Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAccepted-Finance 30 74 BLOCK NO EXTRA 30 TRILOK PURI DELHI EAST DELHI 110091 | EAST | DELHI | 110091 | ₹1.9 Cr | L1 | Accepted-Finance Selected |
| 2 | L2₹2.1 CrAccepted-Finance | ₹2.1 Cr | L2 | Accepted-Finance Selected |
| 3 | L3₹2.3 CrAccepted-Finance GROUND FLOOR G 1154 A MANSAROVAR PARK SHAHDARA DELHI 110032 | SHAHDARA | DELHI | 110032 | ₹2.3 Cr | L3 | Accepted-Finance Selected |
| 4 | L4₹2.4 CrAccepted-Finance 322 AGGARWAL MODERN BAZAR C 33 LAWRENCE ROADS DELHI 110035 | DELHI | NORTH WEST DELHI | DELHI | 110035 | ₹2.4 Cr | L4 | Accepted-Finance Selected |
| 5 | L5₹2.8 CrAccepted-Finance | ₹2.8 Cr | L5 | Accepted-Finance Selected |
Tender Value
₹2.0 Cr
EMD Value
₹3.9 L
Closing Date
29 Jun 2026, 3:00 pmClosed
Executive Engineer (E)
O/o EE(E) PWD EMD M-351, R.No.185, Old Sectt Delhi
Construction of New Pump House / Sump Well at Hakikat Nagar under Sub Division-2 of CND-R Division during 2025-26. (SH- SITC of Compact substation, DG Set and Panels with related E and M Works).
2026_PWD_294044_1
21/NIT/SE/CND/PWD/2026-27
Open Tender
Miscellaneous Services
90 days
Hakikat Nagar
Please refer Tender documents.
10 documents required · 10 mandatory
₹0
₹3.9 L
30 Jun 2026
22 Jun 2026
29 Jun 2026
22 Jun 2026
29 Jun 2026
22 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SUB Head No. I (Substation Equipment’s) | |||||
| 1.01 | Supplying, installation, testing & commissioning of Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. with Connection between RMU & transformer shall be using 3 nos. 1C X 185 sq.mm. Aluminium unarmoured (UE) XLPE cable and connections from Transformer to LT Panel comprising of 800Amp ACB shall be by Aluminium Busbar with following equipments. | - | - | - | - |
| 1.02 | Package substation will have the following equipments | - | - | - | - |
| 1.03 | H.T Switch Gear | - | - | - | - |
| 1.04 | 11kV, 630Amps 25KA for 1 Sec. SF6 insulated Non-Extinsible Compact switchgear consisting of Three (03) Nos. Motorised Vacuum Circuit Breaker (VCB) along with one no. 11 KV 630A Air Insulated Metring Cubicle having inbuilt load break switch and earth switch within SF6 insulated robotically welded non ferrite non magnetic stainless steel enclosure of thickness 2.5mm having IP 67, with series trip, self powered microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection. Interconnection between HT switchgear and transformer shall be using 1Cx3x185 sq.mm Al. unarmorured (UE) XLPE Cable, digital multifunction meter with measuring CT with etc. as reqd. | - | - | - | - |
| 1.05 | RMU-NON-Extensible (3 Nos. vacuum Circuit Breaker with AL Busbar)-BIL 28/75kV RMU-NON-Extensible.
1. 11kV, 630Amps 25KA for 1 Sec. SF6 insulated Non-Extinsible Compact switchgear consisting of Three (03) Nos. Motorised Vacuum Circuit Breaker (VCB
2. Operation of breaker – Motorized
3. Self Powered Electronic numerical protection relay providing over-current & earth fault protection – CSPR relay
4. Tape Wound protection current transformers (Details During Detailed Engineering)
5. Capacitive voltage indication fixed type.
6. ON, OFF, EARTH indication on the front mimic of the panel.
7. Cable box for termination of cable suitable up to 3 Nos. X 1C X 185 Sq. mm
8. Cable cover standard.
9. Emergency trip push button.
10. Shunt trip Coil - 24V DC 11. Minimum 40 no Dead Short Ckt life of VI
RMU accessories: -
Operating Handle.
Standard Manometer for SF6 gas pressure indication
Right Angled Cable Boots suitable for 1 Run x 3 C x 400 Sq mm
Battery 24V DC, 12Ah & Battery Charger - 5A | - | - | - | - |
| 1.06 | TRANSFORMER 400KVA , 11KV/0.433KV DYn11 Cast resin Dry type transformer with off load TAP Links having tapping range of +5% to -5% in steps of 2.5%, Z% : 4% (IST) with NLL at rated voltage & freq : 1.8KW (IST) and LL at 75 Deg. C & at Principal tap : 6.5KW (IST), Class F insulation, temp rise : 90 DegC , 3nos. Surge arrestors 9kV 10kA polymeric / Eq, 1 no. Digital WTI with Alarm & Trip contacts. outdoor type Transformer confirming with IP - 33 or more protection and impedance should be, as per relevant I.S. and maximum allowable losses, as per ECBC compliance with upto date amendments, and confirming to IS 11171:1985 & as per specification attached complete in all respects etc as required at site (The acceptable tolerances in regard to transformer shall be, as per relevant IS Code).
Transformer Accessories
Winding temperatue Indicator (Local as well as Remote)
LT Busbar - 1000 A Aluminium Busbar (100% for Phase & 50% for Neutrals) Current density 1amp/sqmm, Fabrication using 2mm thick CRCA sheet steel complete with internal wiring consisting of following.
Voltage Rating- 433V
Current Rating - 1000A
LT Switch Gear | - | - | - | - |
| 1.07 | ACB 4 Pole, 800 Amps EDO type, Ics=Icu=Icw=50kA, microprocessor release LSIG trip unit with variable current & time delay settings for O/L, S/C, E/F, Fault indication LEDs (for Overload, Short circuit, earth fault), In built Energy metering, Power Factor, Zone selective interlocking, Thermal Memory, with Last 10 trip history with nature of fault date & time, TNC Switch & LR Switch etc. as reqd.
On, OFF, TRIP lamp
R/Y/B indicating lamps
CTs 800/5A, AC. CL. 1, 5 VA
Digital MFM - EM 6400 NG, AC. CL. 1.0
ENCLOSURE for PSS | - | - | - | - |
| 1.08 | The enclosure shall be made of 2.0 mm thickness Galvanized Sheet Steel tropicalised to meet Indian weather conditions including all the partition sheets & doors. The base of the enclosure shall be of 4.0 mm thickness Hot Dip Galvanized Sheet Steel to ensure rigidity for easy transport & installation. Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for Transformer Compartment. The Enclosure to be tested for Internal Arc fault test to the tune of atleast 20 KA for 1 second adhering to as per latest IEC 62271- 202.The temperature rise test on enclosure for K10class. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrangement. Transformer Compartment will be provided with Cover. The Compartment illumination lamp with door operated switch shall be provided for.HT and LT compartment. Lifting(Bucket) Arrangement shall be provided with each PSS. For Complete ownership of the solution, All components like ACB, MCCB, Capacitors, RMU & VI, Transformer, Protection relays are of PSS OEM make. Authorised PSS License Partner can assemble the PSS as per guidelines of the OEM. | - | - | - | - |
| 1.09 | EARTHING - Internal earthing connection by using 50 X 6 mm Aluminium Strips
HV KIT - As per manufacturer's specifications/standard
COPPER FLEXIBLE- As per manufacturer's specifications/standard
First aid box as approved by St. john Ambulance Brigade / Indian Red Cross society conforming to IS : 2217 - 1963.
Shock treatment chart duly mounted on a wooden frame with glass on, as required in 2 languages (Hindi & English). | 2 | Job | 37,41,656 | ₹74,83,312 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.52 MB
28EE21SETenderNotice.pdf
Tender Documents • 2.51 MB
BOQ_390910.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid