Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.4 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹10.7 L+₹21,020 (2.01%)Rejected-Finance CA 325 SA767 PWD K EL 13 1 472 CASAMARINA COMPLEX TALAP KANNUR | KANNUR | KANNUR | KERALA | 670101 | L2 | Rejected-Finance L2 |
| Sl No | Description | Qty | Unit | Sajju T L2 | Vinod Kumar M L1 |
|---|---|---|---|---|---|
| 1.00ELETRIFICATION | |||||
| 1.00 | OD289926/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with
120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by
pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range :
160V -280V with cut off e) THD .9 % g) Ambient Temperature :
0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under
charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j)
LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge,
Temperature, frequency q) Approved UPS make : APC/Delta/Numeric, r) Approved C10 rated
battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not
acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year
warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. | 7 | each | 1,35,000 ₹9,45,000 | 1,30,350 ₹9,12,450 Lowest |
| 1.00 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way, Double door | 3 | each | 2,050 ₹6,150 Lowest | 2,300 ₹6,900 |
| 1.00 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way, Double door | 2 | each | 1,930 ₹3,860 Lowest | 2,600 ₹5,200 |
| 1.00 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
Single pole | 25 | each | 275 ₹6,875 | 250 ₹6,250 Lowest |
| 1.00 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 5 | each | 450 ₹2,250 Lowest | 450 ₹2,250 Lowest |
| 1.01 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. | 10 | each | 13 ₹130 Lowest | 13 ₹130 Lowest |
| 1.01 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm | 260 | metre | 111 ₹28,860 Lowest | 124 ₹32,240 |
| 1.01 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm | 20 | metre | 125 ₹2,500 Lowest | 140 ₹2,800 |
| 1.01 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | 150 | metre | 86 ₹12,900 Lowest | 100 ₹15,000 |
Tender Value
Refer Docs
EMD Value
₹26,383
Closing Date
11 Feb 2026, 2:00 pmClosed
Assistant Executive Engineer
PWD Electrical Sub Division, Thalassery
DEPOSIT-SITC of UPS at Revenue Offices - SITC of UPS at Various at Village Offices in Taliparamba Taluk- Maniyoor, Mayyil, Morazha, Irikkur, Payyavoor, Sreekandapuram, Taliparamba, in Talipramba Taluk - Phase 2-General Electrical Work
2026_PWD_833581_1
PWD/BLDG/TR/4757/2024_6_41_40
Open Tender
Electrical Works
Item Rate
150 days
Taliparamba
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹26,383
30 Jul 2026
4 Feb 2026
13 Feb 2026
4 Feb 2026
11 Feb 2026
4 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1ELETRIFICATION | |||||
| 1.001 | OD289926/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with
120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by
pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range :
160V -280V with cut off e) THD .9 % g) Ambient Temperature :
0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under
charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j)
LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge,
Temperature, frequency q) Approved UPS make : APC/Delta/Numeric, r) Approved C10 rated
battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not
acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year
warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. | - | each | - | - |
| 1.002 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way, Double door | - | each | - | - |
| 1.003 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way, Double door | - | each | - | - |
| 1.004 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
Single pole | - | each | - | - |
| 1.005 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | - | each | - | - |
| 1.006 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. | - | each | - | - |
| 1.007 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm | - | metre | - | - |
| 1.008 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm | - | metre | - | - |
| 1.009 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | - | metre | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1401874.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
viewnit.pdf
Tender Documents • 0.02 MB
viewsbd.pdf
Tender Documents • 1.63 MB
mom.pdf
Other Document • 0.26 MB
specificcondition.pdf
Additional Documents • 0.34 MB
BOQ_1401874.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .