| 1 | L1₹41.9 LAccepted-AOC DOOR NO 42 2237 KRISHNA BEHIND ERNAKULAM MEDICAL CENTRE CENTURY CLUB ROAD VENNALA KOCHI 682028 | KOCHI | ERNAKULAM | KERALA | 682028 | L1 | Accepted-AOC L1 | |
| 2 | L2₹44.2 L+₹1.7 L (4.10%)Rejected-AOC THEERTHAM NADUVILEMURI PADANILAM POST NOORANAD ALAPPUZHA DIST KERALA 690529 | ALAPPUZHA | KERALA | 690529 | L2 | Rejected-AOC L2 | |
| 3 | L3₹45.2 L+₹2.7 L (6.47%)Rejected-AOC DOOR NO 32 939C 1ST FLOOR CITY SCAPE BUILDING CHANGAMPUZHA NAGAR P O SOUTH KALAMASSERY ERNAKULAM KERALA 682033 | ERNAKULAM | KERALA | 682033 | L3 | Rejected-AOC L3 | |
| 4 | L4₹49.5 L+₹7.1 L (16.7%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | Rejected-Technical NEAR SWAMI SAMARTH MANDIR GROUND FLOOR 28 1 1 D SHIVRAJ NAGAR SAI MIRACLE ROAD RAHATNI PUNE 411 017 | PUNE | MAHARASHTRA | 411017 | - | Rejected-Technical Does not Meets the criteria |
Tender Value
Refer Docs
EMD Value
₹99,800
Closing Date
5 Sept 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE NS KOCHI
Garrison Engineer Naval Services Kataribagh Naval Base Post Kochi 682004.
CERTAIN SANCTIONED WORKS AT NAVAL BASE KOCHI AND NEDUMBASSERY UNDER AGE E/M NO I AGE E/M NO II AND AGE B/R ALWAYE.
2024_MES_652546_3
8338/E8
Open Tender
Civil Works
Item Rate
150 days
KOCHI
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹99,800
Yes
6 Nov 2024
15 Jul 2024
7 Sept 2024
15 Jul 2024
5 Sept 2024
29 Jul 2024
Amount
Material & Labour for dismantling old Centrifugal pump set (Diesel Driven) from Existing PCC Foundation including taking down Suction pipes all accessories and deposited in MES store yard at Kataribagh.
Material & Labour for dismantling old Centrifugal pump set (Electric Driven) from Existing PCC Foundation including taking down Suction pipes all accessories and deposited in MES store yard at Kataribagh.
Material & Labour for dismantling old Jockey pump set (Electric Driven) from Existing PCC Foundation including taking down Suction pipes all accessories and deposited in MES store yard at Kataribagh.
Supply, install, testing and commissioning of End suction pump Centrifugally type confirming to IS -12469, 1988 with bronze impeller, SS shaft mounted on heavy duty bearings suitable to continuous operation with range of operation 0% to 150 % of rated capacity coupled to diesel engine 110 HP, 2150 RPM on a common base frame with coupling, coupling guard foundation bolts & nuts etc suitable for delivery 2850 LPM at 90 metre head including connection with control cable wiring for auto operation of DD pump, battery and fuel tank of 200 Litre capacity with MS stand and fixing in foundation complete all as specified and directed by Engineer-In-Charge. Make Kirloskar model KFE-E1221R-G07 or equivalent in V-Guard/Crompton Greaves.
Supply, install, testing and commissioning of End suction pump Centrifugally type confirming to IS -12469,1988 with bronze impeller, SS shaft mounted on heavy duty bearings suitable to continuous operation with range of operation 0% to 150 % of rated capacity for 440 Volt, 3 phase 50 Hz, coupled to 75 KW/100 HP, 2965 RPM TEFC Sq. cage induction motor on a common base frame suitable for 2850 LPM at 90 metre head including fixing of suitable starter with relay and contactor in the existing LT panel with control cable wiring for auto operation of Fire pump and fixing in foundation complete all as specified and directed by Engineer-In-Charge. Make Kirloskar model DB 80/26 Xe or equivalent in V-Guard/Crompton Greaves.
Supply, install, testing and commissioning of End suction pump Centrifugally type confirming to IS -12469,1988 with bronze impeller, SS shaft mounted on heavy duty bearings suitable for automatic operation with nonover loading power characteristics for frequent start / stop operation for 440 Volt 3 phase, 50 Hz coupled to Kirloskar make 11 KW/15 HP, 2925 RPM TEFC Sq. cage induction motor on a common base frame suitable for 180 LPM at 90 metre head including suitable starter with relay and contactor fixed in the existing LT panel board with control cable wiring for auto operation of jockey pump and fixing in foundation complete all as specified and directed by Engineer-In-Charge. Make Kirloskar model DB 32/26 Xe /Crompton Greaves/V-Guard.
Supply, installation, testing and commissioning of Fire Alarm control panel complying with BS EN 54 single Loop panel of capacity from 99 detectors & 99 Modules & up to 200 detectors and modules (per each loop) complete all as specified and as directed
Supply, installation, testing and commissioning of Addressable type repeater Panel complete all as specified and as directed.
Supply, installation, testing and commissioning of Control Module complete all as specified and as directed
Supply, installation, testing and commissioning of detectors complying with and type certified to EN - 45 Addressable type multisensory detectors with heat and smoke with combination
Supply and fix Remote response indicators complete all as specified and directed
Supply, install, testing and commissioning of Addressable Manual Call Point re-settable type complete all as specified and directed
Supply, installation, testing and commissioning of Addressable electronic Sounder cum Strobe complete all as specified and directed
Supply, install, testing and commissioning of PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sqmm, 2 core, 1100 Volts grade for circuit connection of detectors all as specified and directed
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre depth and getting out in hard/dense soil for laying of cable all as specified and directed by the Engineer-in-Charge
Material and labour for riddle sand cushioning for underground cables complete all as specified and as directed by the Engineer-in-Charge. (Note: Punned thickness shall be measured & paid for the Measurement purpose)
Returning, filling of soil including spreading leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by the Engineer-in-Charge.
Material and labour for un-reinforced precast concrete cable cover Class LV, Type I, flat, size 250x150x40mm complete all as specified and directed
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level, not exceeding 1.5 metre above the starting point complete all as specified and directed by the Engineer-in-Charge
Material & Labour for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nut bolt etc, of size 40mm dia complete all as specified and directed.
Material & Labour for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nut bolt etc, of size 50mm dia complete all as specified and directed.
Supply, install, testing and commissioning of Fire Alarm Sirens Electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Metre with sound output variation of +5 DB, range up to 1500m including proper mounting and protection covering complete all as specified and as directed.
Supply and Fix modular switch 1 way 16 Amps, 1 module 230 Volts, 50Hz, including mounting enclosure ISI marked complete all as specified and as directed
Supply & Fixing sub main wiring with two run of PVC (FR) insulated multistranded copper conductor cable of 4 Sqmm drawing through PVC conduits with continuous earth wire PVC (FR) insulated cable of size 4 Sqmm connected to earth including all conduit accessories complete all as specified and directed. (Note: Two run of sub main wire, one run of earth wire and one run of PVC Conduit pipe measured as one unit).
Supply and Laying UG cable in trenches/passing through pipes/fixed on walls or poles cable XLPE insulated, screened, PVC bedded, steel strip or wire armoured electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 120 sqmm with suitable cable gland complete all as specified and directed.
Material &Labour for earthing complete with galvanized iron or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Metres below ground level) with top edge of earth plate not less than 1.5 Metres below ground level connected to galvanized iron strip 32x6 mm by means of nuts, bolts, thimbles, check nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering funnel with 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point or LT panel etc, and testing on completion, complete all as specified & directed by Engineer-in-Charge.
Cutting existing road/hardstand of any type by using crow bar chisel not exceeding 45cm wide and not exceeding 1.5metre depth for laying GI pipe including making good the surface by returning filling watering ramming in layers 150 mm thick PCC 1:2:4 over 200 mm thick hard core of broken bricks/stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre depth and getting out in soft/loose soil for laying of cable all as specified and directed by the Engineer-in-Charge
Material and labour for common burnt clay building bricks sub-class 'B' designation of size 230X115X75mm complete all as specified and directed
General Servicing, cleaning and checking of Addressable single unit type detectors have a combination of both heat and smoke type detection complete all as directed by Engineer in charge
General Servicing, cleaning and checking of conventional type heat detectors complete all as directed by Engineer in charge
General Servicing, cleaning and checking of addressable module for conventional heat detectors complete all as directed by Engineer in charge.
General Servicing, cleaning and checking of manual push button to initiate audio alarm resettable, intelligent and addressable (Inside office Building) complete all as directed by Engineer in charge.
General Servicing, cleaning and checking of manual push button to initiate audio alarm resettable, intelligent and addressable type enclosed in a flame proof, weather proof enclosure (Inside Hangar) complete all as directed by Engineer in charge.
General Servicing, cleaning and checking of addressable type fire alarm hooter cum strobe complete all as directed by Engineer in charge.
Retrieving of Password from OEM and updating software for Main Addressable fire alarm control Panel including reprogramming complete all as directed by Engineer in charge.
General Servicing, cleaning and checking fault clearing and reprogramming of existing Addressable microprocessor based two loop fire alarm/ detection control panel complete all as directed by Engineer in charge.
General Servicing, cleaning and checking of intelligent active repeater panel complete all as directed by Engineer in charge.
Supply, Install Testing & Commissioning of analogue addressable fault isolator modules including all accessories like junction boxes, glands, terminating legs complete as required and as per specification and NFPA72E compliance RE-717 MI complete all as directed by Engineer in charge.
General Servicing, cleaning and checking of response indicator for addressable detectors which are placed in above ceiling area complete all as directed by Engineer in charge.
Servicing of UV IR flame detector with Ex- proof enclosure, flickering LED indication for normal operation, 24 Volt DC, 4 wire system, 2 for input supply and 2 wire suitable to connect for addressable fire alarm panel complete all as directed by Engineer in charge.
Supply, Install Testing & Commissioning of UV IR flame detector with Ex-proof enclosure, flickering LED indication for normal operation, 24 Volt DC, 4 wire system, 2 for input supply and 2 wire suitable to connect for addressable fire alarm panel complete all as directed by Engineer in charge.
Supply, Install Testing & Commissioning of addressable module for UVIR detector RE 717 M2 analogue addressable zone interface module complete all as directed by Engineer in charge.
Supply, Install Testing & Commissioning of addressable of addressable smoke detector RE 317 DSC analogue addressable smoke detector UL listed complete all as directed by Engineer in charge.
Servicing and testing of High intensity electronic Siren complete all as directed by Engineer in charge.
Supply & Fix FRLS cable Loop testing fault clearing checking and servicing complete all as directed by Engineer in charge.
Green Ray Enterprises (BID ID -3081023)
ALLIES FIRE SYSTEMS PVT LTD (BID ID -3085539)
Archana Enterprises (BID ID -3084416)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .