Loading…
Loading…
Tender Value
₹10 L
EMD Value
₹10,000
Closing Date
13 Aug 2026, 5:00 pmClosed
Mr. Hitendrakumar Arvindrai Surti
Tender for Underground Cable Fault Tracing & attending the same by Supply and Fixing of Cable End Termination and Straight Through joint kit for various sites within jurisdiction of VAPI GIDC Sub Division under Vapi Industrial Division.
329168
VPID/TECH/TENDER/2644 Dtd. 29.07.2026
Open
Electrical and Maintenance Works
Works
Valsad
4 documents required · 4 mandatory
₹3,540
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹10,000
30 Jul 2026
30 Jul 2026
30 Jul 2026
13 Aug 2026
30 Jul 2026
Item Code Unit Rate
Labour charge for excavation of
cable trench of 400mm width x
1200mm depth, in any type of soil for
laying of cable of size up to 240 mm2
(For additional cable 200 mm
additional width shall be considered
i.e. half trench length is to be
Labour charge for excavation of
cable trench of 600mm width x
1200mm depth, in any type of soil for
laying of cable of size up to 240 mm2
(For additional cable 200 mm
additional width shall be considered
i.e. half trench length is to be
Labour charge for excavation of
cable trench of 400mm width x
1500mm depth, in any type of soil for
laying of cable of size up to 240 mm2
(For additional cable 200 mm
additional width shall be considered
i.e. half trench leng th is to be
Labour charge for laying of 11kV /
kV XLPE Cable of size up to 240 mm2
& preparation of sand layer 100mm
thick, in the cable trench & covering
the cable with 150 mm dia (Outer),
thickness 25 mm, 1.0 meter long
RCC half round muffs and providing
and fixing of 4inch width yellow
colour polyethylene tape with
printing"CAUTION ELECTRIC CABLE
BELOW' at 0.75 m depth from ground
surface after laying cable in trench.
This will provide indication that
electric cable is passing underground
so as to protect cable from
mechanical injuries, refilling the
same, as per Instruction of E gineer
in Charge (EIC) .
Labour charge for erecting of 11kV /
22 kV XLPE cable of size up to
mm 2 on DP Structure with fixing of
5 9925000014 02 Nos polymer cleats on top and Meter
middle part. Polymer cleats, nut bolts
etc. fixing material to be provided by
Providing & fixing of 6.11kg/cm2
class4,Green color, 110mm O.D.
8.5mm thickness H.D.P.E. pipe
confirms to IS 4984 and BIS
certification on the erected DP
structure for the mechanical
protection of cable by inserting the
cable inside HDPE pipe. The HDPE
6 9925000015 perJob
pipe shall be erected in such a way
that 300mm shall be below the
ground level and the rest 2700 mm
shall be supported on the DP
Structure with 01 No Polymer cleat.
All materials including polymer cleat
and Nut bolt to be provided by
File No: DGVCLDVPI/TEN/e-file/4448/2026/2431/Account
Approved By: Executive Engineer,Technical,DGVCLDVPI
Letter No: DGVCLDVPI/0638/07/2026 Approved Date: 29-07-2026 05:46
Supply & fixing of heat shrink type
end terminations (outdoor) for up to
7 9925000017 11kV 3C x 185 mm2 size XLPE cable No
as per DGVCL technical s ecification
Supply & fixing of heat shrinkable
type end terminations (indoor) for
8 9925000019 up to 11kV 3C x 185 mm 2 size XLPE No
cable as per DGVCL technical
Supply & fixing of heat shrinkable
straight through joint for up to 11kV
3C x 185 mm 2 size XLPE cables as
per DGVCL technical specification.
Labour charge for excavation of
2100mm long x 1200mm wide x
1200 mm deep joint pits for
installation of 11kV / 22kV Straight
through joints as per instruction of
engineer-in-charge & covering the
cable with 150 mm dia (Outer),
thickness 25 mm, 1.0 meter long
RCC half round muffs & refilling same
as per instruction of EIC .
Testing of cable at various points and
commissioning the feeder as per
9925000025 instruction of engineer-in-charge.Test No
11 result shall be submitted by
contractor with bill.
Supply & fixing of heat shrink type
end terminations (outdoor) for 11kV
12 9925000030 3C x 240 mm2 size XLPE cable as per Nos
DGVCL technical specification.
Supply & fixing of heat shrink type
end terminations (indoor) for 11kV
3C x 240 mm2 size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat shrinkable
straight through joint for 11kV 3C x
240 mm2 size XLPE cables as per
DGVCL technical s ecification.
1 DGVCL will provide key material like MS materials, ABC/Bare conductors,
PSC/RSJ poles, Insulators, Fabricated materials etc. to the contractor.
2 All fabricated items shall be fabricated as per DGVCL approved drawing and
by welding rods confirming to the relevant ISI specification and as directed
by Engineer in charge
3 Necessary electricity connection for fabrication items shall be provided by
DGVCL on payment of required charge for connection & electricity bill of the
same shall be paid by the agency
4 All the rates are inclusive of PF and Exclusive of GST applicable time to time
Work to be carried out after issued of Sub work order by S/dn. Office not
6 All steel material are to be painted as below :
(A) Scrubbing of rusted surface properly before applying the paints on to the
RSJ poles & steel fabricated materials of RSJ/PSC poles is must require.
(B) Two coats of approved ISI mark red oxide (primer) is to be properly
painted for the RSJ poles & Steel fabricated materials of RSJ/PSC poles.
File No: DGVCLDVPI/TEN/e-file/4448/2026/2431/Account
Approved By: Executive Engineer,Technical,DGVCLDVPI
Letter No: DGVCLDVPI/0638/07/2026 Approved Date: 29-07-2026 05:46
(C) Two coats of approved ISI mark Silver paint (i.e. triple mangoes or
equivalent quality silver paint) is to be properly painted on to the RSJ poles &
Steel fabricated materials of RSJ/PSC poles.
7 Submission of Bill for Supply/Purchase of KIT Cable Usage, with bifurcation
of Supply amount along with Labor.
8 Any material (XLPE / Aerial Bunch Cable, Joint Kit etc.) provided by
contractor is approved by DGVCL make, specification and submission of
Invoice with purchase bill.
9 The rates are inclusive of dismantling charges of existing bare conductor and
crediting in to store & dismantling of service lines from LT bare conductor
and to provide service connections on ABC by insulated pierce connectors
through service connection box.
10 The contractor has to collect all the required materials from DGVCL store as
well as credit the dismantle material to the DGVCL store at their cost.
11 Labour Wellfer Cess @1% shell be Deduction in Bill Amt.
EXECUTIVE ENGINEER
DGVCL; VAPI IND DIV.
File No: DGVCLDVPI/TEN/e-file/4448/2026/2431/Account
Approved By: Executive Engineer,Technical,DGVCLDVPI
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NIT-2644.pdf
DE Tech Office Note.pdf
Schedule-B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .