Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.9 CrAdmitted-Finance | ₹24.9 Cr | L1 | Admitted-Finance |
| 2 | Rejected-Technical | - | - | Rejected-Technical Not eligible for opening of Financial Bid on account of not meeting the Qualifying Criteria of having completed similar work. |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not eligible for opening of Financial Bid on account of non-submission of Tender Cost. |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not eligible for opening of Financial Bid on account of non-extension of bid validity. |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not eligible for opening of Financial Bid on account of not meeting the Qualifying Criteria of having completed similar work. |
| Sl No | Description | Qty | Unit | HITECH ERECTORS PVT. LTD. L1 |
|---|---|---|---|---|
| 1.00Total Amount of BoQ 2 | ||||
| 1.01 | Amount after unconditional Rebate | 1 | Nos | 0 ₹8.3 Cr |
Tender Value
₹93.8 Cr
Closing Date
30 Nov 2021, 11:00 amClosed
General Manager/CP
3rd Floor, RITES Bhawan-II, Plot No. 144, Sector-44, Gurgaon- 122003
Supply, Erection, Testing And Commissioning of External Electrical and Substation Works for Kolkata RPO Building, Kolkata
2021_RITES_94161_1
RITES/CP/TC/RPOKOLKATA/SS/2021
Open Tender
Electrical Works
240 days
New Town Rajarhat, Kolkata
Please refer Tender Documents
10 documents required · 10 mandatory
₹7,000
RITES Ltd.
Exempted
2 Jun 2022
9 Nov 2021
1 Dec 2021
9 Nov 2021
30 Nov 2021
23 Nov 2021
10 Nov 2021 - 17 Nov 2021
Amount
Total Amount of BoQ 2
Amount after unconditional Rebate
Description of Work / Item(s)
Amount
Total of BoQ 3 and BoQ 4
Total Amount of BoQ3 (Item Rate)
Total Amount of BoQ4 (Percentage Rate)
Description of Work / Item(s)
Amount
Schedule - (B) Bill of Quantites for Non Schedule Items (MR ITEMS)
Electrical
NS 1 - 33 kV HT PANEL BOARD
NS 1.1 - 33 kV HT PANEL BOARD (WBSEDL PART)
Supply, installation, testing and commissioning of 33kV, 1600A, minimum 26.3kA, 50Hz rated 4 Panels Switchboard comprising of 1Nos. Incomer and 2 Nos. Outgoing feeder & 1No Bus PT confirming to IEC 62271-200 & as per specification of WBSEDCL. The circuit breaker shall be Vacuum type, Busbar shall be of Copper. The switchgear shall be supplied with set of operation accessories like, racking handle, spring charging handle, breaker handling trolley etc as per SLD ,specifications complete as required (General arrangement and schematic Drawings to be approved by the Deptt. before start of fabrication). DC Power Pack including battery charger on each feeder shall be provided with sufficient backup.
The panels shall be constructed of painted 2mm CRCA sheet and shall meet the LSC 2B PM categorisation as per IEC 62271-200
(i) INCOMER PANEL - 1 Nos. each comprising of
1No. 33 kV, 1600A, minimum 26.3 KA drawout type Vacuum Circuit Breaker as per IEC 62271-100.
The VCB shall have 3 Nos. Poles with Vacuum Interrupter
Motorised Spring Stored energy operating mechanism (230VAC)
Operation counter
Auxiliary contacts of 8 NO + 8 NC.
Closing coil & shunt trip coils rated for 110V DC
Manual Closing Pushbutton
Manual Tripping Pushbutton
Free standing CRCA enclosure to house VCB, Busbar, CTs, PTs, Relays etc. having 4 separate compartments one for CB, one for CTs & PTs, one for bus bar & one for Relays & control wiring. The panels shall be provided with metalic shutters operated with the movement of VCB from test to service and vice-a-versa to ensure covering all the live parts when the VCB is taken out of the panel.
Set of 3 phase 1600A Copper bus bar.
1 sets each of current transformer incorporating 3 no single phase resin cast double core CTs of suitable burden of 15 VA each with ratio 400-200/1-1A with accuracy class 0.5 and 5P15, as per relevant IS.
1 No. Digital Ammeter
1 sets of relay - triple pole, non directional IDMTL relay with high set feature having 2 elements for over current setting 50% - 200% and 1 element for earth fault protection setting 10%-40%.
1 No. Master Trip relay
1 No. trip circuit supervision relay
1 No. Breaker Control Switch (TNC Switch)
1 sets of 240V AC single phase space heater with switch
1 sets of LED indicating lamps Red, Green, Amber, While lamps for ON/OFF/TRIP/TRIP CKT HEALTHY indication.
1 set of R Y B indication lamps for phase indication.
1 No. Hooter
Test terminal block, fuses, circuit labels, indication lamps, push button, etc.as per standard practice complete with all necessary wiring including all interconnections.
(ii) OUTGOING - 2 No. comprising of
1 Nos. 33 kV, 1600A, minimum 26.3 KA drawout type Vacuum Circuit Breaker as per IEC 62271-100.
The VCB shall have 3 Nos. Poles with Vacuum Interrupter
Motorised Spring Stored energy operating mechanism (230VAC)
Operation counter
Auxiliary contacts of 8 NO + 8 NC.
Closing coil & shunt trip coils rated for 110V DC
Manual Closing Pushbutton
Manual Tripping Pushbutton
Free standing CRCA enclosure to house VCB, Busbar, CTs, PTs, Relays etc. having 4 separate compartments one for CB, one for CTs & PTs, one for bus bar & one for Relays & control wiring. The panels shall be provided with metalic shutters operated with the movement of VCB from test to service and vice-a-versa to ensure covering all the live parts when the VCB is taken out of the panel.
Set of 3 phase 1600A Copper bus bar.
1 sets each of current transformer incorporating 3 no single phase resin cast double core CTs of suitable burden of 15 VA each with ratio 200-100/1-1-1A with accuracy class 0.5/5P15/PS, as per relevant IS.
1 No. Digital Ammeter
1 sets of relay - triple pole, non directional IDMTL relay with high set feature having 2 elements for over current setting 50% - 200% and 1 element for earth fault protection setting 10%-40%.
1 No. Master Trip relay
1 No. trip circuit supervision relay
2 Nos. 3 element auxiliary relay for transformer faults (OTI, WTI, Bucholz) alarm & trip
1 No. Breaker Control Switch (TNC Switch)
1 sets of 240V AC single phase space heater with switch
1 sets of LED indicating lamps Red, Green, Amber, While lamps for ON/OFF/TRIP/TRIP CKT HEALTHY indication.
1 No. 8 window solid state annunciator for transformer faults
Test terminal block, fuses, circuit labels, indication lamps, push button, etc.as per standard practice complete with all necessary wiring including all interconnections.
(iii) BUS PT - 1 No. comprising of
1 sets of Bus connected 3 Nos. single phase epoxy resin cast voltage transformer having a ratio of 33000/110V-110V, burden of 50VA and accuracy class of 0.5 for metering core and 50VA & 3P for protection core as per relevant IS. The VT should be with HRC fuses on primary and secondary sides respectively.
1 sets of TVM (with KWH meter, PF meter, ammeter voltmeter, etc.)
1 sets of undervoltage relay with time delay
Complete set described as above
NS 1.2 : 33 kV 3 PANEL BOARD (RITES PART) :
Supply, installation, testing and commissioning of 33kV, 800A, minimum 26.3kA, 50Hz rated 3 Panels Switchboard comprising of 1 No. Incomer and 2 No. Outgoing feeders confirming to IEC 62271-200. The circuit breaker shall be Vacuum type, Busbar shall be of Copper. The switchgear shall be supplied with 2 set of operation accessories like, racking handle, spring charging handle, breaker handling trolley. DC Power Pack including battery charger on each feeder shall be provided with sufficient backup.
The panels shall be constructed of painted 2mm CRCA sheet and shall meet the LSC 2B PM categorisation as per IEC 62271-200
INCOMER PANEL - 1 No. comprising of
1 Nos. 33 kV, 800A, minimum 26.3 KA drawout type Vacuum Circuit Breaker as per IEC 62271-100.
The VCB shall have 3 Nos. Poles with Vacuum Interrupter
Motorised Spring Stored energy operating mechanism (230VAC)
Operation counter
Auxiliary contacts of 8 NO + 8 NC.
Closing coil & shunt trip coils rated for 110 V DC
Manual Closing Pushbutton
Manual Tripping Pushbutton
Free standing CRCA enclosure to house VCB, Busbar, CTs, PTs, Relays etc. having 4 separate compartments one for CB, one for CTs & PTs, one for busbar & one for Relays & control wiring. The panels shall be provided with metalic shutters operated with the movement of VCB from test to service and vice-a-versa to ensure covering all the live parts when the VCB is taken out of the panel.
Set of 3 phase 800A Copper bus bar.
1 sets of line connected 3 Nos. single phase fixed type epoxy resin cast voltage transformer having a ratio of 33000/110V-110V, burden of 100VA and accuracy class of 0.5 for metering core and 30VA & 3P for protection core as per relevant IS. The VT should be with HRC fuses on primary and secondary sides respectively.
1 sets each of current transformer incorporating 3 no single phase resin cast double core CTs of suitable burden of 15 VA each with ratio 100/50/1A with accuracy class 0.5 and 5P15, as per relevant IS.
1 No TVM (with KWH meter, PF meter, ammeter voltmeter, etc.) for incoming breaker only
1 No. Digital Voltmeter
1 No. Digital Ammeter
1 sets of relay - triple pole, non directional IDMTL relay with high set feature having 2 elements for over current setting 50% - 200% and 1 element for earth fault protection setting 10%-40%.
1 No. Master Trip relay
1 No. trip circuit supervision relay
1 No. undervoltage relay with time delay
1 No. Breaker Control Switch (TNC Switch)
1 sets of 240V AC single phase space heater with switch
1 sets of LED indicating lamps Red, Green, Amber, While lamps for ON/OFF/TRIP/TRIP CKT HEALTHY indication.
1 set of R Y B indication lamps for phase indication.
1 No. Hooter
Test terminal block, fuses, circuit labels, indication lamps, push button, etc.as per standard practice complete with all necessary wiring including all interconnections.
OUTGOING - 2 No. Each comprising of
1 Nos. 33 kV, 630A, minimum 26.3 KA drawout type Vacuum Circuit Breaker as per IEC 62271-100.
The VCB shall have 3 Nos. Poles with Vacuum Interrupter
Motorised Spring Stored energy operating mechanism (230VAC)
Operation counter
Auxiliary contacts of 8 NO + 8 NC.
Closing coil & shunt trip coils rated for 110V DC
Manual Closing Pushbutton
Manual Tripping Pushbutton
Free standing CRCA enclosure to house VCB, Busbar, CTs, PTs, Relays etc. having 4 separate compartments one for CB, one for CTs & PTs, one for buabar & one for Relays & control wiring. The panels shall be provided with metalic shutters operated with the movement of VCB from test to service and vice-a-versa to ensure covering all the live parts when the VCB is taken out of the panel.
Set of 3 phase 800A Copper bus bar.
1 sets each of current transformer incorporating 3 no single phase resin cast double core CTs of suitable burden of 15 VA each with ratio 100/50/1A with accuracy class 0.5 and 5P10, as per relevant IS.
1 No. Digital Ammeter (1-100A)
1 sets of relay - triple pole, non directional IDMTL relay with high set feature having 2 elements for over current setting 50% - 200% and 1 element for earth fault protection setting 10%-40%.
1 No. Master Trip relay
1 No. trip circuit supervision relay
2 Nos. 3 element auxiliary relay for transformer faults (dry type transformer) alarm & trip
1 No. Breaker Control Switch (TNC Switch)
1 sets of 240V AC single phase space heater with switch
1 sets of LED indicating lamps Red, Green, Amber, While lamps for ON/OFF/TRIP/TRIP CKT HEALTHY indication.
1 No. 8 window solid state annunciator for transformer faults
Test terminal block, fuses, circuit labels, indication lamps, push button, etc.as per standard practice complete with all necessary wiring including all interconnections.
Complete set described as above
METER CUBICAL
NS 2 : Supply,installation,testing and commissioning of 33KV control and relay panel as per specification of WBSEDCL.
NS 3: ELECTRICAL LT PANELS AND ISOLATION BOXES
Supply, installation, testing and commissioning of cubical type LT switchgear suitable for 415V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for frame work and covers, 3mm thick for gland plates including cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable capacity extensible type TPN Aluminium Alloy bus bars of high conductivity, bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5sq.mm. FRLS insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing following 415V Switchgear and accessories in the Panel as per SLD ,specifications complete as required (General arrangement and schematic Drawings to be approved by the Deptt. before start of fabrication) . The Bus bars will be as per the IEC 6068-3-247 Standard.
Also, refer to General Notes and Specifications for Panels/ Boards.
All Switchgear makes shall be from approved List of makes.
Only one make of switchgear to be used in a board / Panel.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars insulation shall be with heat shrinkable sleeves. SMC shrouds busbar supports shall be used.
Minimum Air Clearances between bus bars;
P-P=25mm, P-N=20mm,P-E=20mm and N-E=20mm
GENERAL NOTES FOR MCCB's:
MCCB's shall be of 3P with solid neutral link or 4P as called for in the BOQ.
Ics = Icu for the breakers.
MCCB's upto 200A shall be with thermal - magnetic releases and beyond 200A shall be with micro-processor based releases.
MCCB's upto 100A shall have fixed over current and fixed short circuit setting and breaking capacity for 1 Sec.
MCCB's above 100A but upto 200A shall have adjustable over current and fixed short circuit setting and breaking capacity for 1 Sec.
MCCB's shall be with extended rotary handle and Phase separators both sides
MCCB's shall have auxiliary contacts wherever BMS compatibility is needed.
MCCB of required rating (Amps) as called for in the BOQ and of required breaking capacity for 1 Sec.
Refer Electrical SLD
GENERAL NOTES FOR MCB's:
MCB's shall be of minimum 10kA breaking capacity for 1 sec.
Exact MCB rating & category is to be calculated by the electrical contractor based on the final load of the circuit, its nature and fault current.
Supplying, Installation, testing, commissioning of gas based fire supression system in all compartment of LT panels complete with : i) Heat sensing cable with sensors mounted in an encapsulation at regular intervals, pinpoint sensor location via individual address, constant sensor monitoring via conrol unit & including necessary connection box, fixing accessories etc. Cable shall detect fixed as well as rate of rise of temperature. ii) Cable connection box & controller (Controller shall have provision to give signal to fire alarm panel) iii) Fire suppression gas cylinders to extinguish fire with necessary control panel to receive command from fire panel for Gas release, necessary piping & nozzels in LT panel compartments with all fixing accessories. iv) all necessary power & control cabling.
All Panels Should have provision of Multi Function Meter with required number of MCB's, Indicatuion Lamp, Control circuitry etc as required.
NS 3.1 : Main LT Panel
INCOMER 1
1 Nos. 1600 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases (From TR - 1)(with ethernet)
INCOMER 2
1 Nos. 2500 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases (From TR - 2)(with ethernet)
INCOMER 3
1 Nos. 4000 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases (From DG Sync Panel)(with ethernet)
INCOMER 4 for Solar
2 Nos. 100A 3P 36KA MCCB with O/L,S/C Thermal Mag.Release
BUSBARS SECTIONS -1
1600 amps TPN, 50 kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
BUSBARS SECTIONS -2
2500 amps TPN, 50 kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
BUSBARS SECTIONS -3
4000 amps TPN, 50 kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
Bus coupler
1 Nos. 1600 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases (For TR - 1)
1 Nos. 2500 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases (For TR - 2)
OUTGOING SECTION 1
1 No. of 1250 A TPN ACB 50 kA MDO Type Built in Microprocessor Based Release with O/C, S/C and E/F Protection.
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
1250/5A, 10VA, CL-1, RESIN CAST CT FOR APFCR
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
1 No. of 630 A TPN MCCB
630A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L,S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
2 No. of 315 A TPN MCCB
315A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L,S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
3 No. of 160 A TPN MCCB
160A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L,S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
2 No. of 200A TPN MCCB
200A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L,S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
2 No. of 100 A TPN MCCB
100A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
7 No. of 40 A TPN MCCB
40A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
2 No. of 63 A TPN MCCB
63A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
1 No. of 63 A TPN MCCB with timer for street light
63A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC, with timer
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
63 A 4P Contactor -1 No.
NEUTRAL LINK
OUTGOING SECTION 2
2 No. of 1250 A TPN ACB
1250A, TPN 50 KA MDO ACB MP BASED WITH O/L, S/C & E/F (LSIG) RELEASE, S/T RELEASE,MICROSWITCH FOR COMMON FAULT INDICATION
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
1 No. of 1600 A TPN ACB
1600A, TP 50 KA MDO ACB MP BASED WITH O/L, S/C & E/F (LSIG) RELEASE, MICROSWITCH FOR COMMON FAULT INDICATION
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
1600/5A, 10VA, CL-1, RESIN CAST CT FOR APFCR
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
3 No. of 250 A TPN MCCB
250A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L, S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
1 No. of 100 A FP MCCB
200A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW. +TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
NS 3.2 : DG Sync Panel
INCOMER 1
1 Nos. 1600 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases with load sharing controller unit shall be compact and easy to use whilst providing all essential protection, control and monitoring features (From DG - 1)
INCOMER 2
1 Nos. 1600 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases with load sharing controller unit shall be compact and easy to use whilst providing all essential protection, control and monitoring features(From DG - 2)
INCOMER 3
1 Nos. 800 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases with load sharing controller unit shall be compact and easy to use whilst providing all essential protection, control and monitoring features (From DG - 3)
BUSBARS SECTIONS
4000 amps TPN, 50kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
OUTGOING
1 Nos. 4000 Amps 4P 50 kA EDO, ACB with Microprocessor based Releases
Note: DG Sync Panel shall be in accordance with SLD.
NS 3.3 : LIFT CONTROL DB(TYPICAL)
INCOMER
1 Nos. 63 Amps TPN 15kA MCCB with O/L, S/C,E/F Protection & TM Rel.
BUSBARS SECTIONS
63 amps TPN, 15kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
OUTGOING
2 No. of 63 A 4P RCCB 300mA
2 No. of 16 A DP RCCB
NS 3.4 : LIFT CONTROL DB(LAB BLOCK)
INCOMER
1 Nos. 25 Amps TPN 15kA MCB with O/L, S/C,E/F Protection
BUSBARS SECTIONS
25 amps TPN, 15kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
OUTGOING
2 No. of 25 A 4P RCCB 300mA
2 No. of 16 A DP RCCB
NS 3.5 : SDB - Emg.Lighting Panel
INCOMER
40A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC - 1No.
BUSBARS SECTIONS
40 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 1.0 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING-10 Nos
16A DP C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.6 : SMP Lighting + Power -1
INCOMER
100A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC- 1No.
BUSBARS SECTIONS
100 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
100/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING-12 Nos
40A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.7 : SMP Lighting + Power -2
INCOMER- 1No.
100A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
BUSBARS SECTIONS
100 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
100/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING- 14Nos
40A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.8 : SMP Lift - 1 Panel(Tenant)
INCOMER (160A MCCB)-1 No.
160A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW. + TAC
BUSBARS SECTIONS
160 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
160/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
63A MCCB FEEDER- 5Nos
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
32A MCCB FEEDER- 3Nos
32A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.9 : SMP Lift - 2 Panel(Rites)
INCOMER (160A MCCB)- 1No
160A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW. + TAC
BUSBARS SECTIONS
160 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
160/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
63A MCCB FEEDER- 5Nos
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
32A MCCB FEEDER- 3Nos
32A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.10 : SMP Tenanat office Panel(1st & 3rd to 11th floor)
INCOMER (100A MCCB)- 1 No.
100A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
with Billing Metering facility
BUSBARS SECTIONS
100 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars with kWH /Tariff meter as per supply company specification. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
100/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
40A MCCB FEEDER- 2 Nos
40A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
MCB FEEDER
32A 4P C-CURVE MCB, 10KA- 2 Nos
40A 4P C-CURVE MCB, 10KA- 2Nos
63A 4P C-CURVE MCB, 10KA- 2Nos
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.11 : SMP RITES office Panel (1st to 11th floor)
INCOMER (100A MCCB)- 1 No.
100A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
with Billing Metering facility
BUSBARS SECTIONS
100 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars with kWH /Tariff meter as per supply company specification. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
100/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
40A MCCB FEEDER- 2Nos
40A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
MCB FEEDER
32A 4P C-CURVE MCB, 10KA- 1 No.
40A 4P C-CURVE MCB, 10KA- 2Nos
63A 4P C-CURVE MCB, 10KA- 3Nos
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.12 : UPS Panel (Tenant Side)
INCOMER (40A MCCB)- 1 No.
40A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE
BUSBARS SECTIONS
40 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER- 4 Nos
32A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.13 : UPS Panel (RITES Side)
INCOMER (40A MCCB) - 1 No.
40A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDL
BUSBARS SECTIONS
40 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER- 4 Nos
32A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.14 : SMP Tenant office - Canteen Area
INCOMER (200A MCCB)- 1 No
200A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW. + TAC
WITH BILLING METER
BUSBARS SECTIONS
200 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
200/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
100A MCCB FEEDER- 2 Nos
100A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
MCB FEEDER
32A 4P C-CURVE MCB, 10KA- 2 Nos
40A 4P C-CURVE MCB, 10KA- 1 No.
63A 4P C-CURVE MCB, 10KA- 2 Nos
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.15 : RITES Building 12th floor Panel
INCOMER (250A MCCB)- 1 No.
250A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L, S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
BUSBARS SECTIONS
250 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
250/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
100A MCCB FEEDER- 2 Nos
100A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
63A MCCB FEEDER- 2 Nos
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
MCB FEEDER
32A 4P C-CURVE MCB, 10KA- 4 Nos
40A 4P C-CURVE MCB, 10KA- 5 Nos
63A 4P C-CURVE MCB, 10KA- 2Nos
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.16 : UPS Panel (12th floor Server room)
INCOMER (63A MCCB)- 1 No.
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE
BUSBARS SECTIONS
63 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER- 5 Nos
32A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.17 : APFC Panel -750kVAr Refer Schematic(with EXHAUST fan)(Auto/manual control provision)
INCOMER (1600A ACB)- 1 No.
1600A,TPN 50KA MICROPROCESSOR BASED MDO TYPE ACB WITH O/L, S/C. & E/F RELEASE , MICRO SWITCH FOR COMMON FAULT INDICATION
25A SP TNC SWITCH
BUSBARS SECTIONS- 50kA
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP, SPRING CHARGED, TRIP CKT HEALTHY INDICATION LAMP , LED TYPE, 230V AC
TRIP CIRCUIT HEALTHY PUSH BUTTON
1600/5A, 15VA, CL-1 RESIN CAST CURRENT TRANSFORMER FOR METERING
DIGITAL AMMETER, CL-1, SIF-96X96 SQ. MM.
DIGITAL VOLTMETER, CL-1, SIF-96X96 SQ. MM.
14 STAGE APFC RELAY, CT SECONDARY CURRENT 5A
6A TP C-CURVE 10KA MCB
6A DP C-CURVE 10KA MCB
10A DP C-CURVE 10KA MCB
6A 10KA DC MCB
AUXILIARY CONTACTOR 4NO . CONTACT,COIL VOLT-24V DC
AUXILIARY CONTACTOR 4NC ADD ON BLOCK AUX. CONTACT,COIL VOLT-24V DC
230V/24V DC 12.5A SMPS
ON, OFF TOGGLE SWITCH
MULTIFUNCTION TIMER
DOOR LIMIT SW.
CFL LAMP
NETRAL LINK
CONTROL TRANSFORMER FEEDER
415V/240V 2 KVA 1PH CONTROL TRANSFORMER- 1 No.
4A TP MPCB WITH S/C PROTECTION ONLY FOR TRAFO. PRIMARY- 1 No.
32A 10KA DP MCB
OUTGOING FEEDER
100KVAR CAPACITOR BANK WITH 7% DETUNED REACTOR- 5 Nos
250A SEMICONDUCTOR FUSE WITH BASE
ON/OFF INDICATION LAMP (RED/GREEN), LED TYPE, 24V DC
28.1KVAR 480V 50Hz AC MPP HEAVY DUTY CAPACITOR BANK CYLINDRICAL TYPE
25KVAR 440V,50HZ, 7% DETUNED COPPER REACTOR
START PUSH BUTTON WITH ELEMENT, GREEN
STOP PUSH BUTTON WITH ELEMENT, RED
50KVAR THYRISTER SWITCHING MODULE
Series Resistor-EW22
AUX CONTACTOR WITH 3NO+1NC CONTACT
50KVAR CAPACITOR BANK WITH 7% DETUNED REACTOR- 5 Nos
140A SEMICONDUCTOR FUSE WITH BASE
ON/OFF INDICATION LAMP (RED/GREEN), LED TYPE, 24V DC
28.1KVAR 480V 50Hz AC MPP HEAVY DUTY CAPACITOR BANK CYLINDRICAL TYPE
25KVAR 440V,50HZ, 7% DETUNED COPPER REACTOR
START PUSH BUTTON WITH ELEMENT, GREEN
STOP PUSH BUTTON WITH ELEMENT, RED
50KVAR THYRISTER SWITCHING MODULE
Series Resistor-EW22
AUX CONTACTOR WITH 3NO+1NC CONTACT
AL BUS BAR
NS 3.18 : APFC Panel -600kVAr (with EXHAUST fan)(Auto/manual control provision)
INCOMER (1250A ACB)- 1 No.
1250A,TPN 50KA MICROPROCESSOR BASED MDO TYPE ACB WITH O/L, S/C. & E/F RELEASE , MICRO SWITCH FOR COMMON FAULT INDICATION
25A SP TNC SWITCH
BUSBARS SECTIONS- 50kA
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP, SPRING CHARGED, TRIP CKT HEALTHY INDICATION LAMP , LED TYPE, 230V AC
TRIP CIRCUIT HEALTHY PUSH BUTTON
1250/5A, 15VA, CL-1 RESIN CAST CURRENT TRANSFORMER FOR METERING
DIGITAL AMMETER, CL-1, SIF-96X96 SQ. MM.
DIGITAL VOLTMETER, CL-1, SIF-96X96 SQ. MM.
10 STAGE APFC RELAY, CT SECONDARY CURRENT 5A
6A TP C-CURVE 10KA MCB
6A DP C-CURVE 10KA MCB
10A DP C-CURVE 10KA MCB
6A 10KA DC MCB
AUXILIARY CONTACTOR 4NO . CONTACT,COIL VOLT-24V DC
AUXILIARY CONTACTOR 4NC ADD ON BLOCK AUX. CONTACT,COIL VOLT-24V DC
230V/24V DC 12.5A SMPS
ON, OFF TOGGLE SWITCH
MULTIFUNCTION TIMER
DOOR LIMIT SW.
CFL LAMP
NETRAL LINK
CONTROL TRANSFORMER FEEDER
415V/240V 2 KVA 1PH CONTROL TRANSFORMER- 1 No.
4A TP MPCB WITH S/C PROTECTION ONLY FOR TRAFO. PRIMARY- 1 No.
32A 10KA DP MCB- 1 No.
OUTGOING FEEDER
100KVAR CAPACITOR BANK WITH 7% DETUNED REACTOR- 4 Nos
250A SEMICONDUCTOR FUSE WITH BASE
ON/OFF INDICATION LAMP (RED/GREEN), LED TYPE, 24V DC
28.1KVAR 480V 50Hz AC MPP HEAVY DUTY CAPACITOR BANK CYLINDRICAL TYPE
25KVAR 440V,50HZ, 7% DETUNED COPPER REACTOR
START PUSH BUTTON WITH ELEMENT, GREEN
STOP PUSH BUTTON WITH ELEMENT, RED
50KVAR THYRISTER SWITCHING MODULE
AUX CONTACTOR WITH 3NO+1NC CONTACT
50KVAR CAPACITOR BANK WITH 7% DETUNED REACTOR- 4 Nos
140A SEMICONDUCTOR FUSE WITH BASE
ON/OFF INDICATION LAMP (RED/GREEN), LED TYPE, 24V DC
28.1KVAR 480V 50Hz AC MPP HEAVY DUTY CAPACITOR BANK CYLINDRICAL TYPE
25KVAR 440V,50HZ, 7% DETUNED COPPER REACTOR
START PUSH BUTTON WITH ELEMENT, GREEN
STOP PUSH BUTTON WITH ELEMENT, RED
50KVAR THYRISTER SWITCHING MODULE
Auxiliary CONTACTOR WITH 3NO+1NC CONTACT
AL BUS BAR
NS 3.19 : Conference Hall main DB Panel
INCOMER (200A MCCB)- 1 No.
200A TP+NL(SEPARATE NEUTRAL LINK) 36KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW. + TAC
BUSBARS SECTIONS
200 amps TPN, 36kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
200/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
DIGITAL VOLTMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
63A MCB FEEDER WITH TIMER- 6 Nos
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE
63A 4P POWER CONTACTOR(AC1 DUTY) WITH 2NO+2NC CONTACT BLOCK, 230V AC
ASTRONOMICAL TIME SWITCH
START/STOP PB
AUXILIARY CONTACTOR WITH 2NO+2NC CONTACT, 230V AC
ON/OFF INDICATION LAMP (RED/GREEN) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
63A MCCB FEEDER- 2 Nos
63A TP+NL(SEPARATE NEUTRAL LINK) 25KA THERMAL MEGNETIC BASED MCCB WITH O/L & S/C RELEASED, EXTENDED OPERATING HANDLE, 1C/O AUX. SW. + TAC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
MCB FEEDER- 6 Nos
40A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.20 : LT Panel for LAB building
INCOMER
1 Nos. 100 Amps TPN MCCB
BUSBARS SECTIONS
100 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
OUTGOING
1 No. of 63 A TPN MCB
1 No. of 40 A TPN MCB
4 No. of 25 A TPN MCB
1 No. of 25 A DP MCB
1 No. of 63 A TPN MCB as SPARE
1 No. of 40 A TPN MCB as SPARE
1 No. of 25 A TPN MCB as SPARE
NS 3.21 : UPS PANEL for LAB building
63A MCCB FEEDER
63A 4P 36KA THERMAL MAGNETIC BASED MCCB WITH O/L & S/C RELEASED EXTENDED OPERATING HANDLE, 1C/O AUX.SW.+TAC- 1No.
BUSBARS SECTIONS
100 amps TPN, 25kA, 430volts grade busbar chamber of suitable length with Al busbars. All busbars and interconnections shall be of suitable size Al busbar, current density of bus-bars shall not be more than 0.8 Amps/ sq.mm cross sectional area of Bus Bar.
R-PHASE INDICATION LAMP (RED), LED TYPE, 230V AC
Y-PHASE INDICATION LAMP (YELLOW), LED TYPE, 230V AC
B-PHASE INDICATION LAMP (BLUE) , LED TYPE, 230V AC
ON/OFF/TRIP INDICATION LAMP (RED/GREEN/AMBER) , LED TYPE, 230V AC
60/5A, 15VA, CL-1, RESIN CAST CT FOR METERING
DIGITAL AMMETER, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL MULTIFUNCTION METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
3PH 4WIRE DIGITAL KWH METER WITH RS-485 PORT, CL-1, SIF 96X96 SQMM
6A SP C-CURVE MCB, 10KA
NEUTRAL LINK
OUTGOING FEEDER
MCB FEEDER- 6 Nos
25A 4P C-CURVE MCB, 10KA
Construction of LT panel as per IS-8623 ( Part-I) Standard
NS 3.22 : Main Fire Fighting Panel
Supply, installation, testing and commissioning of cubical type LT switchgear suitable for 415V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for frame work and covers, 3mm thick for gland plates including cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable capacity extensible type TPN Aluminium Alloy bus bars of high conductivity, bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5sq.mm. FRLS insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing following 415V Switchgear and accessories in the Panel as per SLD ,specifications complete as required (General arrangement and schematic Drawings to be approved by the Deptt. before start of fabrication) . The Bus bars will be as per the IEC 6068-3-247 Standard.
Incomings
Outgoings
1 no. Sprinkler Pump(85KW) S/D Feeder
1 no. Hydrant Pump(85KW) S/D Feeder
1 no. Jockey Pump for sprinkler(5.5KW) S/D Feeder
1 no. Jockey Pump for Hydrant(5.5KW) S/D Feeder
1 no. Jockey Pump-2(5.5KW) S/D Feeder
1 no. Drencher Pump(11KW) S/D Feeder
4 no. Booster Pump(10KW) S/D Feeder
1 No. Fire Fighting DB
16A 4P 10KA MCB
1 No. Diesel Engine
16A DP 10KA MCB
Spare
1 no. 320A TP MCCB S/D Feeder
2no. 32A TP MCCB S/D Feeder
Diesel Engine Control
NS 3.23 : PLUMBING PHE(UTILITY) PANEL
Supply, installation, testing and commissioning of cubical type LT switchgear suitable for 415V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for frame work and covers, 3mm thick for gland plates including cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable capacity extensible type TPN Aluminium Alloy bus bars of high conductivity, bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5sq.mm. FRLS insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing following 415V Switchgear and accessories in the Panel as per SLD ,specifications complete as required (General arrangement and schematic Drawings to be approved by the Deptt. before start of fabrication) . The Bus bars will be as per the IEC 6068-3-247 Standard.
INCOMING
300A TP+NL(SEPARATE NEUTRAL LINK) 36KA MICROPROCESSOR BASED MCCB WITH O/L, S/C & E/F (LSIG) RELEASED, EXTENDED OPERATING HANDLE, SPREADER TERMINALS, 1C/O AUX. SW.+TAC
Outgoings
Outgoing 63A MCCB Feeder - 10 Sets
63A 3P 25KA MCCB with O/L,S/C Thermal Mag.Release
Outgoing 32A MCCB Feeder - 4 Sets
32A 3P 25KA MCCB with O/L,S/C Thermal Mag.Release
Outgoing 16A MCCB Feeder - 9 Sets
16A 3P 25KA MCCB with O/L,S/C Thermal Mag.Release
Outgoing 16A MCB Feeder - 1 Sets
16A TPN 10KA MCB
Outgoing 5.5KW DOL Feeder - 2 Sets
32A 3P MCCB with Magnetic S/C Release
NS 4 : Distribution Transformer
NS 4.1 : Supplying, installation, testing and commissioning 3 phase, 33/0.433kV, 50 Hz., 1000 kVA, indoor type, vaccum cast coil (VCC) dry type cast resin transformer, copper wound , Dyn11 vector group, with delta connection on HV side & star connection on LV side with additional neutral brought out on load side, for indoor use continuous duty, average temp rise of winding (at principal tap) 115°C at ambient temp max 50°C & Min -5°C at full load rating, with tapping (with off circuit bolted links type tap changer) for off load +5 to - 5% @ 2.5% in +2/-2 Steps, HV variation, class of insulation H/H, method of cooling AN, no load loss at rated voltage & frequency (+15% IS Tol) 2.80 kW, full load loss at rated current 9.00 kW, with 98.83% efficiency at full load & 99.00 % at 1/2 full load Efficiencies at 75 Deg. C at Unity Power Factor, with 125 KV peak full wave lightning impulse withstand voltage with complete enclosure having IP 23 degree of protection, cable box arrangement at HV side & bus duct at LV side ,with rating & diagram plate, base channel,lifting lugs, earthling terminals & WTI scanner with 3 PT-100 sensors,etc. standard accessories complete with test certificate (as per IS:11171 & IEC 60076-11) with necessary permissions of Electrical Inspector Note: The Maximum allowable Transformer Losses should be in compliance to ECBC Norms for 50% and 100% Load @ 75° C.
NS 4.2 : Supplying, installation, testing and commissioning 3 phase, 33/0.433kV, 50 Hz., 1600 kVA, indoor type, vaccum cast coil (VCC) dry type cast resin transformer, copper wound , Dyn11 vector group, with delta connection on HV side & star connection on LV side with additional neutral brought out on load side, for indoor use continuous duty, average temp rise of winding (at principal tap) 115°C at ambient temp max 50°C & Min -5°C at full load rating, with tapping (with off circuit bolted links type tap changer) for off load +5 to - 5% @ 2.5% in +2/-2 Steps, HV variation, class of insulation H/H, method of cooling AN, no load loss at rated voltage & frequency (+15% IS Tol) 3.70 kW, full load loss at rated current 13.50 kW, with 98.94% efficiency at full load & 99.12 % at 1/2 full load Efficiencies at 75 Deg. C at Unity Power Factor, with 125 KV peak full wave lightning impulse withstand voltage with complete enclosure having IP 23 degree of protection, cable box arrangement at HV side & bus duct at LV side ,with rating & diagram plate, base channel,lifting lugs, earthling terminals & WTI scanner with 3 PT-100 sensors,etc. standard accessories complete with test certificate (as per IS:11171 & IEC 60076-11) with necessary permissions of Electrical Inspector. Note: The Maximum allowable Transformer Losses should be in compliance to ECBC Norms for 50% and 100% Load @ 75° C.
NS 5 : DG Set
Providing, Installing, Testing and Commissioning of ‘Silent Type’ Diesel generating set alongwith having Prime Power Rating of 2x 1010 KVA and 1 x 500 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor and consisting of the followings:
a) Diesel Engine:
Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories.
b) Engine mounted Instrument Panel fitted with and having digital display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lub. Oil trip indication
(ix) Engine Hours indication
c ) Alternator :
Synchronous alternator rated at 1010 KVA and 500 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class- F/H insulation.
d ) Base Frame & Foundation :
Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
e ) Fuel Tank :
Daily service fuel tank of 990 liters capacity fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. The first filling of Diesel is covered in the Item.
f ) Exhaust System :
Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor.
g ) Starting System
12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180 Amp. Hour capacity lead acid type) as required as per specifications.
h) Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications.
NS 5.1 : 500 KVA (Prime Power Continuous Duty) DG Set Complete in all respect
NS 5.2 : 1010 KVA (Prime Power Continuous Duty) DG Set Complete in all respect
NS 6 : Design, supply and fixing MS class-B exhaust pipe of following dia Wewlded black MS B class pipe conforming to 3589 cut to required lengths and installed with necessary bends, supports and clamps, anti vibration mountings. The exhaust pipes shall be insulated with 75 mm thick mineral wool (density 125 kg/m3) insulation wrapped in chicken mesh and clad with 26 gauge aluminium sheet
NS 6.1 : 200 mm dia
NS 6.2 : 300 mm dia
NS 6.3 : 400 mm dia
NS 6.4 : 500mm dia
NS 7 : SS Fleexible bellows
NS 7.1 : Supply and installation of SS Flexible Bellows, 12" dia. (300 mm NB , 200 mm long), complete with counter flanges, heat resitant gaskets, nuts-bolts-washers etc., complete as required.
NS 7.2 : Supply and installation of SS Flexible Bellows, 16" dia. (400 mm NB , 200 mm long), complete with counter flanges, heat resitant gaskets, nuts-bolts-washers etc., complete as required.
NS 7.3 : Supply and installation of SS Flexible Bellows, 20" dia. (500 mm NB , 200 mm long), complete with counter flanges, heat resitant gaskets, nuts-bolts-washers etc., complete as required.
NS 8 : Design, Supply and Installation of steel structure work for DG Exhaust piping as per drawing including painting work etc as required at Site. The Design of exhaust structure including foundation is covered in the scope. Construction of Exhaust structure foundation will be not covered in the scope.
HT CABLES
NS 9: Supply of 3 x 240 sq. mm. aluminium 33 kV(E), XLPE armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification
LT CABLES
NS 10 : Supply of PVC / XLPE ARMOURED Cables 19 C x 1.5 Sqmm with copper Conductor 1100 V. Grade conforming to IS : 7098 (Pt-1) 1988
NS 11: Supply of 1.1 kV LT UG cable having aluminium conductor PVC insulated, extruded inner sheathes, galvanized, steed strip confirming to IS 3975:1990 (No. of strip indicated in GTP) & extruded PVC outer sheathed armoured cable with specified IS-1554 Part-1:1988
NS 11.1 : 3.5 core 300 Sq.mm
NS 11.2 : 3.5 core 240 Sq.mm
NS 11.3 : 3.5 core 185 Sq.mm
NS 11.4 : 3.5 core 150 Sq.mm
NS 11.5 : 3.5 core 95 Sq.mm
NS 11.6 : 3.5 core 70 Sq.mm
NS 11.7 : 3.5 core 50 Sq.mm
NS 11.8 : 3.5 core 35 Sq.mm
NS 11.9 : 3.5 core 25 Sq.mm
NS 11.10 : 3 core 95 Sq.mm
NS 12 : Supply of 1.1 kV LT PVC / XLPE ARMOURED Cables with COPPER Conductor 1100 V. Grade
NS 12.1 : 4 core 10 Sq.mm
NS 12.2 : 4 core 6 Sq.mm
NS 12.3 : 4 core 4 Sq.mm
NS 12.4 : 3 core 4 Sq.mm
NS 12.5 : 4 core 2.5 Sq.mm
NS 12.6 : 2 core 1.5 Sq.mm
NS 13 : Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required
NS 13.1 : 4 core 6 Sq.mm
NS 13.2 : 4 core 4 Sq.mm
NS 13.3 : 3 core 4 Sq.mm
NS 13.4 : 4 core 2.5 Sq.mm
NS 13.5 : 2 core 1.5 Sq.mm
NS 14 : Supply and Installation of following size of G.I ladder type cable tray,suspended from the ceiling with suspenders/ attached to wall by anchoring, as required, including bolts & nuts, painting suspenders etc as required
NS 14.1 : Hot dipped galvanized ladder type cable tray manufactured from 14 swg (2.0 mm thick) GI sheet of 1000 mm width & 100 mm height comprising all required standard accessories.
NS 14.2 : Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories.
NS 14.3 : Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
NS 15 : Supplying, installation testing & commissioning FP ACB 1250A, 50 KA breaking capacity, 415 VA, draw out type in existing plug-in box
NS 16 : SITC of Earth Strip
NS 16.1 : SITC of 50 x 10 mm GI Strip
NS 16.2 : SITC of 50 x 6 mm GI Strip
NS 16.3 : SITC of 40 x 6 mm GI Strip
NS 16.4 : SITC of 50 x 6 mm Cu Strip
NS 17 : Providing and fixing of GI Test Link Box
NS 18 : Providing and fixing of 1 meter wide, antiskid rubber mat of reputed make to be spread in front of switchgear of following voltage grade as per IS 15652:2006
NS 19 : Providing & fixing danger plates made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscriptions in signal red colour on front side as read
High Voltage- size 250mm x 200mm
Medium Voltage- size 200mm x 150mm
NS 20 :Providing First Aid Box as approved by St. John Ambulance Brigade/Indian Red Cross conforming to IS 2217:1963
NS 21 : Supply and fixing shock treatment chart duly mounted on a wooden frame with 5mm thick glass as reqd.( approximate front area 1.20 sq meter)
NS 22 : Supply & Fixing safety instruction chart duly framed with 5mm thick glass as required(approx. front area 1.20 sq mt)
NS 23 : Supply & Fixing SLD chart duly framed with 5mm thick glass as required(minimum front area 1.20 sq mt)
NS 24 : Supply and fixing of set of 4 Nos. 9.5 Ltr capacity G.I bucket painted in post office red colour with prior coat of red oxide paint and written with white paint Fire and mounted on MS Angle iron frame with bucket of appropriate size and capacity including filling sand etc.
NS 25 : Supply and fixing of Auto glow type Exit sign stickers (100x300mm) for substation building
NS 26 : Supply of 33 KV Grade Rubber Hand Gloves
NS 27 : Online Uninterruptible Power Supply (UPS)
Supply, installation, testing and commissioning of IGBT based True online double conversion 3 phase output 3 phase input, K rated transformers UPS System , power factor 0.9 or more, inverter efficiency 94% and above with 30 minutes back up at full load including Required number of SMF batteries, interconnecting cables, battery racks with shroud and castor wheels etc.
NS 27.1 : 10kVA UPS
NS 27.2 : 20kVA UPS
NS 28 : Supply, Installation,testing and commissioning of LED Ground Mounted Bollard with a system lumen output of 300 lumens. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 3000K and CRI>75. The luminaire shall meet IP65 & IK10 rating with THD < 20% and PF > 0.9. The luminaire housing should made of pressure die cast aluminium with polycarbonate diffuser. The total power consumption should not exceed 8W (including driver). (Equivalent to Philips Make LED BOLLARD II "BCP150 LED3000/WW PSU GR").Installation of bollard light in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required
NS 29 : Supply ,installation ,testing and commissioning of LED Post top lantern designed to complement the geometry of the area having Pressure die cast housing . 27W-35W LED Post top Light with IP 65/IK07 protection ,CCT-4000K P.F>0.9.System efficacy>85lm/watt (Equivalent Philips LED post top BGP161 LED2500/NW PSU 220-240V 7043 IN or Havells Victoria 35W)
NS 30 : Supply ,installation,testing and commissioning of Li- Fe Solar Standalone Street Light system 24W including LED street Light with in-built SCC, SPV Panel, LiFeP04 Battery, HDG Tubular Pole.
NS 31 : Supply ,installation ,testing and commissioning of New generation energy saving and environmental friendly long life LED 45 W street light made up of pressure die cast aluminium housing with high power LED as lighting source having minimum system level efficacy of 100 lm/watt.Opening seperate driver compartment with IP66 protection and impact resistance of IK07. Operating voltage 140-270 volts. Minimum Surge Protection of 4kV.( Equivalent to Philips Model No : Endura Smartbright 45W Streetlight BRP052 LED045)
NS 32 : Supply , installation, testing & commissioning of GI decorative pole, primered, painted & factory finished. The column shall also be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be built into the pole with base plate including wire and wiring inside the following poles from the luminaire to the MCB with 3 x 2.5 sq.mm, flexible, copper wire including connections etc.as requred. (Similar to Bajaj Cat. BOP 5030 or equivalent as per list of approved makes)
NS 33 : Supply, installation, testing and commissioning of automatic linear pneumatic Tube Detection based CO2 INDIRECT SYSTEMS as per IS 15222 Base System for transformer including CO2 Cylinder 22.5kg capacity (Cylinders shall be CCOE approved and manufactured to IS:7285), complete with all necessary s, fittings, support and accessories, connected with IHP Valve,End of Line adaptor NRV, Pressure Switch UL Listed,Flexible Polymer Detection Tube with all necessary fittings & supports. UL Listed, Discharge Piping and 3 Nozzles & Fittings,Manual release , Helath Monitoring cum alarm Panel,Auto weight measuring Unit with digital /analog display.
NS 34 : Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra)
Bidder Name
Amount
HITECH ERECTORS PVT. LTD.(GSTN-07AAACH0859B1Z0)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
Technical_Bid.pdf
Tender Documents • 1.24 MB
BOQ_102475.xls
BOQ • 0.69 MB
Drawings.pdf
Additional Documents • 5.98 MB