade, XLPE aluminium conductor cable of 11 KV grade as required
Supplying of the following sizes of 11KV aluminium, armoured XLPE HT power cable as per IS7098(part-2)-1985 amended up to date, as per specifications. (The outer sheath shall be FRLS.) a) 11 KV, 3C x 120 Sq. mm XLPE Aluminium Armoured cable
Laying of one number PVC insulated and PVC sheatehd / XLPE power cable of 11 KV grade of upto 120 sq. mm on existing cable tray/ direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Supply and drawing of 2.5 Sq mm, single core 1.1 KV grade copper cable for space heater and thermostat wiring.
Supply and laying of 2.5 sq mm x 3 core Cu cable for UPS connection
Supply and laying of 2.5 sq mm x 12 core Cu armoured. cable for protection purpose
SITC 1 KVA UPS for AVR Cum Transformer.
Supply and fixing of 2.5 mm (nominal ± 10%) thick and 1 mtr wide synthetic insulation mat suitable for 11KV grade as per IS: 15652:2006 with upto date amendments. Insulating mat should be flexible, anti-skid, fire retardant, water and moisture proof with no adverse effect of acids, alkalis and transformer oil and other sealing materials as per specifications. Insulating mats should be lSI marked along- with CM/L nos at every meter. Insulating mats should be ERDA and CPRI tested.
Supply and fixing of following types of high voltage Synthetic Insulating Mat made out of synthetic Elastomer conforming to IS 15652:2006 with minimum width of 1 Metre. Insulating mat should be flexible, anti-skid, fire retardant, water and moisture proof with no adverse effect of acids, alkalis and transformer oil. Insulating mat should be fixed with suitable adhesive/Chem bound resin, water proofing compound and other sealing materials as per specifications. Insulating mats should be lSI marked along- with CM/L nos at every meter. Insulating mats should be ERDA and CPRI tested. (a) Class- A type, Up-to 3.3 KV (Thickness: 2 mm)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 50 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].