EE ECWD MORADABAD
220 KV SUB STATION MANJHOLA MORADABAD
For Increasing Capacity of 33 11 KV S S Jamuna Khas District Amroha from 2 INTO 5 MVA to 10 PLUS 5 MVA under the business plan scheme 2022 23 IN THE JURISDICTION OF ECWD MBD
2022_PVVNL_685719_1
01/ECWD(M)/2022-23
Open Tender
Electrical Works
Lump-sum
30 days
AMROHA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE ECWD MORADABAD
₹7,000
28 Apr 2022
7 Apr 2022
27 Apr 2022
7 Apr 2022
27 Apr 2022
7 Apr 2022
90 days
1. Safe carriage of following stock material, from Store Center of PPVNL to site of 33/11KV S/S Jamnakhas (Amroha). (Distance approx.- 150Kms.):for Item No. 1.01 to 1.02 1.01 – Switchyard items and other materials, such as Isolator 11KV cable jointing kit, control cable, ms channel, ms angle.
11KV Alumn. Cable XLPE- 3x300
2. Safe carriage of following stock material, from Store Center of PPVNL to site of 33/11KV S/S Jamnakhas (Amroha). (Distance approx.- 150Kms.): for Item No. 2.01 to 2.02 2.01 – 33KV Control panel for double T/F
24 Volt Battery & Battery Charger
Providing & laying of G.I.Strip of size 50x6mm for connecting the earthmat with each equipment 10MVA body, 10MVA Nutral, cable stand and double transformer control panel. The work also includes cutting, bending, straightening, over laping and welding the earth strip with earth mat and by using high quality arc welding in already digged trenches, as per PVVNL guidline.
Boring and lowering by providing of G.I.Pipe size 40mm dia, into the ground upto water level or minimum 80Mtr, which ever is more, with the lower end of solid copper cone Approx 224mm long and 750gm in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG, from the cone upto the ground surface where it will be bolted to the G.I. Strip for Transformer neutral connection. Transformer body connection and double transformer control pannel structure (required G.I strip of 50x6mm provided by contractor) the G.I.Strip will be connected to star point through providing Copper Bond Strip of size-35x6mm, as per PVVNL guidline.
Mounting & fixing of following outdoor equipments, on single Bay, by providing Bolt, Nuts &Washers. As per Respo norms & PVVNL guidline. 5.01–Erection of 01 No. 33KV Double T/F control panel in alignment in control room, including safe shifting from dump place making 4 Nos. Pockets for each and providing/fixing of Teg Bolt by CC in ratio 1:2:4, with tightening also.
Safety/Dragging/lifting of 33/11KV, 10MVA T/F on Plinth from the unloaded place.
Erection of 33/11KV, 10MVA Power T/F on Plinth, by fixing all accessories, like Radiators, Conservator Tank, Filling the T/F Oil to desired level and ensuring that there is no leakage, complete job in all respect. As per PVVNL guidline.
Digging of Trench of size 0.45x0.6M., for laying of 11KV Cable for incoming/outgoing feeder and T/F.
Laying of 11KV XLPE 3x300Sq.mm. Alumn.Cable in the Trench, for T/F and I/C pannel at Control Room. As per PVVNL guidline & actual site conditions.
providing & laying of Ist Class Bricks on both sides and on Top of the Cable. Filling the Sand, inside the Bricks and refilling of loose earth in the Trench. As per PVVNL guidline & actual site conditions.
Making of joints by 11KV (3x300Sq.mm) Heat Shrink type Jointing Kits, Indoor/Outdoor type, providing & fixing of Alumn. Lugs of proper size, by crimping on each phase of the Cable at both ends.
Fixing of Cable Box on 10MVA T/F, 11KV Switchgears, by Bolt & Nuts and tapping the joints by providing HT/Empire/PVC Tape and Copper Strip of size 50x6mm., 75mm.long, including proper tapping.
Providing & Laying of Control Cable in Packka Trench, from VCB/CTs/T/F to 33KV Control Panel and making connection for operation & protection of equipments, by using ferrules including commissioning battery charger with battery by providing copper lead with lugs & dressing of Control Cable and making arrangement for testing in the equipments. (Control cable provided by the contractor)
Assembling and installation of the cabinet of 24 volt battery and battery charger including grouting of foundation bolt as per manufacturer drawing in control room including safe shifting. The electric connection between battery and battery charger with flexible copper lead of size 7/20SWG shall be done properly. The work including wireing upto control pannels, testing & commisnoning in al respect as per pvvnl guidline.
Providing & fixing 1 No. MCB Box 63amp. TPN and 03 No. 32 Amp. SPN box and power plug on wall and it is proper grouting including it is connection with A/C supply by providing proper size of connection wire.
Fabrication of M.S frame for support of 11KV cable stand as per RESPO..:for Item No.16.01 tp 16.04 16.01 - Fabrication of structure including cutting & straightening of niling of holes & electric welding to raise the height of Neutral link structure.
Fabrication of structure including cutting & straightening of niling of holes & electric welding to raise the height of cable stand structure.
Fabrication of structure including cutting & straightening of niling of holes & electric welding to raise the height of L.A Structure.
Excavation of earth (0.60x0.30x1.00m) grouting with C.C in ratio 1:4:8 (0.60x0.30x1m) of Neutral stand & cable stand.
Painting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Alumn. Paint after rubbing with sand paper to the surface of the structure includidng labour and T&P complete in all respect.:for Item No.17.01 tp 17.05 17.01 – Line Isolator Structure
Fuse Set Structure
Post Insulator, L.A.Structure
V.C.B.Structure, C.T.Structure
M.S.Frame for Cable
Draining of oil from conservator, radiators of existing 5MVA T/F, at 33/11KV S/S Jamnakhas (Amroha), into the dry & clean drums and staking at the safe place at 33/11KV S/S Jamnakhas (Amroha).
Dismantling of conservator, radiators and other accessories from existing 5MVA Transformer.
Shifting of 5MVA Transformer main body and other accessories from the substation switchyard to outside the switchyard.
Dismentling of defective 01 No. single transformer control panel and 01 no. single feeder control panel after safety disconnecting the control cables of different sizes and single transformer control panel and single feeder control panel safe place of control room as per PVVNL guidlines.
Reconnecting the different sizes of control cable to newly erected 01 no. double transformer control panel safely and insure overcurrent, earthfoult current, OTI, WTI, buceholz trip and alram shows on control panel for both power transformer of S/S as per power transformer safety norms.
Hiring of D/G Set, including carriage, loading, unloading & operating charges (with fuel) at 33/11KV Substation, :for Item No.23.01 to 23.02 23.01 – 20 KVA, 3 Phase D/G Set for testing of equipments installed at Sub-station.
5 KVA, Single Phase D/G Set for testing of equipments installed at Sub-station.
Providing required No. of Technicians to work on power T/F, HT/LT Panels, during testing as assisting technical hands of test team during commissioning & energisation.
M/S SARLOK SERVICES
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .