Execuive Engineer Projects Division Pulwama
Execuive Engineer Projects Division Pulwama
Supply, Installation, Testing and Commissioning of 33kv RMU unit and standby Auxiliary Transformer to be carried out under Capex Budget at AIIMS Awantipora.
2026_PDD_332302_1
PDP 02 of 2026 27
Open Tender
Electrical Works
Item Rate
AWantipora
Please refer Tender documents.
3 documents required · 3 mandatory
₹3,000
Accounts Officer with chief engineer Projects
₹3.6 L
Yes
26 Nov 2026
26 Nov 2026
12 Dec 2026
26 Nov 2026
9 Dec 2026
27 Nov 2026
27 Nov 2026 - 28 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Item Description | |||||
| 1.01 | 33kV RING MAIN UNIT (4-way type,two isolators and two Circuit breaker scheme): Out-door type RMU, SF6 Insulated, Extensible type, at 33kV system voltage and breaking capacity 25kA for three second, with SF6 insulated VCB with O/C + E/F Relay system comprising of
a)33kV, 630 Amp. motorized Isolators including earthing switches with making capacity 62.5kA, having mechanical ON/OFF.
b)33kV,630Amp motorized, spring operated, Circuit Breakers (CB) with earthing switches. VCB must meet 10000 ON-OFF mechanical operation, and the operating sequence must be O-0.3sec-CO-3Min-CO. Suitable CT shall be placed in Cable chamber for protection.
( c). Cu Bus - Bar of 630 Amp. rating.
d)One (1) No. Numerical Aux powered relay having Non-directional 0/C and E/F protection (for No. Circuit Breaker feeder). Relay should have minimum 4-DI & 6-DO. The relay shall also interface via an RS 232/485 port in order to send, as a minimum, real-time readings using the MODBUS protocol.
e)Incoming Isolators shall have FPI with electrical reset contact / facility.
f)All necessary potential-free contacts for indications relevant to RMU monitoring and control.
g)Capacitor Voltage Dividers serving live-line cable indicators in No. Breaker & Isolator.
h)The RMU must be offered with a single- phase Auxiliary VT 33KV/230V AC, 500VA and 26AH, 24V battery with 7amps Battery Charger.
i)The RMU (Gas tank +Cable chamber) must be Internal tested for 25KA for 1 sec duration with AFLR classification. RMU shall have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. | 1 | No | 100 | ₹100 |
| 2.01 | 33 kV, Single core 400 mm² Aluminium, Flat strip Armoured XLPE Cable FRLS (from four pole to RMU and RMU to 33 kV Bus with 12 runs of 90 mtr each). | 1.08 | Kms | 100 | ₹108 |
| 3.01 | 33 kV, 1 core 185sq.mm, Al conductor, XLPE, insulated, armoured cable (for 33kV/440V Auxilarry Transformer,with six runs of 30 mtr each) | 180 | Mtrs | 10 | ₹1,800 |
| 4.01 | 33 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 400 sq.mm. | 48 | Nos | 10 | ₹480 |
| 5.01 | Straight Through Jointing kit for 400 sqmm | 4 | Nos | 10 | ₹40 |
| 6.01 | 33 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 185 sq.mm | 12 | Nos | 10 | ₹120 |
| 7.01 | 6 core 2.5 sq.mm.Control Cable Copper Armoured, 1.1 kV Grade, ISI, FRLS. | 300 | Mtr | 11 | ₹3,300 |
| 8.01 | Warning Tap | 1 | Kms | 10 | ₹10 |
| 9.01 | Cable Route Markers. | 10 | No. | 10 | ₹100 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
SBDAIIMS.pdf
Tender Documents • 1.52 MB
BOQ_1128134.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .