Loading…
Loading…
Tender Value
₹4.1 L
EMD Value
₹5,000
Closing Date
11 Sept 2026, 5:00 pmClosed
Dy. Executive Engineer, Sachivalaya Complex Electrical Sub Division No 2, Gandhinagar.
Renovation of Revenue Department office at 7th floor of block 11 at New Sachivalay Dist. Gandhinagar. ( Second Attempt )
341186
9/1
Open
Electrical
Works
Gandhinagar
7 documents required · 7 mandatory
₹600
Executive Engineer, SACHIVALAYA COMPLEX ELECTRICAL DIVISION,GANDHINAGAR
₹5,000
3 Sept 2026
3 Sept 2026
3 Sept 2026
11 Sept 2026
3 Sept 2026
BILL OF QUANTITIES(%TENDER)
:: BILL OF QUANTITIES::
Name Renovation of Revenue Department office at 7th floor of block 11 at New Sachivalay Dist. Gandhinagar.
Item No Description of item(with brief specification and reference to book of specifications) Qty Unit Amount
Replaced Old & Unservicable By New Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire
of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper
wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push &
accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single
mounting base frame covered with textured/metallic/white front plate modules erected on / in wall /
ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed.(f)
with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete Cat.
Replaced Old & Unservicable By New Point wiring for FAN with 2-1.5 sq.mm & earth wire of
sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper
wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free
EME step type electronic fan regulator mounted and accessories with earth continuity of following
2 type erected on PVC / Metallic/Wooden box, single mounting base frame covered with 10 Pt. 809.01
textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with
necessary ceiling rose / H.D.Connector as directed.(f) with medium class Rigid PVC pipe and
accessories erected concealed in wall/ceiling complete Cat. III
Replaced Old & Unservicable By New Point wiring for on board Looped Plug with 6A Modular type
switch & 5 pin socket erected on PVC / Metallic/Wooden box, single mounting base frame covered
3 with textured / metallic/white front plate modules erected on / in wall / ceiling with following type 8 Pt. 309.06
accessories Cat. III
Replaced Old & Unservicable By New Providing following type of Modular Type Accessories
mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured /
metallic/white front plate , modules erected with necessary connections as per site situation
directed by Engineer In charge.(1)One No. SP 6 Amp. Cat.III
(2) One No 5 pin plug Cat.III 10 Ea. 151.50
(3) Two Pin/RJ-11 Telephone Socket [A] For One Gang Cat.III 4 Ea. 160.59
(7) Blank Plate Single Cat.III 10 Ea. 25.25
(9) 16 Amp. SP one way switch Cat.III 4 Ea. 180.79
(10) 6/16Amp. Universal socket Cat.III 4 Ea. 199.98
(14) 6A/ 10A/ 16A/ 20A/ 25A/ 32A Double Pole Modular MCB Switch Cat.III 6 Ea. 410.06
Replaced Old & Unservicable By New Providing and erecting ISI mark Medium class RIGID PVC
PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC
fittings & Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in
approved manner as directed (b) 25 mm
Providing & erecting PVC Corrugated Flexible Conduit with required nos. of coupling, PVC bushes,
Check-nuts etc. complete of following sizes. (2) 25 mm
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid
material with ignition free and flame proof confirming BS with necessary end caps Internal and
external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following
sizes (2) 100 mm x 50 mm trunking
Supplying under floor pregalvanised corrosion proof rectangular sheet steel cable trunking of
mm thick having with stand point load up to 1.33 Ton & free from seepage of concrete of screed
water with all accessories,Junction Box,Joints as required and demanded by engineer-incharge
and laying/erecting as per OEM guidelines and as per instruction of engineer incharge having
following size of dimensions and No of compartments (W x D x T) Cat-III [3] 100mm x 25mm x
mm with one compartment
Replaced Old & Unservicable By Providing and erecting Mains with 1.1 KV grade FRLS PVC
insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected
9 concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated 100 Mtr. 58.58
stranded wire of green colour for earth continuity of following size (E) in existing pipe (a) 2 wire
(b) 2 wire 2.5 sq. mm 215 Mtr. 78.78
Replaced Old & Unservicable By New providing and erecting Mains with 1.1 KV grade FRLS PVC
insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on
wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour
for earth continuity of following size (E) in existing pipe (a) 2 wire 4 sq. mm
Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked
copper wires of following size to be erected as directed.(h) 2.50 Sq.mm 3 core round PVC sheathed
(j) 4.00 Sq.mm 3 core round PVC sheathed 36 Mtr. 159.58
Providing & Erecting approved make following size of TV Co-axial flexible cable comprising inner
conductor of solid bare copper insulated with Foam PE & Secondary conductor made of poly -
Aluminium film bonded Al. Braids @ suitable coverage overall sheathed with black PVC insulation.
Replaced Old & Unservicable By New Supplying & erecting approved make Telephone Cable
electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape &
13 sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C- 110 Mtr. 20.20
DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary
connections.[A] Conductor Size 0.5 mm (a) Unarmoured (2) Two Pairs
Supplying & erecting approved make LAN cable Cat 6A/Class EA cable shall be constructed of
AWG copper conductors with FEP Plenum (CMP) insulation. The copper conductors shall be
14 twisted in pairs and separated by a cross-divider. All four pairs shall be surrounded by a 160 Mtr. 166.65
nonconductive foil tape and a flame retardant jacket. The foil tape shall suppress the effects of alien
crosstalk.Rate approved
BILL OF QUANTITIES(%TENDER)
Item No Description of item(with brief specification and reference to book of specifications) Qty Unit Amount
Replaced Old & Unservicable By New Providing & erecting Switch board for Computer or electric
apparatus consisting of following modular type accessories mounted with PVC / Metallic
concealed/open box with single mounting base frame covered with textured/metallic /white front
15 plate,modules erected with necessary connections as directed 6 Ea. 1133.22
1 no. 6A/16A universal plug-switch combined.
3 nos. 6A Switch
3 nos. 6A 5 pin Plug For Modular Type Accessories Cat. III
16 Decorative call bell Ting-tong box type 250 volts complete erected 2 Ea. 71.71
Replaced Old & Unservicable By New Supplying and erecting LED indoor fittings with LEDs of
wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall
be made of thick sheet Steel conforming to IS: 513/CRCA/aluminium pressure die cast powder
coated and high U.V. & corrosion resistance with diffuser housed in aluminium casted body with
company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between
the ranges shown.) (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision
for spring loaded mounting clips complete.IP20 (ii) 11-15 watts, Surge-2 KV Cat-lll
(iv) 22-24 watts, Surge-2 KV Cat-lll 8 Ea. 758.51
B) LED Panel Light with provision for Plane front frame with translucent cover fixed to housing
complete.IP20 (vi) 36 watts, 24" x 24", Surge- 2KV Cat-lll
(I) Adjustable spot light with COB led having aluminium reflector of following wattage (i) 8 Watts
SITC `17` mm to 22mm surface type alumium profile with presairmatic fiber cable with self adasive
led strip conforming to IS: 513/CRCA/aluminium pressure die cast powder coated and high U.V. &
corrosion resistance with diffuser housed in aluminium casted body with company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: above description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between
the ranges shown.)
Replaced Old & Unservicable By New providing and erecting Miniature circuit breaker single pole
19 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be 18 Ea. 123.22
erected in existing box. confirming to IS 8828/1996 with ISI Mark Cat.III
Replaced Old & Unservicable By New Providing & erecting 415 V MCB Four Pole for Motor &
20 Inductive Load (C Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box 2 Ea. 811.03
having following capacity (c)63 Amp. Cat.III
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted
fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 &
21 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of 1 Ea. 2913.85
MCB to be used) suitable for (B) three phase incoming and single phase horizontal type outgoing
Per phase isolation type (PPI) (b) sheet steel double door (ii)6 way
Replaced Old & Unservicable By New providing and erecting Approved make RCCBs conforming to
IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and
22 suitable for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping 3 Ea. 2458.34
with all advance feature & do not incorporate any electronic component. for following Max. rating
erected as directed (ii) 40Amps. DP Cat.III
Providing and erecting FRLS-XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper
23 conductor for 1.1 kV. to be laid on wall with necessary clamps or in existing trench / pipe at road 50 Mtr. 1235.23
crossing or floor of following size of cables.(B) 4 core 16 Sq. mm
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated
24 armoured cable complete with out going tails, insulating tape etc for following size of cables.(D) 2 to 4 Ea. 47.47
4 core 16 Sq. mm
Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly
25 crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut 16 Ea. 12.12
bolts in an approved manner. (C) 16 Sq.mm.
Supply, Installation, Testing and Commissioning of suitable sweep, BEE 5 Star rated, Ceiling fan
with Brush Less Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust
free 3 nos.Aluminium blades, 2 nos. canopies, shackle kit with earthing provision, copper winding,
Power factor not < 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM,
26 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, with remote unit for Speed Control 10 Ea. 2885.57
and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree
C (Max.), suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload
protection , 50 Hz, Single phase AC Supply, earthing etc. Complete as required.[ Make shall be
approved by Engineer in Charge] (B) 1200 mm Sweep (48")
Replaced Old & Unservicable By New Supplying and erecting 19 / 20 mm. nominal bore Medium
Class M.S. Pipe down rod erected duly painted for fan complete with proper insulation without
leakage and earthing.
Providing Fan clamp of 30 x 5 mm flat of required length & 10 mm M.S. Bolt & Nuts erected with
28 necessary hook of 10 mm M.S. Round Bar. 10 Ea. 98.98
Replaced Old & Unservicable By New Supplying & erecting approved make low noise decorative
29 exhaust fan having square frame ABS body with inbuilt lowers & square frame.250mm with 1350 1 Ea. 1366.53
SITC of Face Plate - Dual (Keystone Jack,square) [Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
BILL OF QUANTITIES(%TENDER)
Item No Description of item(with brief specification and reference to book of specifications) Qty Unit Amount
SITC of Jack Cat 6 Keystone UTP [Approved by Competent Authority i.e. not Below the rank of
Executive Engineer ]
32 Providing and erecting Annealed bare Copper wire 8 to 16 SWG. 10 Kg 794.87
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode
consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped
G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of
mm having 200-250 Micron galvanising, connection terminal dia of 12mm with constant ohmic value
surrounded by highly conductive compound with high charge dissipation suitable for following type
of applications with chamber and heavy duty cover. (A)(approved make OEM has to submit test
certificate including value of earth resistance of installation duly stamped and signed by agency and
officer Incharge has to ensure the value of earthing resistane mentioned in test Certificate) & having
back fillingapproved
Supplying compoundmake
Inner chemical (CCM
refrigerator Compound)-
of 165 Ltr to 185Resistivity:-
Ltr storage0.2 ohm / meter
capacity, single testing
34 minimum 3 star rating. 1 Each 15116.67
Shifting of Split A.C. The Scope includes dismantling, shifting, re-installing & re-commissioning of
35 the units including topping up of Refrigerant gas, minor civil work wiring existing piping M S Stand 2 Each 1969.50
electrical cabling with PVC drown piping for 1.00, 1.5 & 2.0 TR capacity.
Replacing old & u/s by Supplying and erecting 15Watt LED Dimmable Sensor cum Driver indoor
Downlight fittings as per feature(1)Polycabonate housing duly powder coated (2)Motion based On-
Off-Dim operation(in-built) (3)Adjustable detection area 50%/100% (4)Adjustable hold time
5s/1min/5min/10min (5)Dimming %- 10% to 30% (6) Operating voltage range 198 to 264V AC (7)
36 Power factor more than 0.90 (8) Driver Efficiency more than 85% (9) Inbuilt surge protection 4KV 15 Each 565.50
(10) CCT 3000K to 6500K (11) Fixture efficacy more than 100 Lm/w (12) Sensor detection area
meter dia. (13) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for
spring loaded mounting clips complete.IP20 LM 79 and 80 report required for fitting
Replacing old & u/s by Supplying and erecting 15Watt LED On-Off Sensor cum Driver indoor
Downlight fittings as per feature(1)Polycabonate housing duly powder coated (2)Motion based On-
Off operation(in-built) (3)Adjustable detection area 50%/100% (4)Adjustable hold time
5s/1min/5min/10min (5) Operating voltage range 198 to 264V AC (6) Power factor more than
37 (7) Driver Efficiency more than 85% (8) Inbuilt surge protection 4KV (9) CCT 3000K to 6500K (10) 5 Each 545.50
Fixture efficacy more than 100 Lm/w (11) Sensor detection area 6 meter dia. (12) Square/ Circular
shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips
complete.IP20 LM 79 and 80 report required for fitting
Four lakh eleven thousand three hundred ninety-five point two two
I/ We am/are willing to carry out the work at_________% above / below percent (should be written in figure & words) of the estimated mentioned above. Amount of
my / our tender works out as under.
Estimated amount put to Estimated amount put to
(a) I/we hereby declare that we have visited the site and fully exquisite myself/ourselves with the Local situation regarding materials labour and other factors
pertaining to work before submitting Tender.
(b) I/we hereby declare that we have carefully studies the conditions of contracts. Detailed Specification and other tender document of this work and agree to
execute the same accordingly.
1 If required and found necessary material to be used for this work and brought at site will have to sent to Govt.approved laboratory. The qualified agency/
manufacturer of Particular product under testing will have to pay/ bear necessary charges.
2 All works shall be carried out as per public works Department hand book and other Specification.
3 Rates are inclusive of 1% Labour cess in tender amount so 1% of total amount of bill will be deducted from the bill.
3 Rates are inclusive of 1% Labour cess in tender amount so 1% of total amount of bill will be deducted from the bill.
4 The material to be used in this work must be as per instruction by under liason of Engg. In charge.The agency will have to agree to carried out the work as
per brand/make demand of concern deptt.
5 Contractor must have registration in E-2 & above class registered under elect. (R & B) division.
Sign of Dy. Exe. Engineer Exe. Engineer
Sachivalay Complex Elect. Sub-Div.No.-2 Sachivalay Complex Elect. Div
R. & B. Deptt. Gandhinagar R. & B. Deptt. Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
G S T LTR.pdf
GR.pdf
New SOR Revenue Block 11 7 floor dm.pdf
Revenue Block 11 7 floor boq.pdf
Revenue Block 11 -7 floor_SBD Book 30 06 2026.pdf
nivida 9.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .