Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 CrAccepted-AOC | ₹1.4 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹1.6 Cr+₹19.0 L (13.3%)Rejected-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹1.6 Cr+₹19.0 L (13.3%) | L2 | Rejected-Finance Not the lowest bidder |
| Sl No | Description | Qty | Unit | Blue Star Limited L2 | cool master L1 |
|---|---|---|---|---|---|
| 1.00DOUBLE SKIN DX COIL AIR-HANDLING UNITS (Plug Fans with VFD) | |||||
| 1.01 | AHU housing shall be made of 45±2mm thick panels consisting of 0.8 mm thick galvanized preplasticised/powder coated sheet on outside and 0.63 mm thick plain GI sheet inside with polyurethane foam (PUF) 40 kg/m3 (minimum) density insulation factory injected between them by injection moulding machine. AHU housing framing structure shall be thermal break structure type. The AHU shall have a fan section with Plug Fan (AMCA/Eurovent certified), TEFC drive, IE-3 motor suitable for 415+ 10% volts, 1/3 phase 50 Hz AC supply, motor mounting arrangement inside the casings, stainless steel (18G) drain pan with PUF insulation, belt drive system and with vibration isolators, Coil section with ARI 410A compliant Cu Tube / Al finned 6 Row deep -13 FPI Dx coil, with suitable for DX Unit connective , aluminium damper on the outlet of AHU. The cooling coil section shall be of 6-row DX type as per technical specification, with a removable coil frame, and shall include a double-wall stainless steel (SS) drain pan with 25 mm thick foam insulation to prevent condensation. The filter section shall comprise one set of commissioning filters, including Pre-filter (MERV 8) and Fine filter (MERV 13), with easily removable access for maintenance, and manometer ports shall be provided to monitor pressure drop across the filters. The maximum face velocity shall not exceed 2.5 m/s. The fan outlet shall be provided with a heavy-duty, double-layer flexible canvas connection for vibration isolation. AHU should supply with necessary VFD for speed control based on return air temperature (Qty of VFD should be as per no. of Fan) and Bypass Starter. AHUs shall be fitted with GI VCD's (Volume Control Damper) for supply/return/fresh air / purge air opening of AHU body with canvass connection. The AHU shall be supplied with a mixing Box, Thermostat for Temperature control, AHU kit of OEM if required etc . All supporting GI hangers, ,MS angles, channels nut , bolts, washers etc. necessary for unit installation shall be inclusive in the cost. All AHUs shall be suitable for Static Pressure as mentioned below. Vendor to consider the suitable size of FRLS power cable from panel to unit in scope of supply.
Wherever multiple condensing units are offered for the AHU, the AHU DX coil shall have multiple circuit with required controls compatibility with Refrigerant of the Outdoor Unit . Cost of VFD drive & VFD bypass starter panel along with Copper power and control cabling , earthing ,cable tray etc. unto 10 mtr.length shall be considered along with the cost of AHU. Air handling unit shall be selected for the lowest operating noise level i.e., not exceeding 60 dbA @ 1 metre distance from the equipment. Fan performance rating and power consumption data, with operating points clearly indicated shall be submitted and verified at the time of testing and commissioning of the installation.
25 TR, 7500 cfm, 15 sqft./ 6 Row, [Floor Mounted]
External Static Pressure (ESP) 45 mm wg, | 4 | Nos | 4,98,894 ₹19,95,576 Lowest | 5,15,730 ₹20,62,920 |
| 1.02 | Installation, testing & commsssioning the AHU UNIT, With Refrigerent chargingig as per above specification including all accessories as specified and as required in the Techncial Specifications.
25 TR, 7500 cfm, 15 sqft./ 6 Row, [Floor Mounted]
Low sound AHU not exceeding 60 dbA @ 1 metre | 4 | Nos | 12,642 ₹50,568 Lowest | 32,106 ₹1,28,424 |
| 2.00Condensing Units [Split] – Inverter Scroll Compressor | |||||
| 2.01 | Supply, installation, testing, and commissioning of corrosion-resistant galvanized powder-coated (or equivalent) sheet steel outdoor Air cooled condensing unit, designed for low-vibration operation and installed on suitable vibration isolators. The unit shall comprise an energy-efficient inverter scroll compressor with built-in controls, including a thermal protector, HP/LP cutouts, and a pressure relief valve. The condensing unit shall include a finned-tube air-cooled condenser with a protective metal-framed condenser fan unit.
The unit shall have integral refrigerant copper piping within the compressor and condenser, with accessories such as refrigerant shutoff valves (at the compressor/compressors and liquid refrigerant outlet, if required) and a filter dryer. The outdoor units located within sunshades or on terraces shall be mounted on a MS angle iron frame, which shall be pre-welded, corrosion-proof painted, securely grouted on the floor, and isolated with vibration isolation pads. R32/R134A/R410A shall be the refrigerants and selected for high ambient condition and operating at 40 degree celcius for capacity selection
The price shall be inclusive of all required MS supports and factory-supplied matching-rated electrical starter & control panel, including an AHU kit if required for indoor outdoor communication. The scope includes the Refrigerent Supply and charging, supply and commissioning of copper refrigerant piping (with 19 mm thk Nitrile Rubber insulation) as per the drawing, up to a maximum of 18 meters, along with all necessary accessories including control cable between indoor and outdoor . with all external refrigeration pipe insulation to be coated with one coat of fungicidal protective coating (lke star bond CR 30-36) on canvass coating as per Techncial Specification .
Capacity : 8.5 TR condensing unit | 12 | Nos | 1,40,218 ₹16,82,616 Lowest | 1,57,980 ₹18,95,760 |
| 2.02 | Installation, testing & commsssioning the CONDENSING UNITS [SPLIT] as per above specification including all accessories as specified and as required. control Cable shall be laid in suitable conduits between indoor and outdoor unit.
8.5 TR condensing unit | 12 | Nos | 29,550 ₹3,54,600 | 6,500 ₹78,000 Lowest |
| 3.00DUCTABLE DX SPLIT UNIT -Scroll Compressor | |||||
| 3.01 | Supply of R32/R410a Refrigerant type Ductable Aircooled split unit with Indoor and outdoor units with Scroll Compressors, Suitable Size copper refrigerant piping (insulated: 19 mm thk Nitrile Rubber) length as per drawing maximum upto 18 mts (between Indoor and Outdoor), thermostat and all standard accessories and designed should be high ambient conditions etc. Electronic microprocessor pendant controller with digital display, vibration isolator pads, structural support for fixing IDU/ODU, safety devices including thermal protector, pressure relief valve, overload relay single phase preventer etc. Power wiring and thermostat wiring, high-low pressure cut out. suitable for 3 phase 415 ± 10% V, 50Hz, AC supply etc. complete as required. AHUs shall be complete with:- (I) Fan section with Statically & dynamically balanced direct drive DIDW forward curved centrifugal fan, permanent split capacitor type drive motor/ TEFC Motor. (II) Coil sections with 6-row DX type cooling coil. Face velocity not over 500 FPM. Seamless copper coils of plate finned compact tape with a minimum of air by pass. Copper tubes with smooth non-corrugated fins of aluminium. The aluminium fins used on the evaporator coil to have a hydrophilic coating (III) Filter Sections with Fine FiltersMinimum MERV 8 / PM2.5 (90% Down to 10 Micron)washable filters, Comprising heavy gauge construction with Echelon arrangement of filters, slides & end cap shall permit filter access at any end & compressing device hold filter snugly together. (IV) Sandwich insulated SS drain tray. (V) AHU mounted opposed blade aerofoil design low-leakage isolation (IL) or volume control dampers (VCD) of Aluminium with Nylon gears for supply & return air (VCD) for normal operation As applicable. (VI) Corded Control unit with LCD display for temperature setting and adjustment (VII) Commissioning of Sheathed Communication Cable in PVC Conduit between indoor unit to outdoor unit. (VIII) Min Set Point Temp. 18 deg C (IX) All necessary accessories including required amount of refrigerent etc.
Capacity: 11 TR , (high Static) Ductable split selected and designed for an outdoor ambient design condition of 40 degree celcius and having a minimum sensible cooling capacity of 400 CFM/TR | 6 | Nos | 2,26,377 ₹13,58,262 Lowest | 2,41,225 ₹14,47,350 |
| 3.02 | Supply of R32/R410a Refrigerant type Ductable Aircooled split unit with Indoor and outdoor units with Scroll Compressors, Suitable Size copper refrigerant piping (insulated: 19 mm thk Nitrile Rubber) length as per drawing maximum upto 18 mts (between Indoor and Outdoor), thermostat and all standard accessories and designed should be high ambient conditions etc. Electronic microprocessor pendant controller with digital display, vibration isolator pads, structural support for fixing IDU/ODU, safety devices including thermal protector, pressure relief valve, overload relay single phase preventer etc. Power wiring and thermostat wiring, high-low pressure cut out. suitable for Single Phase/ 3 phase 415 ± 10% V, 50Hz, AC supply etc. complete as required. AHUs shall be complete with:- (I) Fan section with Statically & dynamically balanced direct drive DIDW forward curved centrifugal fan, permanent split capacitor type drive motor/ TEFC Motor. (II) Coil sections with 4/ 6-row DX type cooling coil. Face velocity not over 500 FPM. Seamless copper coils of plate finned compact tape with a minimum of air by pass. Copper tubes with smooth non-corrugated fins of aluminium. The aluminium fins used on the evaporator coil to have a hydrophilic coating (III) Filter Sections with Fine FiltersMinimum MERV 8 / PM2.5 (90% Down to 10 Micron) washable filters, Comprising heavy gauge construction with Echelon arrangement of filters, slides & end cap shall permit filter access at any end & compressing device hold filter snugly together. (IV) Sandwich insulated SS drain tray. (V) AHU mounted opposed blade aerofoil design low-leakage isolation (IL) or volume control dampers (VCD) of Aluminium with Nylon gears for supply & return air (VCD) for normal operation As applicable. (VI) Corded Control unit with LCD display for for temperature setting and adjustment (VII) Commissioning of Sheathed Communication Cable in PVC Conduit between indoor unit to outdoor unit. (VIII) Min Set Point Temp. 18 deg C (IX) All necessary accessories including required amount of refrigerent etc.
Capacity:5.5 TR Ductable split high Static) selected and designed for high ambient conditi of 40 degree celcius and having a minimum sensible cooling capacity of 400 CFM/TR | 2 | Nos | 1,41,508 ₹2,83,016 | 1,31,974 ₹2,63,948 Lowest |
| 3.03 | Supply of 3.0TR single circuit, 3 phase power supply,inverter scroll, High Static ductable split AC unit of minimum three star rating having cooling capacity not less than 36000 BTU/Hr, 30 Pa static pressure & 400 CFM per TR having front flow type indoor unit, air cooled condenser, initial charge of gas (R32/R410A], LCD remote control, protection from under voltage, over voltage, phase imbalance voltage, phase loss, phase revers & HP/LP etc., having minimum 8 mtrs connecting copper pipes with insualtion, cable and cable tray, conduits complete as per technical specifications etc. as required. The evaporator and condenser coil comprise of copper tube, aluminum fin.
The unit shall also include wall-mounted digital thermostat suitable for hideaway / ducted split units, compatible with 24V AC / 230V AC control systems, supporting on/off control, 3-speed fan operation. The thermostat shall feature an LCD display (digital models) with a temperature control range of 10°C to 32°C, ensuring seamless integration with ducted split units. as per the approved makes
Capacity: 3.0 TR Ducted Split | 4 | Nos | 1,07,134 ₹4,28,536 Lowest | 1,09,570 ₹4,38,280 |
Tender Value
₹1.4 Cr
EMD Value
₹3.5 L
Closing Date
5 Nov 2025, 4:00 pmClosed
Managing Director
Managing Director, Cochin International Airport Ltd, Kochi Airport P O, Nedumbassery, Ernakulam
HVAC System works in connection with the construction of Hospitality and sporting facilities at CIAL Golf Club
2025_CIAL_807427_1
CIAL/ELE/393/ET13
Open Tender
Miscellaneous Works
Item Rate
365 days
Cochin International Airport Golf Club
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,950
₹3.5 L
12 Nov 2025
9 Oct 2025
6 Nov 2025
9 Oct 2025
5 Nov 2025
24 Oct 2025
9 Oct 2025 - 22 Oct 2025
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
Drawings.rar
Other Document • 8.66 MB
BOQ_1345665.xls
BOQ • 0.41 MB
tender.pdf
Tender Documents • 1.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .