| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.2 LAccepted-Finance | 1 | Accepted-Finance L1 LOWEST BIDDER | |
| 2 | 2₹3.9 L+₹78,470 (24.8%)Rejected-Finance | 2 | Rejected-Finance RATES ARE ON HIGHER SIDE | |
| 3 | 3₹4.0 L+₹80,620 (25.5%)Rejected-Finance | 3 | Rejected-Finance RATES ARE ON HIGHER SIDE |
Tender Value
₹3.2 L
EMD Value
₹3,500
Closing Date
20 May 2022, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC UPPTCL AZAMGARH
220KV S/S COLONY HAFIZPUR AZAMGARH
WORK FOR REPLACEMENT OF IV SIDE B-PHASE DEFECTIVE BUSHING OF 200MVA, 220/132KV T/F AT 220KV S/S AZAMGARH UNDER ELECTY. 400KV S/S DIVISION, AZAMGARH
2022_UPTCL_699768_1
09/AETC/2022-23
Open Tender
Electrical Works
Item Wise
20 days
AZAMGARH
UTR SLIP OF EMD TENDER FEE PAN CARD GST CERTIFICATE WORK EXPERIENCE etc.
2 documents required · 2 mandatory
₹413
SE ETC UPPCL AZAMGARH
₹3,500
25 May 2022
14 May 2022
20 May 2022
14 May 2022
20 May 2022
14 May 2022
14 May 2022 - 20 May 2022
90 days
Amount
Shifting of 20KL oil tank from open store to 200MVA transformer (Approx distance 70mtr) with the help of hydra and cleaning of oil tank.
Draining of oil from ICT by using 6KLPH oil filteration machine up to core level after shutting off isolation 80 NB valve of conservator pipeline in oil storage tank.
Dismantling & removal of defective bushing from ICT using crane.
Mounting/erection of spare bushing in ICT using crane and subsequent to erection leakage test using N2 gas / Dry air (of dew point -50 Deg. C) @ 2 PSI for 3 Hrs.
Providing of 02 Nos. N2, gas cylinder having Dew point -50 to -60 C, purity 99.9% in 7 m3 volume cylinder having pressure130-140Kg/cm2 for leakage test (Cylinder will be returned after completion of work)
Filtrations of drained oil in storage tank to achieve specified oil parameter (BDV: 70 kV & Moisture: 5 PPM).
Vacuuming of transformer tank after bushing erection & prepare oil to be filled in ICT under vacuun condition under supervision Engineer of M/s BHEL Ltd.
After oil filling in ICT, hot oil circulation (HOC) to carried out to achieve specified oil parameters (BDV: 70 kV & Moisture: 5 PPM)
Dielectric-related test of ICT (IR & PI of winding and Tan Delta of winding, spare bushing (before and after erection) & other bushings by calibrated test kit (by third party) at the time of preerection and precommsioning .
Testing of transformer oil from NABL certified lab 01 sample:- BDV, PPM (Oil storage tank) 01 sample :- BDV, PPM (Main tank).
Perfect Power Transformer Associates
Preeti Enterprises
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .