Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.3 LAccepted-AOC 362 SUBHASH NAGAR PO CLEMENT TOWN DEHRADUN UTTARAKHAND | L1 | Accepted-AOC Lowest | |
| 2 | L2₹36.8 L+₹3.5 L (10.5%)Rejected-AOC | L2 | Rejected-AOC Not Lowest | |
| 3 | L3₹38.0 L+₹4.6 L (13.9%)Rejected-AOC | L3 | Rejected-AOC Not Lowest | |
| 4 | L4₹39.1 L+₹5.8 L (17.4%)Rejected-AOC | L4 | Rejected-AOC Not Lowest | |
| 5 | L5₹41.1 L+₹7.8 L (23.3%)Rejected-AOC GANDHI CHOWK LANSDOWNE DISTT PAURI GARHWAL PIN 246155 | PAURI GARHWAL | UTTARAKHAND | 246155 | L5 | Rejected-AOC Not Lowest |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
16 Aug 2021, 6:00 pmClosed
CWE HILLS DEHRADUN
HQ Commander Works Engineers Hills Mall Road Dehradun Cantt Dehradun 248003
PROVN OF 125 KVA DG SET FOR POWER BACKUP TO STATIC OXYGEN GENERATING PLANT AND MEDICAL EQPTS OF HOSP COMPLEX COVID 19 WARD DEPTS ICU OT 50 KVA SERVO VOLTAGE STABILIZER NEW CONNECTION OF OXYGEN PIPE FOR 33 BEDS AND BOOSTER COMPRESSOR UNIT 150 BA
2021_MES_463467_1
87060/LDN/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
AGE I LANSDOWNE
Class D category b i
6 documents required · 6 mandatory
₹500
AGE I LANSDOWNE
₹90,000
24 Aug 2021
28 Jul 2021
18 Aug 2021
29 Jul 2021
16 Aug 2021
11 Aug 2021
29 Jul 2021 - 4 Aug 2021
Amount
Sch A Part-I
Supply insttallation commmissioning and testing of silent diesel engine drive factory assembled floor mounted, Generating set of capacity 125 KVA, 3 phase, 4 wire, 50 HZ, 1500 RPM complete with safety control and metering equipment mounted on common base frame on new PCC foundation required at site and as recommended by manufacturer, complet all as specified and as directed comprising of the following.
(A) Prime Mover directly coupled, diesel engine tubo charged water cooled suitably de-rated of matching BHP for driving 125 KVA capacity alternator electric start, four stroke, 1500 RPM conforming to IS-10000 part -II, 1980, IS10001/10002 for continuous running and capable for taking 10% overload for one hour complete with the following accessories:-
Fly wheel to suit flexible coupling
Flexible coupling with guard
Air cleaners both oil type/dry type with filters
Lubricating oil filter, fuel filter, fule pre filter
Blower type fan
Fule injecting system with injection pump, nozzles, governer (Electronic) of sutable capacity
Electric start equipment
Lead acid storage maintenance free battery 12 volts of rating 180AH (02 Nos) with charging, alternator, ammeter, as recommended by manufacturer make : Exide alongwith copper battery lead and connector.
Battery rack made out of MS angle iron 40mm x 40mm x 5mm & 150mm height.
Standard safety device libe.
Fule tank of suitable capacity for minimum 08 hrs run with mechanical lever indicator, as per manufacturers specification detachable, strainer, drain cock, fuel outelet, air vent and locking arrangement etc, including fuel pipe conncections.
Exhaust silencer (Residental silencer) with exhaust piping of sitable size brought out side on top of size 76.5 mm dia and complete length of silencer and exhaust piping continuosly wrapped with 12 mm dia asbestos rope and suitable anti-vibaration arrangement around pipe passing through wall.
LED display type control panel as per manufacturere's instructions indicating KWH, KVA, PF Volts, Amps, HZ, RPM Hour, oil pressure, oil temperature, coolent temperature fuel level battery charging ammeter, battery charging lamp and indicator lamp (RYB), panel duly per wired and displaying protection and safeties as under:-
Protection :- Short circuit, over laod, over speed, earth fault as standard and reverse power as optional.
Safeties :- Auto shut down, visual & audio alarm for low lub oil pressure, high coolant temperature, low fuel lavel, canopy temperature & radiator water lavel.
(B) Alternator 125 KVA brushless type at 0.8 power factor, self regulated, self excited, screen protected 3 phase with neutral 415 volts 50 Hz, 1500 RPM, as per IS : 13364/ IS : 2613/ IS-4722 complete with automatic voltage regulator, having voltage regulation +/-1%, SPDP encloser including making cable, connections, insulation class - H, permanent lubricating bearing, permissible overloading upto 10% for one hour, permissible unbalancing capability minimum 25% per phase and alternator control panel as supplied by manufacturer.
(C) AMF CONTROL PANEL:- As per manufacturer's design with the following options: (a) Start/ stop settings including delay and timing setting duly programmable. (b) programmable timing for idle running . (c) Auto/ manual option. (d) Self starting kiks for three times or as per programme . (e) Alarm for any fault with buzzer and indicating lamp . (f) One main supply voltage monitor . (g) One alternator supply voltage monitor . (h) One set of DC control relays and timers. (j) One set of control relays for the automatic control system .
(D) Base frame sturdy, MS febricated, channel iron base freame for mounting the engine & alternator with anti vibration pads.
(E) Acoustic encloser of suitable size to accommodate DG set 125 KVA, modular constuction, febricated out of 3mm tihick, cold annealed CRCA sheet duly epoxy painted doors to be provided with high quality EDPN gasket, duly epoxy painted. The canopy to be equipped with heavy duty with heavy duty fancs of reputed manufacturer for air circulatiion and cooling the canpy. Rock wool of requiste denesity per Kg M3 to be used for insulation. Enclosure to be provided with one light point controlled with one switch for internal lighting. Noise level at one meter to be 75 decibels@ one mtr. in line as per CPCB norms. Make:- Jackson/Greaves Power/Cummins/KIRLOSKAR GREEN
(F) FOUNDATION:- Foundation of the DG set (PCC/RCC) will be provided by the contractor and will be made as per the manufacturers instruction. Cost of foundaton is deemed to be included in the rate of this item. (Make of Engine:-Cummins/Kirloskar oil engine/ /Greaves Cotton/Perkins/Caterpillar (FGW) (Make of Alternator:- Kirloskar electric/Stamford/Jyoti/BHEL/CROMPTON GREAVES
NOTE :-(a) The engine of DG set suitably conditioned to suit the climatic condition of Landowne (UK) station, so as to give desired outputs including and testing up to 10% over load. (b) The items required for testing of DG set e.g. fuel, tripod, tools , water tank etc. and panel shall be provided by the contractor and the rate of which is deemed to to be included in the rate of this item. Testing of DG set will be carried out as specified. (c) Generating set will be placed on suitable foundation as recommended by manufacturer and cost thereof shall be included on the prices quoted . (d)Tools shall be supplied as per manufacturer,s instructions and cost thereof shall be included in the price quoted . (e) DG Set shall be placed at the site directed by Eng-in-charge which can be upto 20 meter from the road. (f) Testing of DG set shall be done as per relivant clause of PS.
Supply & laying cable XLPE insulated PVC sheathed, galvanised steel strip armored. Electric power cable (heavy duty) 1100 V grade with stranderd aluminium conducter of size 95 Sqmm 3.5 core complete all as specified and directed.
Supply & laying cable XLPE insulated PVC sheathed, galvanised steel strip armored. Electric power cable (heavy duty) 1100 V grade with stranderd aluminium conducter of size 150 Sqmm 3.5 core complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtr wide and not exc.1.5 mtr in depth for poles /laying of electric underground cables and GI tubing (where provided for protection of cables) and getting out trimmimg the sides, forming bottom surface to required level in any type of soil complete all as specified and directed.
Returning , filling in including spreading leveling, watering and well ramming in layers not exceeding 25 cm thick with excavated soil complete all as specified and directed.
M&L for fine dry sand cushing for under ground cable by providing layers of sand 8cm deep before laying and 15cm deep after laying the cable including streching the cable complete all as specified and directed . Note:- Punned (consolidated ) thickness of sand will be measured .
M&L for well burnt bricks sub class 'B' in old size as cable protection laid flat width wise complete all as specified and directed.
Removing excavated material (surplus soil) to a distance not exceeding 50 mtrs and depositing where directed at a level not exc 1.5 m above the starting point all as specified and directed.
Supply and laid 80 mm GI light grade pipe for cable protection complete all as specified and directed.
Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 300 Amps for each phase and 200 amps for Neutral. Maximum current density 1.6 Amps/Sqmm, including interconnection of all switch gears, fixed on DMC insulators and provision of extension. Make of Panel :- ABB/Schneider/ Universal switch gear/Tenco systems and switch gears Pvt Ltd Indore.
Outgoing:- (i ) MCCB 160 amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%Icu(1 sec) complete all as specified and directed - 01 Nos (ii) S&F 10 KA 'C' curve miniature circuit breaker (MCB) of single poles and Neutral current carrying capacity 40 AMP, ISI marked, 240 Volts, 50 Hz in the panel and connecting the cable with suitable size of copper lugs Complete with connection testing and commissioning complete all as specified & directed.
Notes for Item No 10 :- 1. Panel manufacturers should have in house powder coating plant with minimum 8 tank pretreatment of MS sheet facilities, dust free spray paint booth.(8 tanks pretreatment process includes: degreasing/water rinsing/de-dusting/water rinsing/activation/phosphating water rinsing/passivation). 2. Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel 3. The panel manufacturer should have following certification: (i) CPRI certification degree of protection IP-54 ( should have IEC:61439-1-2 & IEC:60529 tests) (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA (iii) CPRI certification rated current for short circuit not less than 5000A 4. All the electricals switch gear like MCCBs, MCB should be of same make 5. Drawing of panel board should be got approved from AGE(I) before fabrication. 6. Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.
M& L, for earthing with galvanised steel earth plate of size 600 x 600 x 6 mm thick burried directly in ground not less than 2.5 mtr below groud level with top edge of earth plate not less than 1.5 meters below ground level connected by 32x6 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate including concrete chamber of PCC 1:3:6 type C1 using 20 mm graded stone aggregate, with fair finish, inetrnal surface of concrete chamber shall be given internal dia 300mm X 300mm , 15 mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 mm size (1:2:4) type B1 using 20 mm graded stone aggregate, all, as shown in electrical plate No 3 of MES SSR Part-1 (2009) and specified incuding and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, Medium grade, including all excavation and earth work and connecting the earth strip to an earthing test point/panel including testing on completion complete alll as specified and directed by Engr-in-charge Note:- (1) RCC pit cover shall be precast of RCC (1:2:4) type B1, 80 mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover (2) Cost of addtional GI strip more than 7.5 mtr will be measured and paid seperately under relevant item
Material & Labour for Point Wiring for one light Point/one fan point/ one call bell point, controlled by one switch with 1100 volts grade single core conforming to (IS:694 /1990) PVC insulated unsheathed 1.5 sqmm multi stranded copper conductor cable (FRLSH) with contineous earth wire of 1.5 Sqmm stranded copper conductor cable (FRLSH) PVC insulated unsheathed , drawn in and including concealed rigid PVC conduit (ISI marked), duly concealed to wall/floor or above false ceiling with fittings(ISI marked) not less than 20 mm dia (Color coding of wires shall be Phase, neutral and earth wire all as specified ) sunk Metal flush box with and incl decorative polycarbonate frame for housing Modular Switches, sockets , fan regulators etc including white cover cover plate, Make of cable: Finolex/RRcable Make of conduit AKG/PRESTOPLAST/PRECISION complete all as specified and directed.Note:- Flush box and cover plate should be of same make all as approved for switches/sockets.
All as per item No 13 above but wiring with 2.5 sqmm conductor for phase and neutral & 2.5 Sqmm copper conductor as earth continuity for one 15/16 Amps socket on independent board Complete all as specified and as directed .Make of cable: Finolex/RRcable Make of conduit AKG/PRESTOPLAST/PRECISION Note:- Flush box and cover plate should be of same make all as approved for switches/sockets.
S & F switch Modular single pole, one way 6 Amps , 1 module, 230 volts, 50 hz all as specified and directed by Engr-in-Charge.Make: Legrand cat No: 6734 01/ Indoasian Cat No: 800000 or equivalent make of L&T/Havells
Supply and fix Modular switch 1 way 16 Amps, 1 module, 230 volts, 50 hz white/ivory finish all as specified and directed by Engr-in-Charge. Make: Legrand cat No: 6734 11/ Indoasian Cat No: 800002 or equivalent make of L&T /Havells
Supply and fix Modular Socket outlet, 6A - 2/3 pin combined, 2 module ISI marked, 230 volts, 50 hz all as specified and directed by Engr-in-Charge.Make: Legrand cat No: 6734 52 / Indoasian cat no: 800020 or equivalent make of L&T/Havells
Supply and fix Socket outlet, modular type 6/16 Amp -3 pin, 230 volts, 50 hz, ISI marked complete all as specified and directed by Engr-in-Charge.Make: Legrand cat No: 6734 55 / Indoasian cat no: 800022 or equivalent make of L&T/Havells
S&F LED tube light batten 20 Watt, 4ft, Polycarbonate housing, translucent diffuser, With LED Light Source, 2200 Lumens, natural White, Surge Protection range- 2KV, Voltage Protection range – 120 -280VAC, 2 years warranty , System efficacy not less than 110Lm/Watt for the fitting, power factor >0.95, total harmonic distortion<20%, Color rendering index >80, Coefficient Colour Temperature – 6500K, Fixed on site with all accessories all as specified & directed. Cat No: SZSLBMX020 of shakti Cat No, LDL 20 CDL of crompton or equivalant in Havells, Wipro and LM 79 & LM 80 Reports to be produced. BIS Certification must.
Sch A Part-II
Supply, Installation, Testing and Commissioning of Indigenous oxygen manifold of 2 banks of 4 cylinders each suitable to withstand pressure of 145kg/Cm size (100Kg cap) complete alongwith 08 nos copper annealed with end brass adaptor suitable for oxygen cylinders, manifold should have top,middle and bottom frames made out of high pressure copper pipes of suitable size high tensile brass fittings and connections, pig tail pipes & 08 nos of non return valves etc and hydraulically tested at 3500 Psi complete all as specified and directed. Make:- Competent Medical system(India)Pvt Ltd/PES Installation India/Medical Product service (MPS)/Bangla sahib/AKTIV/GHL
Supply, Installation, Testing and Commissioning of Indigenous emergency oxygen manifold of 2 banks of 2 cylinders each suitable to withstand pressure of 145kg/Cm size (100Kg cap) complete alongwith 04 nos copper annealed with end brass adaptor suitable for oxygen cylinders,manifold should have top, middle and bottom frames made out of high pressure copper pipes of suitable size high tensile brass fittings and connections, pig tail pipes & 04 nos of non return valves and pressure regulating system etc and hydraulically tested at 3500 Psi complete all as specified and directed. Make:- Competent Medical system(India)Pvt Ltd/PES Installation India/Medical Product service (MPS)/Bangla sahib/AKTIV/GHL
Supply, Installation, Testing and Commissioning of Fully-Automatic Oxygen control Panel 1200-1500 LPM gas flow at 4 Bar pressure outlet pressure with regulators, automatic switchover system from running to reserve, pressure gauge to indicate cylinder pressure, indication lamp for signal on changeover auto alarm saftey switches and built in transformes for low voltage operation etc fully complies and meets with HTM 02-01, C11, standards and should be duly CE maked complete all as specified and directed. Make:-ACTIV/MECPL/GHL .
Supply, Installation, Testing and Commissioning of OXYGEN outlets with matching stainless steel probe/adaptor.Fully compllies and meets with HTM02-01, C11 standards and should be dully CE markes all as specified and directed. Make:- MECPL/AKTIV/GHL
Supply, Installation, Testing and Commissioning of indigenous OXYGEN flow meter with humidifier bottle made out of brass materials and shall be accurate gas flow measurement and control within a rang of 0-15 litres per minute and flow tube & shroud components are made of clear impact resistant polycarbonate material, the humidifier bottle shall be made of unbreakable polycarbonate material and autoclavable at 134 degree centigrade complete all as specified and directed. Make:- Radix/Competent Medical system(India) Pvt Ltd/PES Installatin india/Medical product Service(MPS)/MEDILINE/MECPL/GHL
Supply, Installation, Testing and Commissioning of oxygen H.P antistatic tube all asspecified and directed. Make:- BANGLA SAHIB/GHL
Supply, Installation, Testing and Commissioning of copper pipe medical grade, seamless, fully degreased and half hard (designed to R 250), deoxidised, non arsenical tempered all as conforming to BS : EN 1057 : 1996 & BS : EN 13348 for following dia pipes including copper fittings cinforming to BS : EN 1254-1 suitable for steam working pressure of 17 bar specially made for brazed socket type connections all as specified and directed. Make:- Pricision UK/LLOYD/Nanda Metal Tune(I) pvt Ltd Baroda/Maxflow/Mehata tubes Ltd. Note:- Copper pipe line is to be installed/Brazed as per HTM 02-01 guide line.
35mm OD*1.2 mm thick
28mm OD*1.0 mm thick
22mm OD*0.9 mm thick
15 OD* 0.9 mm thick
12mm OD*1.0 mm thick
Supply, Installation, Testing and Commissioning of Indigenous zonal valve box with isolation valve 1 services complete all as specified and directed. Make:- competent medical system India Pvt Ltd/Prime automattion/Pes Installation India Pvt Ltd/MPS/MDd/Rodix/ACTIV
Supply and fix ball valve of non lubricated 90 degree turn lever with FTFE seat having opening seat, having opening by quarter turn of handle and shall be pneumatically tested for twice the working pressure and degresed for oxygen gas supply suitable for complete all as specified & directed. Make:- BONOMY/A/AKTIV/CIM/RIB
Supply, fix, testing and comissioning automatic digital dual supply and one outlet axygen gas change over, made out of MS Sheet duly powder coated having independent pressure gauges showing incoming and out going gases status with digital pressure reading and micro processor based pressure removers alongwith twin shuttle volve for auto changeover of gas alongwith 03 Nos isolation valves suitable for 500-100 LPM of oxygen flow @ 4 bar max, two no of oxygen regulator and suiltable indication in case of variation in supply / delivery pressure complete all as spacified and directed.
Supply, installation, testing & comission of Indiigenous medical gas alarm panel (post source) with electronic component/ board relays, control switches and LED status indicators including OD alaram on position such as low, medium, high pressure etc. with necessary fixing arrangements as per manufactere's recommedation working on 230Volts AC 50Hz complete all as specified and directed. (Make:- GHL/ MPS/PES/ AKTIV/ Redix/ Bangla Sahib/ GHL/ Tridev Medical)
M/s Kamal Builders
SEEMA ELECTRICAL
Amit Engineering
PIONEER REFRIGERATION AND ELECTRICALS
M/S Electrotech Sales
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .