Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.2 LAccepted-AOC CHAKKALAKKAL H KOTTAT P O | L1 | Accepted-AOC First lowest | |
| 2 | L2₹8.0 L+₹80,234.25 (11.1%)Rejected-AOC | L2 | Rejected-AOC Second lowest | |
| 3 | L3₹8.4 L+₹1.1 L (15.6%)Rejected-AOC | L3 | Rejected-AOC Third lowest |
Tender Value
Refer Docs
EMD Value
₹20,117
Closing Date
11 Apr 2025, 6:00 pmClosed
Assistant Executive Engineer
PWD Electrical Subdivision, Palakkad
GENERAL-Reconstruction of Kuruthikode bridge in Tarur LAC in Tarurpally Thonikadavu road-work-General Electrical Wor
2025_PWD_756971_1
ET-78/ESDPKD/2024-2025
Open Tender
Electrical Works
Item Rate
562 days
Palakkad
Please refer Tender documents.
11 documents required · 11 mandatory
₹1,775
₹20,117
18 Jun 2025
29 Mar 2025
19 Apr 2025
29 Mar 2025
11 Apr 2025
29 Mar 2025
Amount
SITC of AC
90.15.3.5:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x12 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc. complete 7 Meters
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD91578/2024-2025:Supply and fixing of Threaded rod foundation bolt 4nos of 8.8 Grade M20 size in 600mm length using chemical anchoring vertically on the footpath. The bolt shall be anchored minimum 10cm inside main concrete and through top slab including 2 nuts washers equivalent to HIlti Threaded rod AM20x3000 8.8 Zinced + Injectable Motar HIT-RE 500 V4/500
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
90.12.5.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm
90.12.5.3:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
OD23251/2024-2025:Supplying and fixing 24Hours Timer for operating ON-OFF function in 1the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required.
OD23252/2024-2025:Supplying and fixing 3Pole Power contractor ( MNX type)make L&T in 1the existing enclosure complete with connections, testing and commissioning etc. as required.
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
OD91626/2024-2025:Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD23265/2024-2025:Supply & installation of dust and vermin proof, 1 Phase Syntax Meter Board( GS-MB- 3525) including 32 A HRC Fuse Base with HRC Fuse link ,32 A neutral link and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD91625/2024-2025:Supply and fixing Danger notice board of size, 125 x 75 mm
ARUN.C.S (BID ID -2193548)
AYAPPA ELECTRICALS (BID ID -2193885)
Bidder Name
BIJU JOSE
AYAPPA ELECTRICALS
ARUN.C.S
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1229563.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .