| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹53.3 LAccepted-AOC 27 ANNAI SATHYA NAGAR VALASARAVAKKAM CHENNAI 600 087 | CHENNAI | TAMIL NADU | 600087 | ₹53.3 L | L1 | Accepted-AOC Responsive L1Tenderer |
| 2 | L2₹54.4 LRejected-AOC | ₹54.4 L | L2 | Rejected-AOC Responsive L2 Tenderer |
| 3 | L3₹61.2 LRejected-AOC | ₹61.2 L | L3 | Rejected-AOC Responsive L3 Tenderer |
Tender Value
Refer Docs
EMD Value
₹46,400
Closing Date
20 Jan 2026, 3:00 pmClosed
Superintending Engineer (C and M)
Office of Superintending Engineer, Contracts Monitoring, 4th Floor, CMWSS Board, No.1, Pumping Station Road, Chintadripet, Chennai 600 002
Improvement works to existing Electromechanical arrangements to 10 Lakh Litre and 5 Lakh Litre UGT of Ezhil Nagar and Tsunami (ETRP) Tenements in Depot 195 and 196, Area XV.
2026_CMWSS_638502_1
CNT/WSS/DEP/3710/2025-26
Open Tender
Electrical Works
Chennai
Class IIB and IVA and above
5 documents required · 5 mandatory
₹0
₹46,400
11 May 2026
2 Jan 2026
21 Jan 2026
2 Jan 2026
20 Jan 2026
12 Jan 2026
REPLACEMENT OF EMI FOR TSUNAMI 5LL UGT
Supply, delivery, erection, testing and commissioning of electrically driven, water lubricated horizontal split case water supply pumpset with bronze impellers, other accessories suitable for following duty point, including required common base plate, with suitable starter, fasteners including incidental civilworks etc. complete.
UNIT- 1 - 2760 lpm against a total head of 25 m
Supply, delivery, erection, testing and commissioning of vacuum pump of suitable capacity to prime the above pump, including required capacity 3 Ph, 415 V, AC, 50 Hz, Electrical Motor along with a common base plate for the pump and motor, coupling pulley, suitable starter, fasteners including incidental civil works and connecting with the suction pipe of the above pump sets including supply of necessary materials and labour etc.complete as instructed at site.
Vacuum Pump - 10 HP
Supply, delivery, erection, testing and commissioning of following sizes of power shunt capacitor for power factor improvement, suitable to operate on 415V, 3Ph,50Hz A/C supply, on suitable angle iron frame-works (37.5 mm x 37.5 mm x 6.24mm ) at a height of 0.25m from the ground, including earthing and incidental civil works etc., complete.
UNIT- 1 - 9 kVAR
Vacuum Pump - 4 kVAR
Capacity of M.V. Panel - 100 Amps
100 A FP Motorised Online Change over Switch 25 kA
63 A TP MCCB 25 kA for UNIT- 1
32 A TP MCCB 25 kA for Vacuum Pump
63 A TP MCCB 25kA (for UNIT- 1 cap.)
32 A TP MCCB 25kA (for Vacuum Pump cap.)
32 A TPN MCB 10kA (for LDB)
Supplying and fixing of cable gland and termination with Al. cable lugsfor the following sizes of PVC insulated PVC sheathed armoured alumunium LT UG cable and with earth connection.
size 3.5C, 50 Sqmm (EB)
size 3.5C, 50 Sqmm (DG)
Size 3.5C, 25 sq.mm (UNIT- 1)
Size 3C, 6 sq.mm (Vacuum Pump)
size 3C, 10 Sqmm (UNIT- 1 capacitor)
size 3C, 6 Sqmm (Vacuum Pump capacitor)
size 3 core 2.5 sq.mm copper
Supply, delivery and fixing of dust and vermin proof Local Push Button station near the pumpset with 1 No"ON" and 1 No "OFF" push buttons (the "OFF" push button shall be locable in "OFF" position).
Supply, delivery and installation of water level measuring system up to 1 mm accuracy to measure up to 30 m depth in wells/OHTs/ sumps with suitable sensor, level transducer with transmitter, 2 or 4 wire loop, all wetted parts in SS304 or above and with Remote control and suitable LED display unit easily readable upto 10m distance, cabinet to house remote display unit, Low/High alarm with suitable speaker, suitable cables with data storage capacity for 1 year and data transfer facility and with all required accessories including 1 year free replacement warranty etc., complete.
REPLACEMENT OF SUCTION AND DELIVERY ARRANGEMENTS FOR EZHIL NAGAR TSUNAMI 5LL UGT
250x150mm D/F DI taper
250mm DI D/Fl 90 deg bend
250mm D/Fl 3m length pipes
250mm CI bell mouth
150x125 mm D/F DI taper
Supplying and delivery at site, conveying and fixing CI sluice valves (PN 1.0) with tail pieces of following sizes conforming to IS:including loading, unloading, Transportation charges and stacking at the site etc complete as per specifications.
150mm CI Non return valves
150 mm CI Sluice valves with actutor
Supply,delivery, installation and testing of Electromagnetic flow meter for 200mm dia Delivery Pipeline of Ezhil Nagar Tsunami 5LL UGT
Supply, delivery, erection, testing and commissioning of Electromagnetic Flow Meter shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in different units (Kiloliters / Cubic meter) and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3 m/sec to 4 m/sec and be constructed as follows: Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon steel flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber/ Polyurethrene/ PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow. The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects. Coil Housing shall be fabricated from stainless steel (SS304)/ Die cast /Aluminium/ Carbon steel with anticorriosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation with IP68 Protection. Signal Converter shall be pulsed DC coil excitation type with auto zeroing.
The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output. The microprocessor based signal converter shall have a self-diagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume”. Converter shall be supplied with a programmable low flow drop out, higher flow and empty pipe zero return. The signal converter housing should be die-cast aluminum with glass window. The converter cum transmitter should be fully programmable from the front facia. The programming should be user friendly, self-prompting menu driven. Flow meter test calibration certificate from FCRI, flow test lab / NABL accredited lab to be furnished as per the details provided in the specificaion - with 5 years warranty
Specials for Electromagnetic FlowMeter
200 mm F/Spi Tail Piece
200 mm F/Soc Tail Piece
Jointing the DI Socket/spicot specials with rubber gasket(Tyton joint) including cost of jointing materials etc. complete.
Jointing the DI double flanged pipes and specials with rubber insertion to the required specification with M.S bolts and nuts including the cost of jointing materials etc. complete.
Cutting of DI Pipes true to axis and finishing the ends complete .
REPLACEMENT OF EMI FOR EZHIL NAGAR 10LL UGT
REPLACEMENT OF ELECTRICALLY DRIVEN HORIZONTALLY SPLIT CASE WATER SUPPLY PUMPSETS WITH ALLIED ELECTRICAL WORKS FOR EZHIL NAGAR 10LL UGT
Supply, delivery, erection, testing and commissioning of electrically driven, water lubricated horizontal split case water supply pumpset with bronze impellers, other accessories suitable for following duty point, including required common base plate, with suitable starter, fasteners including incidental civilworks etc. complete.
UNIT- 1 - 7850 lpm against a total head of 25 m
Supply, delivery, erection, testing and commissioning of vacuum pump of suitable capacity to prime the above pump, including required capacity 3 Ph, 415 V, AC, 50 Hz, Electrical Motor along with a common base plate for the pump and motor, coupling pulley, suitable starter, fasteners including incidental civil works and connecting with the suction pipe of the above pump sets including supply of necessary materials and labour etc.complete as instructed at site.
Vacuum Pump - 10 HP
Supply, delivery, erection, testing and commissioning of following sizes of power shunt capacitor for power factor improvement, suitable to operate on 415V, 3Ph,50Hz A/C supply, on suitable angle iron frame-works (37.5 mm x 37.5 mm x 6.24mm ) at a height of 0.25m from the ground, including earthing and incidental civil works etc., complete.
UNIT- 1 - 20 kVAR
Vacuum Pump - 4 kVAR
Capacity of M.V. Panel - 200 Amps
200 A FP Motorised Online Change over Switch 25 kA
150 A TP MCCB 25 kA for UNIT- 1
32 A TP MCCB 25 kA for Vacuum Pump
63 A TP MCCB 25kA (for UNIT- 1 cap.)
32 A TP MCCB 25kA (for Vacuum Pump cap.)
32 A TPN MCB 10kA (for LDB)
Supplying and fixing of cable gland and termination with Al. cable lugsfor the following sizes of PVC insulated PVC sheathed armoured alumunium LT UG cable and with earth connection.
size 3.5C, 150 Sqmm (EB)
size 3.5C, 50 Sqmm (DG)
Size 3.5C, 95 sq.mm (UNIT- 1)
Size 3C, 6 sq.mm (Vacuum Pump)
size 3C, 25 Sqmm (UNIT- 1 capacitor)
size 3C, 6 Sqmm (Vacuum Pump capacitor)
Size 4 core 10 sq.mm LDB
size 3 core 2.5 sq.mm copper
Supply, delivery and fixing of dust and vermin proof Local Push Button station near the pumpset with 1 No"ON" and 1 No "OFF" push buttons (the "OFF" push button shall be locable in "OFF" position).
Supply, delivery and installation of water level measuring system up to 1 mm accuracy to measure up to 30 m depth in wells/OHTs/ sumps with suitable sensor, level transducer with transmitter, 2 or 4 wire loop, all wetted parts in SS304 or above and with Remote control and suitable LED display unit easily readable upto 10m distance, cabinet to house remote display unit, Low/High alarm with suitable speaker, suitable cables with data storage capacity for 1 year and data transfer facility and with all required accessories including 1 year free replacement warranty etc., complete.
Supplying and delivery at site, conveying and fixing CI sluice valves (PN 1.0) of following sizes conforming to IS:including loading, unloading, Transportation charges and stacking at the site etc complete as per specifications.
250mm CI Non return valves
250 mm CI Sluice valves with actuator
Supply,delivery, installation and testing of Electromagnetic flow meter for 250mm dia Delivery main of Ezhil Nagar 10LL UGT
Supply, delivery, erection, testing and commissioning of Electromagnetic Flow Meter shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in different units (Kiloliters / Cubic meter) and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3 m/sec to 4 m/sec and be constructed as follows: Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon steel flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber/ Polyurethrene/ PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow. The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects. Coil Housing shall be fabricated from stainless steel (SS304)/ Die cast /Aluminium/ Carbon steel with anticorriosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation with IP68 Protection. Signal Converter shall be pulsed DC coil excitation type with auto zeroing.
The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output. The microprocessor based signal converter shall have a self-diagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume”. Converter shall be supplied with a programmable low flow drop out, higher flow and empty pipe zero return. The signal converter housing should be die-cast aluminum with glass window. The converter cum transmitter should be fully programmable from the front facia. The programming should be user friendly, self-prompting menu driven. Flow meter test calibration certificate from FCRI, flow test lab / NABL accredited lab to be furnished as per the details provided in the specificaion (with 5 years warranty)
Supply, delivery , conveying and fixing DI D/F pipes as per IS:8329/2000 and DI SS/DF specials like Tee, Bends ,Tapers and Tailpieces as per IS:9523/2000 including loading,unloading and stacking at the site excluding earthwork excavation as directed by the Engineer at site etc complete.
Specials for Electromagnetic FlowMeter
250 mm F/Spi Tail Piece
250 mm F/Soc Tail Piece
Jointing the DI Socket/spicot specials with rubber gasket(Tyton joint) including cost of jointing materials etc. complete.
Jointing the DI double flanged pipes and specials with rubber insertion to the required specification with M.S bolts and nuts including the cost of jointing materials etc. complete.
Cutting of DI Pipes true to axis and finishing the ends complete .
Sub Total
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.03 MB
CHECKLIST3710.pdf
Tender Documents • 0.10 MB
BOQ_764184.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid