Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹68.1 LAccepted-AOC CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | 1 | Accepted-AOC Being the lowest bidder. | |
| 2 | 2₹79.4 L+₹11.3 L (16.6%)Rejected-AOC 301 TULSI TOWER KHADAKPADA KALYAN THANE MAHARASHTRA 421301 | THANE | MAHARASHTRA | 421301 | 2 | Rejected-AOC Being other than the lowest bidder. | |
| 3 | 3₹82.1 L+₹14.0 L (20.6%)Rejected-AOC | 3 | Rejected-AOC Being other than the lowest bidder. | |
| 4 | 4₹85.2 L+₹17.1 L (25.2%)Rejected-AOC | 4 | Rejected-AOC Being other than the lowest bidder. |
Tender Value
₹63 L
EMD Value
₹1.2 L
Closing Date
31 Aug 2022, 6:00 pmClosed
CWE Bareilly
HEADQUARTERS, COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, STATION ROAD, BAREILLY CANTT, PIN 243001
SPECIAL REPAIRS/ REPLACEMENT OF HT 4 POLE/ 2 POLE STRUCTURE INTO RMU AND CONNECTED WORK OF JRC FEEDER AND PROVN OF POWER SUPPLY FOR INSTALLATION OF PVMS NO 2510331.5 TESLA MRI SCANNER OF TURNKEY BASIS AT MH BAREILLY UNDER GE (WEST) BAREILLY
2022_MES_531806_2
8100/B/740/E8
Open Tender
Civil Works
Item Rate
180 days
Bareilly
Class C Category b(ii) For Unenlisted Contractor - Meeting enlistment criteria of MES with regard to having satisfactory completed requisite value of work, Annual turnover, working capital , etc as mentioned in NIT.
6 documents required · 6 mandatory
₹1,000
GE ( W ) Bareilly
₹1.2 L
Yes
10 Sept 2022
6 Aug 2022
7 Sept 2022
6 Aug 2022
31 Aug 2022
17 Aug 2022
Amount
Supply, Installation, testing and comissioning of 11KV SCADA Compatible of 11KV, 630 Amps, 21KA for 3 second of SF 6 insulated RING MAN UNIT (RMU) 4 way consist of motorised 3 load break switch and 01 (one) VCB suitable size replaceble bushing complete all as specified and directed. ( Make- ABB, Seimens, Crompton, Schneider, Lucy Electric India Pvt Ltd)
Supply, Installation, testing and comissioning of 11KV SCADA Compatible of 11KV 630 Amps 21KA for 3 second of SF 6 insulated RING MAN UNIT (RMU) 3 way consist of motorised 2 load break switch and 01 (one) VCB suitable size replaceble bushing complete all asspecified and directed. ( Make- ABB, Seimens, Crompton Schneider,Lucy Electric India Pvt Ltd))
M&L for dismentling of 4/2 pole HT structure from ground level including opening of existing cable connection from GOD / jumper, opening of insulator LA angle iron frame complete with making good of distrubed surface and connecting the HT cable with RMU complete all as specified and directed.
M&L for foundation for RMU with bricks masonary work incl plastering white wash of the same upto 0.60 mtr from ground level incl provn of a step infront of RMU on openable side with brick masonary, plastering and white wash up to height of RMU bottom, width 0.45 cm and length equal to the RMU width for operating of RMU and surrounding area fenced with chain link fencing duly supproted with MS work i.e angle iron 50X50X6 mm and braced with flate iron 25x25x6mm incl provn of opening gate with same material with linking arragement and brick work with plastering and white wash around the fencing with height 0.30 cm from GL and height of fence should be up to RMU height complete all as specified and directed.
Supply, fixing, testing and commissioning of heat shrink end jointing kit for 11 KV (Earthed) grade cable for indooe termination heat shrink type joint complete with jointing materials and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size up to 95 sqmm complete all as specified and directed.
Supply, installation, testing and commissioning of transformer as per IS-1180 outdoor type complete 250 KVA, 11/0.433 KV, 3 phase 50Hz, 4 wire, ONAN( Oil natural Air natural) cooled oil immersed copper wound step down transformer complete with first filling of filtered and dehydrated transformer oil as per IS 335 ( ISI markded) and other standard fitings/accessories and 7 postition off circuit Tap changer (Tapping range +7.5% in steps of 2.5% each) with vector group Dyn-11 all as specified and directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 Core 95 sq mm complete all as specified and directed.
Disconnection and dismantling of HT cables and GOD/ bus bar from four pole structure and after taking proper safety precaution and rerouted the cables by excavation and re-connection the same in RMU complete all as specified and directed.
Dismaintling of HT steel poles/struts, any size after reconnection of HT cables in RMU complete all as specified and directed.
Dismantling cross-arms of M.S. channel or angle sections etc complete all as specified and directed.
M & L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 Sqmm to 95 Sqmm complete all as specified and directed.
Supply, laying and testing of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core complete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/dence soil for laying of LT UG cables/base for Pole etc complete all as specified and directed.
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard/dense soil complete all as specified and directed.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed .
M&L for sand cushioning laid in trenches for laying of LT UG cables complete all as spd and directed. ( Punned thickness of sand ie 18 cm will be measured and paid) complete all as specified and directed.
M&L Modular bricks common burnt clay building bricks, sub-class ‘B’ designation-75 for LT UG cable protection complete all as specified and directed.
M&L for earthing complete with galvanised or steel earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to strip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 3 of SSR -2009 Part I and connecting to arthing test point,main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 3 of SSR(Pt-I)2009 complete all as specified and directed.
Supply, installation, testing and commissioning of 11KV, 630A, 21KA for 3 sec, SF6 insulated Ring Main Unit (RMU) consist of motorized 3 load break switch and 1 VCB with suitable site replaceable bushings complete in all respects as per specs (CCCV) including foundation with brick masonary , plastering and white wash of suitable size and height up to 60 cm from GL for installing of RMU and provn of a step with brick masonary infornt of openable side of RMU for operating of RMU complete all as specified and directed.( Make of RMU - ABB, Seimens, Crompton, Schneider,Lucy Electric India Pvt Ltd))
M&L for horizontal boring and inserting casing pipe with fitting with material HDPE of pressure rating 6 Kg/sq cm 150 mm dia along road and under pavement, hard standing , road crossing in all type of soil at prescribed depth of boring not less than 1.5 mtr from the road surface incl making PCC chamber with cover at both side of road complete all as specified and directed.
M&L for plateform for installing 250 KVA Transformer outdoor type of size 3x2.5x1.25 Mtr height from GL constructerd with Brick wall and filling with hardcore boulders and 30CM 1:2:4 type BI using 20 mm graded stone aggregate concrete, plastering , painting complete and to meet and full fill the requirement of OEM and as specified and directed.
M&L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
M&L for providing fencing of transformer / RMU with chain link and supported with MS work ie angle iron 50x50x6 mm and braced with flat iron 25x25x6mm incl provn of opening gate with same material with locking arrangement and brick work with plastering min height 0.30 cm from GL around the fencing, min height of fence should be 1.5 Mtr complete with suitable size all as specified and directed. (Note: MS work will be measured and paid separetely in respective items here in before) Note : Tenderers may note that amount of credit Rs. 1,91,275.00 will be deducted from the total amount arrived, at the time of Acceptance of tender.
Diamond Electric Co.
LUMOS INFRA PVT LTD
JAZZCON ENGINEERS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .