Executive Engineer (Electrical Tender)
O/o Sr. Chief Engineer (Electrical), BSNL TamilnaduElectrical Zone, 5th Floor Tamilnadu Telecom Complex,No.60,EthirajSalai,Chennai - 600008
Replacement of 1x1250 KVA (11KV / 433V) Dry Type Transformer at D Tax Bldg. Trichy(2nd Revision)
2025_BSNL_259891_1
82/CEE/TNEZ/CH/2025-26
Open Tender
Electrical Goods/Equipment
Item Rate
60 days
Trichy
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹73,035
9 Jan 2026
20 Dec 2025
2 Jan 2026
20 Dec 2025
1 Jan 2026
20 Dec 2025
Part A: Supply Supplying of 1250 KVA 3Phase, 50HZ, self cooled (air natural) cast resin dry type indoor transformer double wound for voltage ratio of 11KV / 433V, between phases, at no load and arranged for Delta / Star connection as per vector group Dyn11 with the neutral brought out on star side with matching percentage impedance, voltage ratio and vector group etc.of the existing transformer, (details attached) with provision for connecting cable on HV side & bus duct on LV side with enclosure and all standard fittings etc.,as per attached specifications complete as required.
Part B: ITC Installation, Testing & Commissioning of the above transformer at the specified location giving connection with the existing cable/bus duct on HV/LV side respectively and checking with exchange load complete as required i/c liaisoning work with TANGEDCO, electrical inspector, preparation of drawings for getting approval etc as per specifications.
Dismantling the existing life expired / faulty 1250 KVA Transformer i/c disconnecting from the cables/bus duct, earth connections, control wiring etc and shifting the same to the location specified by the Engineer-in-Charge complete as required.
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.64 MB
BOQ_300492.xls
BOQ • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .