Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.8 LAccepted-Finance | ₹24.8 L | L1 | Accepted-Finance LOWEST |
| 2 | L2₹26.8 L+₹2.0 L (8.18%)Rejected-Finance | ₹26.8 L+₹2.0 L (8.18%) | L2 | Rejected-Finance OTHER THAN LOWEST |
| 3 | L3₹27.8 L+₹3.0 L (12.0%)Rejected-Finance | ₹27.8 L+₹3.0 L (12.0%) | L3 | Rejected-Finance OTHER THAN LOWEST |
| Sl No | Description | Qty | Unit | G.M. ENGINEERING SERVICES L2 | SIDDAHANT ENTERPRISES L3 | dinesh enterprises L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, laying and testing of XLPE electric power cable insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty ) 1100 volt grade with stranded aluminium conductor of size 95 sqmm, 3.5 core complete all as specified and directed.
Note:- There is no earth work the cable drawn inside HDPE pipe inside building. | 75 | RM | 750 ₹56,250 | 761 ₹57,075 | 680 ₹51,000 Lowest |
| 2.00 | M & L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI earth galvanised iron strip of size 32×6mm and 40 mm dia bore light grade GI protection pipe for earth strip and GI watering pipe 20 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009 complete all as specified and directed.
Note:-
For LT Voltage stabilizer - 01 x 04 = 04 Nos
For LT Panel - 05 panel x 02 Earthing = 10 Nos
For High mast light - 02 Nos
High mast light control panel - 02 Nos | 18 | Each Set | 5,000 ₹90,000 | 4,460 ₹80,280 | 4,200 ₹75,600 Lowest |
| 3.00 | S & L HDPE pipe PN -10 of 100 mm bore for protection of LT cable | 50 | RM | 200 ₹10,000 | 86 ₹4,300 Lowest | 220 ₹11,000 |
| 4.00 | Supply, Installation, Testing and commissioning of Servo Controlled Voltage stabilizer of capacity 100 KVA confirming to BIS 9815 (Part-I): 1994, reaffirmation 2019 latest version, Three phase, four wire (RYBN), 50 Hz, Naturally oil cooled, indoor, unbalanced type, copper wound, metallic body duly poweder coated with lifting hooks two nos, digital display, relay free smooth and silent operation with display type, relay free smooth and silent operation with 1st filling of Transformer oil up to level having following specifiaction:-
(a) Capacity of Servo Voltage Stabilizer - 100 KVA.
(b) Type - Suitable for unbalanced load and unbalanced input.
(c ) Input voltage - 360 Volts to 480 Volts, Input frequency 50 HZ.
(d) Output voltage - Stabilized at any designed/desired voltage 415 ± 1%
(e) Rated frequency - 50 Hz.
(f) Wave form distortion -NIL.
(g) Response time - not to exceed 20 Milliseconds.
(h) Sensitivity - ± 1%
(j) Rate of correction - Not less than 6 Volt/second between phase and netural.
(k) Efficiency - more than 95 %
(l) Type of load - Three phase, unbalnced type.
(m) Metering - Digital display voltmeter / Ammeter with multifunction meter.
(n) Operating temperature-For indoor use upto max ambient temperature + 55° C.
(o) Dimmer rating - Min 140 Amps max 200 Amps.
(p) Dimension of tanks - As per IS standard.
(q) Oil capacity - As per IS standard and manufacturer recommendation. | 1 | Each | 3,41,839 ₹3,41,839 | 5,45,000 ₹5,45,000 | 2,90,000 ₹2,90,000 Lowest |
| 4.01(r ) Class of Insulation - Class F (s) Mode of operation -Automatic /Manual (t) Winding Temperature rise - Max 55° C (10° C above operating temperature) (u) Transformer oil - IS 335 marked. (v) Core _ CRGO M4 Grade/GRNO (Cold Roll Grain oriented) (w) Auto Transformer (Variant) - 100 percent copper wound Electolyic Grade. (x ) Losses - As per IS Norms. (y) Power Factor - Not less than 0.99 (z) Protection :- (i) Over load protections. (ii) Short circuit protection (iii) High /low voltgae cut off (iv) By pass arrrangement faciltiy in case of emergency (v) Single phase sequence change /phase fail protection (vi) Earth fault protection (aa) Standard fitrting & Accessories e.g. Marking plate, lifting lugs, CI rollers, Earthing terminals etc cable box including first fill of oil included on the quoted rate. Note: (i) The new voltage stabilizer installed inside existing building, the necessary lifting arrangements i.e Hydraulic crane/lifter, transporting of 100 KVA servo stabilizer from factory to Dayalchak ASCON Node site that situated the hilly area near Dayalchak Sidi Gori Baba Mandir area including on the quoted rate. (ii) The rate included for disconnecting the existing cables and connections from BER Stabilizer and re connect with new stabilizer and checking load balance including on the quoted rate if extra cable requiered it will me measured and paid relevent item of schedule. | ||||||
| 5.00 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.15 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS control cable of adequate size (minimum 1.5 sqmm 4 core), CT for all incoming and outgoing MCCBs as per switchgear capacity CT ratio recommended by CPRI including required civil works/anchoring bolts for fixing, PCC foundation 1: 3:6 type C-2 using 40 mm graded stone as in foundation filling mass concreting et etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade Aluminium shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection same size bus bar of all switch gears , fixed on DMC insulators and provision of extension.(Location: Dayalchak & Samba Military station inside) | 5 | Each | 1,57,025 ₹7,85,125 | 1,70,600 ₹8,53,000 | 1,55,000 ₹7,75,000 Lowest |
| 5.01INCOMER : (i) MCCB 350 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed 01 Nos. (ii) Multifunction meter = 01 set. (ii) Phase Indication lamps (RYB), LED type - 01 No (set of three). | ||||||
| 5.02Outgoing : (a) (i) MCCB 160 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 04 Nos (ii) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed - 02 Nos. (iii) LED indicator set of three -06 Nos | ||||||
| 5.03(i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) CPRI certificates short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA. (iii) CPRI certification rated current for short circuit not less than 5000A. (iv) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be submitted by contracotr for got approved from GE (samba) before fabrication. (vi) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. | ||||||
| 6.00 | Labour and Hydraulic lifter with transporting vehicle for shifting of unserviceable voltage stailizer 100 KVA from Dayalchak ASCON Node near Sidhi Baba Mandir dayalchak hill and deposit to GE Samba office Store yard all as specified and directed by Engr-in-Charge. | 1 | Each job | 10,000 ₹10,000 | 5,000 ₹5,000 Lowest | 5,000 ₹5,000 Lowest |
Tender Value
₹25.3 L
EMD Value
₹50,680
Closing Date
12 Aug 2026, 6:00 pmClosed
GE SAMBA
GE SAMBA PIN 184121
PROVN OF WATER AND ELECTRICITY CONNECTION IN OTM ACCN 02 HIGH MAST SECURITY LIGHTS IN KHETARPAL LINES AND SPL REPAIR REPLACEMENT OF BER VOLTAGE STABILIZER AT ASCON NODE DAYALACHAK UNDER GE SAMBA
2026_MES_778634_1
8166/GE/SMB/T-43/2026-27
Open Tender
Miscellaneous Works
Item Rate
180 days
GE SAMBA
Class D Cat a ii and b i
8 documents required · 8 mandatory
₹500
GE SAMBA
₹50,680
Yes
5 Sept 2026
15 Jul 2026
14 Aug 2026
15 Jul 2026
12 Aug 2026
29 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, laying and testing of XLPE electric power cable insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty ) 1100 volt grade with stranded aluminium conductor of size 95 sqmm, 3.5 core complete all as specified and directed.
Note:- There is no earth work the cable drawn inside HDPE pipe inside building. | 75 | RM | 100 | ₹7,500 |
| 2 | M & L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI earth galvanised iron strip of size 32×6mm and 40 mm dia bore light grade GI protection pipe for earth strip and GI watering pipe 20 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009 complete all as specified and directed.
Note:-
For LT Voltage stabilizer - 01 x 04 = 04 Nos
For LT Panel - 05 panel x 02 Earthing = 10 Nos
For High mast light - 02 Nos
High mast light control panel - 02 Nos | 18 | Each Set | 102 | ₹1,836 |
| 3 | S & L HDPE pipe PN -10 of 100 mm bore for protection of LT cable | 50 | RM | 102 | ₹5,100 |
| 4 | Supply, Installation, Testing and commissioning of Servo Controlled Voltage stabilizer of capacity 100 KVA confirming to BIS 9815 (Part-I): 1994, reaffirmation 2019 latest version, Three phase, four wire (RYBN), 50 Hz, Naturally oil cooled, indoor, unbalanced type, copper wound, metallic body duly poweder coated with lifting hooks two nos, digital display, relay free smooth and silent operation with display type, relay free smooth and silent operation with 1st filling of Transformer oil up to level having following specifiaction:-
(a) Capacity of Servo Voltage Stabilizer - 100 KVA.
(b) Type - Suitable for unbalanced load and unbalanced input.
(c ) Input voltage - 360 Volts to 480 Volts, Input frequency 50 HZ.
(d) Output voltage - Stabilized at any designed/desired voltage 415 ± 1%
(e) Rated frequency - 50 Hz.
(f) Wave form distortion -NIL.
(g) Response time - not to exceed 20 Milliseconds.
(h) Sensitivity - ± 1%
(j) Rate of correction - Not less than 6 Volt/second between phase and netural.
(k) Efficiency - more than 95 %
(l) Type of load - Three phase, unbalnced type.
(m) Metering - Digital display voltmeter / Ammeter with multifunction meter.
(n) Operating temperature-For indoor use upto max ambient temperature + 55° C.
(o) Dimmer rating - Min 140 Amps max 200 Amps.
(p) Dimension of tanks - As per IS standard.
(q) Oil capacity - As per IS standard and manufacturer recommendation. | 1 | Each | 104 | ₹104 |
| 4.01 | (r ) Class of Insulation - Class F
(s) Mode of operation -Automatic /Manual
(t) Winding Temperature rise - Max 55° C (10° C above operating temperature)
(u) Transformer oil - IS 335 marked.
(v) Core _ CRGO M4 Grade/GRNO (Cold Roll Grain oriented)
(w) Auto Transformer (Variant) - 100 percent copper wound Electolyic Grade.
(x ) Losses - As per IS Norms.
(y) Power Factor - Not less than 0.99
(z) Protection :- (i) Over load protections.
(ii) Short circuit protection
(iii) High /low voltgae cut off
(iv) By pass arrrangement faciltiy in case of emergency
(v) Single phase sequence change /phase fail protection
(vi) Earth fault protection
(aa) Standard fitrting & Accessories e.g. Marking plate, lifting lugs, CI rollers, Earthing terminals etc cable box including first fill of oil included on the quoted rate.
Note: (i) The new voltage stabilizer installed inside existing building, the necessary lifting arrangements i.e Hydraulic crane/lifter, transporting of 100 KVA servo stabilizer from factory to Dayalchak ASCON Node site that situated the hilly area near Dayalchak Sidi Gori Baba Mandir area including on the quoted rate. (ii) The rate included for disconnecting the existing cables and connections from BER Stabilizer and re connect with new stabilizer and checking load balance including on the quoted rate if extra cable requiered it will me measured and paid relevent item of schedule. | - | - | - | - |
| 5 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.15 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS control cable of adequate size (minimum 1.5 sqmm 4 core), CT for all incoming and outgoing MCCBs as per switchgear capacity CT ratio recommended by CPRI including required civil works/anchoring bolts for fixing, PCC foundation 1: 3:6 type C-2 using 40 mm graded stone as in foundation filling mass concreting et etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade Aluminium shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection same size bus bar of all switch gears , fixed on DMC insulators and provision of extension.(Location: Dayalchak & Samba Military station inside) | 5 | Each | 104 | ₹520 |
| 5.01 | INCOMER : (i) MCCB 350 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed 01 Nos. (ii) Multifunction meter = 01 set. (ii) Phase Indication lamps (RYB), LED type - 01 No (set of three). | - | - | - | - |
| 5.02 | Outgoing : (a) (i) MCCB 160 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 04 Nos
(ii) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed - 02 Nos.
(iii) LED indicator set of three -06 Nos | - | - | - | - |
| 5.03 | (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) CPRI certificates short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA. (iii) CPRI certification rated current for short circuit not less than 5000A. (iv) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be submitted by contracotr for got approved from GE (samba) before fabrication. (vi) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. | - | - | - | - |
| 6 | Labour and Hydraulic lifter with transporting vehicle for shifting of unserviceable voltage stailizer 100 KVA from Dayalchak ASCON Node near Sidhi Baba Mandir dayalchak hill and deposit to GE Samba office Store yard all as specified and directed by Engr-in-Charge. | 1 | Each job | 111 | ₹111 |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.45 MB
BOQ_872092.xls
BOQ • 5.96 MB
TenderDocumentsT43.pdf
Tender Documents • 1.01 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .