Assistant Engineer, Balurghat Electrical Sub Divis
Purta Bhavan, 4th Floor, Kachari Raod, Balurghat, Dakdhin Dinajpur, Pin-733101
Servicing, Shifting and Re-Installation of One No. (01) 62.5 KVA DG set (Make-Jakson) at CMOH Office, Balurghat, Dakshin Dinajpur
2025_WBPWD_870081_1
WBPWDTE/AE/BESD/e-NIQ-14 of 2025-26(2nd Call)
Open Tender
Electrical Work/ Equipment
Item Rate
15 days
Balurghat
Please refer Tender documents.
6 documents required · 6 mandatory
₹9,210
21 Jul 2025
25 Jun 2025
11 Jul 2025
25 Jun 2025
9 Jul 2025
25 Jun 2025
Repair & Servicing charges of one no 62.5 KVA DG sets at site by authorised service partner of OEM.(Make- Jakson 62.5 KVA). Below mention materials are required: i) 001200240911 FILTER ELEMENT WITH O RING-- 01 No. ii) 001200240912 FLTR INSRT WITH O RING-- 01 No iii) LUB OIL FILTER (BOWL TYPE FILTER SMALL)-- 01 No iv) 123200198624 GREAVES LUB OIL CI4 -10 LTR PACK-- 01 No v) 123200198614 GREAVES LUB OIL CI4 - 5 LTR PACK vi) 601922100002 COOLANT ADDITIVE 1LT PACK-- 02 Nos vii) EXIDE BATTERY 12V 150AMP EXPRESS SERIES-- 01 No viii) AIR FILTER- ( F8348800, F8348900 )-- 01 Set ix) FREIGHT & FORWARDING CHARGES x) SERVICE CHARGES FOR ATTENDING OF DG SET
Transportation Charges for one no 62.5 KVA DG & AMF panel from Dist.Hospital campus to CMOH office, D/D, including loading and unloading both ends with Hydra on truck.
Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode. [For DG Neutral Earthing]
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/8 stranded GI (Hot Dip) wire (4 Mts. long), 25 mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. [For DG Body Earthing]
Excavation of soil for installation of Earth Electrode and filling & ramming. (a) For Soft Soil
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. (a) 80 mm dia
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall /floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
Installation of DG Exhaust System Supply & Fixing of Exhaust piping/ Exhaust Chimney (Aprox Hight 20 mtr) including angle iron structure and Base foundation as required as per CPCB-IV norms.
DG Base foundation DG Sets Foundation [LxWxH=(2500X2000X500)mm] as required.
S & D of 1.1 KV. Gr. armored XLPE/A Al. LT cable of following. [Make: Gloster/Havells/RR/Polycab]. a) 2 core X 6 sq.mm
b) 4 core X 120 sq.mm
Laying of cable upto 120 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
Commissioning & testing of the Diesel Generator Set along with AMF panel with agency's own tools, tackles & fuel in presence of EIC.(Test Run- 1Hrs)
Supply, installation, testing of 240V; 72W LED type out door fitting on wall/ pipe pole and making necessary connection as per direction of E.I.C. ( Make:CG/ Philips:BRP409 LED 94 CW HE NR FG S1 PSU GR ) the following fittigs installed by scaffolding arrangement as per direction.
Supplying and fixing 415V, TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make- L&K). i) 63A
Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc.( Make- L&T) i) 250A-L&K
Supplying and fixing 415V, TPN on load front operated Changeover switch open execution type in SS enclosure/cubical with nuts bolts etc. i) 125A-L&K
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .