AEE, ELECTRICAL
IWD
Annual servicing and Preventive Maintenance of Transformers, 33 kv and 11 kv Vacuum Circuit Breakers, APFC Panels etc at Electrical Sub stations of IISER Kolkata Mohanpur Campus.
2025_IISER_843372_1
IISER-K/IWD/Elect/24-25/21
Open Tender
Electrical Works
Item Rate
120 days
IISER KOLKATA
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
A/C NO. 089301000011530
₹36,000
13 Feb 2025
8 Jan 2025
7 Feb 2025
8 Jan 2025
5 Feb 2025
8 Jan 2025
Amount
General servicing of existing 3200A/2500A/1250 A capacity ACB in the MV panel/APFC panel cleaning of contacts with CTC (carbon tetra chloride chemical), checking of trip bridges, shunt trip, UV coil, applying oil and grease for moving contacts checking of interconnections from the IDMT relay to ACB and other minor connected works as per the manufacturer's manual procedure.Make:-ABB/L&T
Supply, fixing, testing and commissioning of 12 step, 440V, 5A multifunctional Power factor Correction relay capacitors in existing APFC Panels at different substations. make:havells/siemens/Schneider/epcos/ ABB
Relay testing, servicing and preventive maintenance of existing APFC Panel along with different capacitor bank feeder ,based on sum total of capacitor banks of each APFC panel servicicing work will be conducted under the nomenclature of following APFC panel sizes
600 KVAR APFC Panel
300 KVAR APFC Panel
600 KVAR APFC Panel
S& F of Crossflow fan, 1-phase 230V AC, 120 Watt,2550 RPM with bracket
Supply, installation testing and commissioning of Indoor Double Door DC Power Pack Panel consist of two seperate cubicle,out of which, one cubicle for Battery Charger with Boost and float option and display showing current and voltage including seperate chamber for 2 nos. Exide 12V,180AH Lead Acid battery for 33 kv HT switch board control and realay function activation purpose & another cubicle for Battery Charger with Boost and float option and display showing current and voltage including seperate chamber for 2 nos. Exide 12V,180AH Lead Acid battery for 11 kv HT switch board control and realay function activation purpose, having lP 42 protection and made out of not less than 2.0 mm thick for load bearing members & 1.6 mm thick for doors, compartmentalized, epoxy powder coated treated in 7 tank process finish with following items, front and back both side openable, duly hinged doors with locking arrangement by providing both sides hold drafts and all hardware for fabrication of box. The cubical panel should be duly primered and epoxy painted.Cable entry from bottom suitable for I/c & O/g feeder. The Panel shall be fabricated in CPRI approved panel builder with approval of the Deptt.. Drawing of DC Power Pack shall be submitted for approval prior to fabrication
Annual servicing & maintenance/Health Check-up required for complete panels (VCB, Panel, CT/PT, Relays) for of 25 Nos. SIEMENS make 33 KV & 11 KV Vacuum Circuit Breakers
Transformer Oil Filtration & Dehydration of 5 MVA 33/11 kv CGL make Power Transformer ,with opening 3 nos HT bushing ,necessary replacement of New Gasket & Rubber Oil seal ,Opening 4 nos LT bushing Replace of gasket ,Rubber oil seal Oil filter with Stream Line Oil Filter Machine 250 Gallons Capacity per hour & B.D.V. Testing 50kv at 2.5 mm sparking gap at site including transportation of filtering machine, providing test certificate etc., as required.
Top up of transformer oil (as per IS 335/2018) in the conservator tank up to the minimum level after filtration of the transformer oil etc., as req.
Supplying and fixing of silica gel breather including removing the old breather etc., as required.
Providing and fixing of earth bus 50 MMx 5 MM copper strip on surface for connection etc. as required
Servicing of 1 MVA 11KV/415V HT Dry type Energy Pack make transformers along with repairing and servicing of RTCC Panel with marshalling box for 1 MVA Dry type transformers
Servicing of 800 KVA 11KV/415V CGL make HT Dry type transformers along with repairing and servicing of RTCC Panel with marshalling box for 800 KVA Dry type transformers
Servicing of Dry type transformers 2 MVA 11 kv/415 v Kirloskar make Dry type transformers
Supplying and fixing of 230/110 volts AC LED indication lamps in the existing LT panels including removing of faulty as required.
33kV Grade 4 mm thickness and 1 meter wide Black Electrical Insulation Rubber Mat
BEACON ENTERPRISE (BID ID -3162873)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .