| Sl No | Description | Qty | Unit | Garg Construction L2 | SHUBHAM TRADERS L1 |
|---|---|---|---|---|---|
| 1.00MV CABLES | |||||
| 2.00Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required. | |||||
| 3.00 | Upto 35 sq. mm | 240 | Mtr | 40 ₹9,600 | 39 ₹9,360 Lowest |
| 4.00 | Above 35 sq. mm and upto 95 sq. mm | 375 | Mtr | 62 ₹23,250 | 61 ₹22,875 Lowest |
| 5.00Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written. | |||||
| 6.00 | 3.5C x 95 Sq.mm. Aluminum XLPE armored cable | 375 | Mtr | 1,280 ₹4,80,000 | 1,279 ₹4,79,625 Lowest |
| 7.00 | 3.5C x 25 Sq.mm. Aluminum XLPE armored cable | 175 | Mtr | 459 ₹80,325 | 458 ₹80,150 Lowest |
| 8.00 | 4C x 6 Sq.mm. CU XLPE armored cable | 25 | Mtr | 842 ₹21,050 | 840 ₹21,000 Lowest |
| 9.00 | 4C x 16 Sq.mm. CU XLPE armored cable | 20 | Mtr | 2,015 ₹40,300 Lowest | 2,015 ₹40,300 Lowest |
| 10.00 | 3C x 4 Sq.mm. CU XLPE armored cable | 20 | Mtr | 474 ₹9,480 | 472 ₹9,440 Lowest |
Tender Value
₹1.5 Cr
EMD Value
₹3.1 L
Closing Date
4 Jul 2025, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrical and Allied work for Langer Hall and Dharmshala at Mahasu Devta, Hanol Distt. Dehradun
2025_BRID3_85052_1
1346/BRIDCUL/985/25 Dated 18.06.2025
Open Tender
Electrical Works
Item Rate
540 days
Mahasu Hanol Dehradun
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹3.1 L
BRIDCUL Dehradun
8 Aug 2025
21 Jun 2025
4 Jul 2025
21 Jun 2025
4 Jul 2025
28 Jun 2025
27 Jun 2025
Amount
MV CABLES
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written.
3.5C x 95 Sq.mm. Aluminum XLPE armored cable
3.5C x 25 Sq.mm. Aluminum XLPE armored cable
4C x 6 Sq.mm. CU XLPE armored cable
4C x 16 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
CABLE TERMINATION
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.
3.5C x 95 Sq.mm. Aluminum XLPE armored cable
3.5C x 25 Sq.mm. Aluminum XLPE armored cable
4C x 6 Sq.mm. CU XLPE armored cable
4C x 16 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
DISTRIBUTION BOARDS
Supply, installation, testing and commissioning following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) - 8way, Double door (IP43, IK09)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4 + 18), Double door (IP43, IK09)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door (IP43, IK09)
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door (IP43, IK09)
Supplying and fixing of weatherproof enclosure for double pole, 240 volts, MCB (6A-32A) complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A Double pole
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 32A
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 25A
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 32A
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 40A
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 63A
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
Supply, installation, testing and commissioning 'C' series, SP MCB Supply, installation, testing and commissioning 5 amps to 32 amps rating, 240 volts, 'B' series, miniature circuit breaker suitable for lighting and other loads of folloeing poles int the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Point wiring in PVC conduit, with modular type switch: Wiring for light point/ fan ponit/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required- Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 & 15/16A amps modular socket outlet and 15/16 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supplying and fixing stiff pendent with 300 mm long, 20 mm dia X 1.6 mm thick steel conduit, aluminium cast back plate and brass holder complete, including wiring the down rod with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and painting etc. as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2X1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1X2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
CONDUIT
Supply, installation, testing and commissioning of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
EARTHING
S/L SWG GI wire in ground: Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc. as required
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Earthing with GI earth plate 600 mm x 600 mmx 6 mm thick including accessories and providing masonary enclouser with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcole/coke and salt as required.
LIGHT FIXTURES
20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures: 20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures complete with suitable rating lamps and all other necessary accessories to complete the installations as per specifications. * Minimum lumen 2000 Lumens in CCT range of 3000/4000 (As per Architect) as per ANSI,LED Make CREE/Osram/Samsung with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained. * Colour of light fixture shall be WHITE as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
18W, 2000 Lumen Recess mounted LED Down light fixtures: (False ceiling light) Supply, Installation, assembling, connection, testing & commissioning of 18W, IP20, 2000 Lumen Recess mounted LED Down light fixtures complete with suitable rating lamps and all other necessary accessories to complete the installations as per specifications. * Minimum lumen 2000 Lumens in CCT range of 3000/4000 (As per Architect) as per ANSI,LED Make CREE/Osram/Samsung with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained. * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
WALL MOUNTED LED LIGHT : (MIRROR LIGHT) Supply, Installation, assembling, connection, testing & commissioning of Mirror LED Light suitable for 12W luminaire along with all other necessary accessories.. IP20. * Minimum lumen 2000 Lumens in CCT range of 3000/4000 (As per Architect) as per ANSI,LED Make CREE/Osram/Samsung with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained. * Colour of light fixture shall be WHITE as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply of Weather Proof Recessed false ceiling light Recessed Celiing Light - 10W,800lm,IP65,3000/4000K, Dimension 100X80mm, Height 80mm Diameter is 100mm, Weight is 0.5kg, Fixing Suitable for ceiling-mounted recessed installation. Fixture is made of Die Cast Aluminium, Powder Coated, LED is COB, Inbuilt driver, Input AC 240V, 50/60Hz * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply of Weather Proof Recessed Downlighter (On Roof Chajja) Recessed Celiing Light - 10W,800lm,IP65,2700/3000K, Dimension 100X80mm, Height 80mm Diameter is 100mm, Weight is 0.5kg, Fixing Suitable for ceiling-mounted recessed installation. Fixture is made of Die Cast Aluminium, Powder Coated, LED is COB, Inbuilt driver, Input AC 240V, 50/60Hz * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Up & Down Light SITC of 2X10 W LED Up down light suitable for wall mounting , BIS approved , Body made of pressure Die cast aluminium , proper heat sink should be designed for better heat dessipation , The diffuser should be clear toughned glass with IK08 protection . The luminaire is provided with surge protection of 4 KV . Electronic driver having power factor>0.95, THD <10 % and input voltage range from 150-270V AC at 50Hz. Minimum lumen 2000 Lumens in CCT range of 3000/2700 as per ANSI,LED Make CREE/Osram/Samsung with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained.Ambient Operating Temperature is -10 Deg. to 50 Deg. Luminaire should Maintain Ingress Protection of IP65/IP66 for better weather proofing. * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
LED COVE LIGHT (5m Roll) Supply of IP20 LED strip with a nominimumal system lumen output of 800 lm /m with system efficacy of 105lm/W. The luminaire shall have a rated system lifetime of 30,000 hours. The luminaire shall have a color temperature of 3000/4000K and CRI>80with SDCM<3. luminaire is to operate on 24VDC.with working temperature rage of upto 35degC ambient. Luminaire must be supplied along with all the accessories such as driver, mounting tracks/ clips, end caps, diffuser, strip connectors etc as applicable. * Colour of light fixture shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supplying and ?xing PVC batten/ angle holder including connections etc. as required.
Supply of exhuast fan (300mm)
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required upto 450mm sweep.
JUNCTION BOXES
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector.
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector.
CABLE TRAYS
supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
DWC PIPES
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
120 mm dia (OD-120 mm & ID-103 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
CCTV SYSTEM
Design, Supply, Install, Testing,Commissionnig of CCTV System complete with all items mentioned but not limited to below: -
In general the complete system design and installations shall confirm to latest IEC guidelines and the specifications, drawings submitted here with.
Supply, installation, testing and commissioning of Cat6 cable.
Supply, Installation,testing and commissioning of 8Port POE Network Switch to provide Power and Data Communication for mentioned Camera. With 1 G SFP Module.
Supply, Installation, Testing & Commissiong of 5 MP IR Dome Camera 1/3? Megapixel progressive scan Exmor CMOS, Infrared, Dome camera with D/N ICR, IR, varifocal lens, 2.8mm-12mm, F1.6, with Audio, H.264, IP66 rated 720p @ 25fps, H.264: 4–8192 kbps, BLC/HLC/DWDR, IR distance up to 30m, RJ-45 connection, Inbuilt microSD card slot, BLC/HLC/DWDR, 3D DNR, ROI, ONVIF, PoE Complete as per specification, IP66, IK10, Including necessary accessories for mounting * Colour of Camera shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, Testing and Commissioning of Wall mounted 9U Rack along with power sockets strips and all other require components & acceessories to mount all the equipments for satisfactory job.
Supply, Installation, Testing and Commissioning of 6 single mode fiber optic cables (9/125 µm) with all necessary accessories to comply the installation.
Hard Drive Disk: SITC of Enterprise surveilliance HDD 8 TB for 60 days storage at D1 resolultion.
Supply, Installation, Testing and Commissioning of industrial type 32" LED Display for 24x7 runningg (ON), 1920 X 1080 Resolution, 450 CD/M2 Brightness, Wall Mounting Bracket.
Supply, Installation, Testing and Commissioning of 1 mtr. Cat 6 Patch cord.
Supply, Installation, Testing and Commissioning of 24 Port fully loaded patch panel
Any other Item Not included above but required to complete the Job:-
Supply installation Testing and commissioning of 10 KVA (3 PHASE) on line UPS system confirms to IS 16242(Part-I):2014 and IEC 60240-1 : 2008 with IGBT technology pure sine wave out put, double conversion with auto and manual static by pass switch three phase input / Three phase output with minimum 15 minutes battery back up of each UPS.
PUBLIC ADDRESS
Design, Supply, Install, Testing of all Public Address Components and Commissioning of a Complete Public Address/Evacuation System complete with all items mentioned but not limited to below: -
In general the complete system design and installations shall confirm to latest IEC Standards and the specifications, drawings submitted here with.
Supply, Installation, Testing and Laying of 2 Core X 1.5 Sq.mm FRLS PVC insulated Shielded Copper armoured cable with all required accessories.
Supply, Installation, Testing and Laying of 2 Core X 1.5 Sq.mm FRLS PVC insulated Shielded Copper unarmoured cable with all required accessories.
Supply, Installation, Testing and Laying of Speaker Cable 4sqmm armoured 2 core with all necessary accessories to comply the installation.
Ceiling mounted Weatherproof Speaker: Supply, Installation, Testing and Commissioning of 7.5W tapping Ceiling Speaker * Colour of Ceiling Speaker shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, Testing and Commissioning of CD Player with in built FM,USB,SD Card Supported.
Supply, Installation, Testing and Commissioning of Network based Power Amplifiers: Supply, Installation, Testing and Commissioning of 240W amplifier, and 4-16 Ohms transformer isolated, Frequency responce 60 Hz~15 kHz ( ± 3 dB ), LED status indicators, Including DC12V fan, Rated Power 120W, Require Power AC 220 V / 50 Hz, network based connections, with protection against overload, short circuit and overheat. can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection.
Supply, Installation, Testing and Commissioning of Wall mounted 9U Rack along with power sockets strips and all other require components & acceessories to mount all the equipments for satisfactory job.
Any other Item Not included above but required to complete the Job:-
LT PANEL
Supply, Installation, testing and commissioning of IP 54 (Double door) rated MAIN LT PANEL_DHARAMSHALA Having, Incomer : 100A FP MCCB ADJUST. TM BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) [MOTORIZED] (01 Nos). 100A FP ATS (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 100/5A CL-1.0,5VA Out Going: 25 Amp FP 10KA MCB with ON-OFF (02NOS.) 32 Amp FP 10KA MCB with ON-OFF (04NOS.) 40 Amp FP 10KA MCB with ON-OFF (01NOS.) 63 Amp FP 10KA MCB with ON-OFF (01NOS.) CONTRACTOR TO REFER SLD & DETAIL TECHNICAL SPECIFICATION ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
Supply, Installation, testing and commissioning of IP 54 (Double door) rated MAIN LT PANEL_LANGAR HALL Having, Incomer : 100A FP MCCB ADJUST. TM BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) [MOTORIZED] (01 Nos). 100A FP ATS (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 100/5A CL-1.0,5VA Out Going: 25 Amp FP 10KA MCB with ON-OFF (01NOS.) 32 Amp FP 10KA MCB with ON-OFF (04NOS.) 40 Amp FP 10KA MCB with ON-OFF (01NOS.) 63 Amp FP 10KA MCB with ON-OFF (02NOS.) CONTRACTOR TO REFER SLD & DETAIL TECHNICAL SPECIFICATION ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
LIGHTNING PROTECTION SYSTEM
Contractor to design lightening protection system along with SITC work. Contractor also need to submit Risk Analysis report based on site condition and location. Contractor to take soil resistivity report and necessary consideration to be taken along with below items. In general, the complete system design and installations shall confirm to latest IEC/IS Standards and the specifications, drawings submitted here with. Quantity and items mentioned here under is just for reference; Bidder shall be responsible to calculate the exact quantity as per design requirements for each item during bidding. The bidder shall include all necessary accessories to comply the installation and design to IS/IEC 62305 requirements, which broadly includes all system requirement.
AIR TERMINAL
Supply, Installation, Testing and Commissioning of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164- 2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) .
Supply, Installation, Testing and Commissioning of Roof conductor holder for sheet as specified in drawing , Bottom section made of stainless steel (V2A) & conductor holder made up of polyamide with Ø 8.5 mm slot at bottom.
Supply, Installation, Testing and Commissioning of cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts .
Supply, Installation, Testing and Commissioning of 1 mtr vertical air terminal with mounting accessories on the flat surface to meet the requirements of IS/IEC 62305. Tested for Electrical , mechanical and chemical as per IEC 62561 or equivalent as per make.
Supply, Installation, Testing and Commissioning of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU.
Supply, Installation, Testing and Commissioning of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ).
Supply, Installation, Testing and Commissioning of Bridging cable: From flexible CU cable of 16mm2 with black colur coating, chlorinated India rubber mixture .Exclusively used for indoor & outdoor application to make continuity at terminals.
Supply, Installation, Testing and Commissioning of Bridging cable with 319 8 Clamping Shoe, 8 mm (5325 307) or equivalent as per make.
DOWN CONDUCTOR
Supply, Installation, Testing and Commissioning of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square According to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx :70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding.
Supply, Installation, Testing and Commissioning of diagonal clamp suitable for FL 30. Installed with 2 hexagonal bolts.
Supply, Installation, Testing and Commissioning of Cross connector for earth fixing point suitable for FL 30. Installed with 2 hexagonal bolts.
Supply, Installation, Testing and Commissioning of Earth fixing point.
Supply, Installation, Testing and Commissioning of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate.
Supply, Installation, Testing and Commissioning of Connector, Rd 8?10 mm with pressure trough with 1 fix contact clamping screw, nut and serrated washer Including pre-mounted pressure sump, steel Conforms to the requirements according to DIN VDE 0185-305 (IEC 62305). Used to connect the aluminium conductor with the earth fixing point.
RING & VERTICAL EARTHING SYSTEM
Supply, Installation, Testing and Commissioning of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square According to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx :70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding.
Supply, Installation, Testing and Commissioning of diagonal clamp suitable for FL 30. Installed with 2 hexagonal bolts.
Supply, Installation, Testing and Commissioning of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate.
EARTH KIT
Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit
SURGE PROTECTION DEVICES
Supply, Installation, Testing and Commissioning of combination surge arresters Class B+C according to IEC 61643-1 for the lightning protection zone 0-2 consisting of din mountable - one common base consisting of 1 numbers of modular pluggable units of high energy varistor based technology to be connected between line to neutral and 1 number of GDT to be connected between neutral to earth complying the below technical parameters: a) Nominal voltage between L-N, Un = 230 volts b) Maximum continuous operating voltage between L-N, Uc = 320 volts c) Maximum continuous operating voltage between N-PE, Uc = 255 volts d) Lightning Impulse Current (L-N), Iimp (10/350 micro sec) = 7 KA e) Lightning Impulse Current (N-PE), Iimp (10/350 micro sec) = 25 KA f) Nominal discharge current In (8/20 micro sec), (N-PE) = 30 KA g) Max discharge current Imax (8/20 micro sec), (L-N) = 50 KA&(N-PE) = 50 KA h) Voltage Protection Level, Up = < 1.3 KV (L-N), < 1.2 KV (N-PE) i) Response time, tA = < 25 (L-N) &< 100 (N-PE) nano seconds j) Working condition of the SPD - Visual indication = Green “OK” & Red “Failure” k) Temp Range, -40° C to +80° C l) Degree of Protection IP 20
SERVO STABILIZER
Supply, Installation, testing and commissioning of Indoor Type Three phase servo controlled voltage stabilizer suitable for input voltage range 340 to 480VAC upto 200 KVA and above 200 KVA 360-480VAC And output voltage range 415V + 1%. A.C Three Phase. Natural Air Cooled with Input MCB / MCCB & Bypass switch , Air cooled upto 60 KVA & above oil cooled Type. (i) Rating : 50 KVA
Fire fighting system
6 Kg ABC (Powder Type) Fire Extinguisher. In HP Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 Providing & Fixing of fire extinguishers with necessary accessories, stand, trolley, etc.
ISI Marked portable fire extinguisher, 4.5 kg CO2 type fire extinguishers complete in all respect including initial fill and wall suspension brackets & shall conform to IS 2878 Providing & Fixing of fire extinguishers with necessary accessories, stand, trolley, etc.
Supplying, installation testing and commissioning of 6 liter K type Fire Extinguisher. In Stainless Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type brass valve fully charged with wet type chemical complete in all respects including wall suspension bracket.
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes: Emergency exit size: 4" X 12"
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes: "ABC" Extinguisher: 8" X 4"
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes: "CO2" Extinguisher: 8" x 4"
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Gun metal
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Gun metal
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal cap and chain as required : Single headed Gunmetal
Providing and fixing as per ISO standard fire hose cabinet Wall mounting type for internal size 600x 750x 250mm to house fire hose pipe , including all other related accessories fabricated from M.S. sheet (16 Gauge) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as shown in the drawing (or as approved by Architect) to house 15 mtr.x2 No. hose pipe
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m
Providing, fixing and testing forged brass 25 mm dia screwed inlet single acting air release valve with 25 mm dia ball valve on inlet side and pressure gauge with isolating cock. 25 mm Air Valve
Providing and fixing 100 mm diameter sand cast Iron grating with Frame For FHC drain
Supplying, installation testing and commissioning of the 80 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 100 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 150 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 200 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of 80 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Supplying, installation testing and commissioning of 100 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Supplying, installation testing and commissioning of 150 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Providing and fixing Power wiring with 3 core x 2.5 sq.mm. PVC armoured copper cable and PVC Conduit Pipe for wiring with termination of FHC from Fire Panel , etc. Including all required material and labour, terminations, etc. Complete.
Providing and fixing of pump trigger system only for Fire Hydrant Main Pump as per requirement and specification consisting of following items Including all required material and labour, terminations, etc. Complete. Pump On / Off switch: per set
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095. Size : 150 mm
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Charges for Liasoning with Fire officer and getting all approvals and permissions & NOC 's required for fire fighting at various stages & after completion of the project including All official payments.
Garg Construction (BID ID -389248)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .