Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.8 LAccepted-AOC | L1 | Accepted-AOC WORK ORDER ISSUED | |
| 2 | L2₹2.8 L+₹1,778 (0.64%)Rejected-Finance 85 BASANTA BABU ROAD KANCHRAPARA | KANCHRAPARA | NADIA | WEST BENGAL | L2 | Rejected-Finance NOT L1 BIDDER | |
| 3 | L3₹2.8 L+₹3,160 (1.13%)Rejected-Finance B 13 109 NIMTALA BUS STAND P O P S KALYANI NADIA PIN 741235 | KALYANI | NADIA | WEST BENGAL | 741235 | L3 | Rejected-Finance NOT L1 BIDDER | |
| 4 | L4₹2.8 L+₹5,404 (1.94%)Rejected-Finance | L4 | Rejected-Finance NOT L1 BIDDER |
Tender Value
Refer Docs
EMD Value
₹5,580
Closing Date
21 Mar 2025, 3:00 pmClosed
Assistant Engineer
Office of the Assistant Engineer Ranaghat Electrical Sub-Division, P.W.D P.O.-Ranaghat, Dist- Nadia
Electrical Installation work for the Establishment of blood Bank in the place of old isolation ward at Santipur S.G Hospital in the district of Nadia -- SITC of Fire detection system.
2025_WBPWD_824383_1
WBPWD/AE/e-NIT- 10/RH of 2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Santipur S.G. Hospital
Please refer Tender documents.
4 documents required · 4 mandatory
₹5,580
Office of the Assistant Engineer Ranaghat Electric
24 Apr 2025
7 Mar 2025
24 Mar 2025
7 Mar 2025
21 Mar 2025
11 Mar 2025
10 Mar 2025
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 2 Loops fire alarm control panel ( VDS / UL / FM / ULC/ EN / LPCB approved ) fully networkable with each loop capable of taking minimum 125 devices per loop, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC/ EN / LPCB approved ) with twist lockable removal base including connections as per specifications complete as reqd and having IP as per recommended standard.(Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, testing and commissioning of Analog Addressable Intelligent Multi-detector(Heat cum Smoke) ( VDS / UL / FM / ULC/ EN / LPCB approved ) with twist lockable removal base including connections as per specifications complete as reqd and having IP as per recommended standard.(Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC/ EN / LPCB approved )soft addressable type. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC/ EN / LPCB )approved. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC/ EN / LPCB approved ) for monitoring flow switches / Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, Testing & Commissioning of Addressable Relay Modules ( VDS / UL / FM / ULC/ EN / LPCB approved ) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply, Installation, Testing & Commissioning of Isolator Modules ( VDS / UL / FM / ULC/ EN / LPCB approved ) for isolate the system from any external hazard with all necessary accessories as required. (Approved Make: Bosch / Apollo / Morley / Gst/ Esser / Siemens )
Supply & Laying of 2C*1.5 sqmm flaxiable copper wire(Make: Finolex/MEM/Technoflex/Polycab) with 20mm NB PVC rigid conduit pipe on the surface of the wall. As per direction of EIC.
RONY ENTERPRISE (BID ID -6249696)
HALDER ELECTRIC (BID ID -6249813)
MAM ENTERPRISE (BID ID -6257806)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .