Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 31 2 ADAKAMARANAHALLI MAKALI POST VILLAGE DASANAPURA HOBLI BANGALORE URBAN BANGALORE RURAL KARNATAKA 562123 | BENGALURU RURAL | KARNATAKA | 562123 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 104 105 KINGSTONE TOWER OPP VIVA COLLEGE BYPASS ROAD VIRAR WEST MAHARASHTRA 401303 | PALGHAR | MAHARASHTRA | 401303 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
₹22.0 L
EMD Value
₹44,060
Closing Date
19 Nov 2022, 6:00 pmClosed
EXECUTIVE OFFICER
NAGAR PALIKA LAXMANGARH
Supply, installation maintenance of Online Continuous Effluent Monitoring System (OCEMS) pH, BOD, COD, TSS Flow along with data transfer to CPCB, RSPCB Municipal Board Laxmangarh server for running 1.0 MLD STP LAXMANGARH
2022_DLB_304425_1
3509-14
Open Tender
Miscellaneous Services
Item Wise
30 days
LAXMANGARH
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
EXECUTIVE OFFICER MUNICIPAL BOARD AND MD RISL
₹44,060
22 Nov 2022
9 Nov 2022
21 Nov 2022
9 Nov 2022
19 Nov 2022
9 Nov 2022
Amount
Supply & Installation of On Line BOD/COD/TSS/PH in-situ based Analyzer with panel for S.T.P effluent Measurement items UV- VIS Spectrometry Double beam with entire spectrum scanning 200 – 720 nm / 190- 750nm wave lengths along with 256 unique pixel diode. •MOC of BOD/COD/TSS sensor -Titanium3.7 / SS316L or better • Cleaning facility.-ultrasonic cleaning or Air pressure Cleaning• Accuracy of BOD/COD/TSS sensor- +/-3% of the measured value • Light Source: Xenon Flash LampFollowing measuring ranges are required :• COD: 0-700 mg/lBOD: 0-400 mg/l TSS: 0-600 mg/lPh range - 0 to 14 • MOC of ph sensor-Stainless Steel316 or better •Ph Accuracy +/- 0.2% •protection type : IP 68 for both the Sensor and Cable (Cable lengthas per site requirement)• Controller/Display- Housing Material – Non corrosive e.g.Acrylonitrile-Styrene- Acryloester polymer or better• Protection Rating IP 67 Controller/display cabin boxshould be IP66 Grade with lock & key SS304 Grade MOC
Ultrasonic open channel flow meter with shall comprise of Flow sensor / transducer, flow transmitter, digital level indicator / remote indicator, control unit • Operating Temperature: 0 to 50°C. • Safety: Explosion Proof or Intrinsically Safe. • Measuring Principal: Ultrasonic. • Communication Protocol: Open Protocol like MODBUS, PROFIBUS, HART, etc. • Analog Output: Isolated 4-20mA. • Relay Contacts: Minimum of 3 SPDT contacts. • Accuracy: ± 0.25% of measured value or better. • Output-. 4 - 20 mA •Protection a.) Sensor: IP-68. b.) Transmitter / Controller: IP-66 (NEMA 4X). • Display: LCD with LED backlighting 130.
1kva UPS • Capacity -1000VA/600W • Input Voltage Range- 140 V ~ 300 V AC Frequency - 50 Hz ± 10% • Operating Temperature- 0°C-40°C; • Charging Time -6~8 Hours recover to 90% capacity Battery Rating -SMF 12V/7AHx2 Batteries. • Output Voltage -230 V AC Nominal Transfer Time- Typical 4~8ms • Type- Sealed Maintenance Free
Comprehensive Operation & Maintenance Cost for whole system for 1st year including data transmission to CPCB, RSPCB & MBL website, four service visits, two times Calibration of system in a year,repairable Cost, replacement cost, Consumables etc.
Comprehensive Operation & Maintenance Cost for whole system for 2nd year including data transmission to CPCB, RSPCB & MBL website, four service visits, two times Calibration of system in a year, repairable Cost, replacement cost, Consumables etc.
Comprehensive Operation & Maintenance Cost for whole system for 3rd year including data transmission to CPCB, RSPCB & MBL website, four service visits, two times Calibration of system in a year, repairable Cost, replacement cost, Consumables etc.
Comprehensive Operation & Maintenance Cost for whole system for 4th year including data transmission to CPCB, RSPCB & MBL website, four service visits, two times Calibration of system in a year, repairable Cost, replacement cost, Consumables etc.
Comprehensive Operation & Maintenance Cost for whole system for 5th year including data transmission to CPCB, RSPCB & MBL website, four service visits, two times Calibration of system in a year, repairable Cost, replacement cost, Consumables etc.
Installation Charges
M/S M. D. CONST. CO.
PT Ecological Services Pvt Ltd
Analyser Instrument Co. Pvt. Ltd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .