Superintending Engineer, Project Implementation Unit, Health & Family Welfare Department.
Supply, Installation, Testing and Commissioning of Semi Modular Operation Theatre At.SDH Uchchhal Di.Tapi.
251161
2025-26/103/06
Open
Civil Works - Buildings
Tapi
1 document required · 1 mandatory
₹2,400
Yes
PIU-General Fund A/c 11-114
₹56,500
Yes
8 Dec 2025
8 Dec 2025
8 Dec 2025
27 Jan 2026
8 Dec 2025
Name Of Work :- Supply, Installation, Testing and Commissioning of Semi Modular Operation Theatre At.SDH Uchchhal
Estimated Rates Total Amount
Estimated Rates Total Amount
Item No. Item Of Work Unit may be more or
may be In Figure In word
Supply, Installation, Testing and Commissioning of 50 mm thick Pre Fabricated
Modular Operation Theater Panels (Walls and Ceiling) made out Polyurethane
foam injected at 40 Kg/m3 sandwiched between
0.8 mm thick GP and SP sheet on front side and 0.5 mm GP and SP/PPGI sheet
on back-side. The inner surface walls be fixed to the bricks wall with essential
support. There will be minimum possible cavity/gap in between solid and steel
walls and will be variable to suit the architects lay out for the flush mounting of
the equipments. The wall and ceiling panels must comply with necessary
provision of to JIS Z 2801/ISO 22196, BS EN 1363-1:2020, EN 1363-2:1999, EN
52210-2:1984-08, DIN 4102-1, Class A2. Any Third-party compliance certificate
Rupees Six Thousand Five Hundred Fifty
1 144.00 mandatory. Panel should be covered with protective sheath of 300 d.f.t Anti- 6,550.00 Sq Mtrs.
and Zero Paisa Only
bacterial Paint having undergone Washability/Water resistance Test JIS K
5663.7.12, permeability test less than 200 unit of permeability, Anti-bacterial
effect against staphyloccoccus aureus, Escherichia coli (via HALO test) and safety
and causative agents such as formaldehyde, toluene, xylene,
paradichlorobenzene etc. Third party (NABL approved Lab) certification for EGP
and thickness test certificate to be submitted
at time of supply.
The flooring within the surgical theatre should consist of a minimum of 2mm
thick antistatic seamless PVC, ensuring durability and safety. This floor should be
smooth, non-slip, and made from an impervious material with sufficient
conductivity to dissipate static electricity effectively, yet not so conductive as to
risk electric shock to personnel. The PVC used should be of very high quality,
particularly designed for electrostatic charge dissipation, and should not be less
than 2 mm in thickness. The installation process should utilize continuous rolls,
and joints should be seamlessly welded using special PVC thermal welding units
with welding bars of the same color to ensure uniformity and prevent
contamination. The sheets should be highly durable, capable of resisting shocks,
indentations, and scratches. The conductive material should be uniformly
impregnated within the PVC as grains to enhance its antistatic properties.
Additionally, the flooring should be inert to body fluids, chemicals, and
disinfectants, and remain unaffected by temperature variations typical within an Rupees Four Thousand Two Hundred
operating theatre. It should efficiently discharge electric charges up to 2 kV, and Fifty and Zero Paisa Only
the electrical resistance (point to ground) should be maintained within 2.5x10^4
to 5x10^6 ohms, ensuring no buildup of electrical charge beyond 100 volts.
Floor installation should be performed by skilled workers from accredited
agencies authorized by the PVC sheet supplier. The installation should include a
conductive copper grid beneath the PVC sheet, supported by liquid epoxy
compounds to create a uniform and level surface. Copper strips should be made
visible by grinding and not project more than 0.5mm above the floor level to
prevent damage to the PVC sheet, with one earthing lead brought out from
every 150 sq.ft area and attached to the main earthing strip/ground. The
flooring should also be mechanically shockproof, scratchproof, flame retardant,
and antimicrobial. Corners of the flooring should be uniformly curved, and a
concealed cove-former (aluminium) should overlap the wall panel to a height of
approximately 25mm and be sealed perfectly and uniformly. Before laying the
PVC, suitable self-leveling compounds should be used to prevent any
The door to the surgical theatre should be a hermetically sealed, single sliding
door measuring 2.1 meters in height and 1.5 meters in width. The door should
be equipped with a controller capable of being operated by elbow switches, foot
switches, and a touchless sensor, providing multiple, accessible control options.
The track for the door should be made from stainless steel or aluminum, with
the running surface for the top rollers angled appropriately to minimize
resistance and facilitate smoother movement. The door leaf should be
suspended using high-quality hard plastic rollers with double bearings at the
top. These rollers should run under the stainless steel or aluminum track to
ensure smooth and noiseless operation. The opening and closing mechanisms of
the door should be controlled by a microprocessor for precise electromechanical
movement. The material of the door should be either SMS or HPL, with a color
that matches the interior design. The door should be designed to be strong yet
lightweight for ease of use. In case the automatic mechanism fails, the door Rupees Two Lakh Ninety Five Thousand
should still be able to open and close effortlessly manually. The handle of the and Zero Paisa Only
door should be made from stainless steel with a matte finish and equipped with
a high-quality cylindrical or ESPg lock for security. The door leaf should
incorporate a high-quality synthetic rubber gasket with long durability to ensure
hermetic sealing and maintain a 99.99% air tightness at a minimum pressure of
75Pa. The floor on either side of the door should be perfectly level, with a
maximum permissible difference of +1mm, to avoid any tripping hazards or
unsealed gaps. The overall thickness of the finished door should range from 30-
60mm, with the inner part of the door filled with CFC-free polyurethane foam,
approximately 48mm thick, sealed airtight to block any microbial ingress. The
door and its controls should comply with IEE regulations, utilizing DC brushless
or PMDC motors that are effectively isolated from mains power to ensure safety
and reliability. Additionally, the door should include a vision window measuring
300mm x 300mm, featuring double-glazed panels that are hermetically sealed
Hatch boxesthe integrity
should of the seal.
be provided in each operating theater to facilitate the safe
and efficient removal of waste materials to the dirty linen area or adjacent
corridor. Each hatch box should be equipped with two doors, operated
electrically or motorized, designed such that only one door can be opened at a
time to prevent cross-contamination. UV lighting should be installed to ensure
sterilization and should remain on when both doors are closed, automatically Rupees One Lakh Fifteen Thousand and
4 1.00 turning off when either door is opened. Indicators should be provided on both 1,15,000.00 Nos.
Zero Paisa Only
sides of the operating theater to monitor the door open/close status. The
material of the hatch box should also be SS304 grade stainless steel, with a
minimum size of 600mm x 600mm.
Supply, Installation, Testing and Commissioning of Storage Units - Storage units
should be constructed with same material, as wall and ceiling panels. The
shelves, made of glass and, should be removable for cleaning. The unit should
be divided into two or more parts, each with individual glass doors equipped Rupees Eighty Five Thousand and Zero
5 1.00 with a high-quality locking system. The overall size of the storage unit should 85,000.00 Nos.
be approximately 200 cm (H) x 120 cm (W) x 35 cm (D).
Supply, Installation, Testing and Commissioning of Double-Bay Scrub Sink - The
scrub station should be compact, designed for use in the OT complex, and
facilitate pre-procedural scrubbing. It should be made from heavy gauge type
304 stainless steel with a minimum thickness of 1.5mm and feature seamless
welded construction polished to a satin finish. The scrub sink should have a front
access panel for easy maintenance of water control valves, waste connections,
stoppers, and strainers. Hands-free operation should be enabled through
infrared sensors with programmable adjustments. Thermostatic mixing valve Rupees One Lakh Twenty Six Thousand
control should maintain constant water temperature and be located behind the and Zero Paisa Only
access panel. Timing should be adjustable to meet individual usage
requirements, and units should have reduced anti-splash fronts. An additional
knee/foot-operated switch should also be provided for enhanced functionality.
AIR HENDALING UNIT Make:KrVelocity: Not More Then 10 mt/second. , Canvass
Connection-Heavy duty, non partical shreding,Fire Retardentuger,Nikotra only
Type: PLUG,Drirect Driven,Dynamically Balanced Selection of fan-Should run
comfortably at 50 HZ at rated capecity. Motor
Make:Siemence,B.B,Crompton,ABB , Type:TEFC, IP:55, Foot Mounted, VFD
compitable and I2 generation Safety: Motor should have interlocked with AHU
Motor door/excess/Fire DamperType-TWO TIRE, Floor Mounted , Inner
const.:0.6mm plain G.I , Outer const.:0.8 mm G.I. Pre coated / Powder coated Rupees Twelve Lakh Twenty Five
7 1.00 Thickness of Insulation: 25mm,PUF injected having density 40 to 42 kg/m3. 12,25,000.00 job
Thousand and Zero Paisa Only
,Colour:As approved by CLIENT CONDENSING UNIT :
Condensing unit for AHU with all assesories and instalation (Copper pipie
provide 3 mtr Only Extra will charged extra) consider 1200 sqfeet insulation
Double Dome OT Light with Ceiling mounted Double Dome LED OT lights having
following features and enclosed technical specifications, having Mobile App
Connectivity, Battery Backup
-Light intensity Ec - 160 000 & 160 000 lux, - Light intensity adjustment - 10 –
100% (using Digital Capacitive Touch (Fully Remote Controlled)
- Color temperature Tc (with adjustment)
-Light field diameter d10 at Ec - 100 - 150 mm
-Working range - 1 m
-Color rendering index 93Ra Rupees Three Lakh Ninety Thousand
8 1 - Focusing Preset: Adjustable 390000 Nos.
and Zero Paisa Only
- LED Average life - 50000-60000 hrs
- Diameter of Light - not less than 650 mm per dome
- Power Consumption - not more than 120W
OT Light should be BIS marked; manufacturer should have CDSCO License for
this product under Class A, Compliant to IEC standards such as IEC60601-
1:2005+A2:2020, IEC 60601-2-41:201 (Relevant Test Certificates to be
submitted with Bid) Clause-wise Technical Compliance to be
Single-arm surgery/anesthesia pendant designed for Operating Theatres should
feature a compact, modular configuration to meet the precise requirements of
hospitals, enabling customization to suit specific operational needs of both
Operating Theatres and Intensive Care Units. It should be equipped with robust
ceiling support capable of mounting a selection of arms. The extension arm,
pivotal for functionality, should allow horizontal movement with a radius of 800-
900mm and provide a level rotation ranging from 0 to 330/340 degrees, with
both the extension arm and terminal box designed to rotate together and
independently for maximum versatility. The pendant should support a net
loading capacity of min. 100 kg, accommodating a variety of medical
instruments and devices securely. For medical and electrical services, it should
offer configurations that include at least two oxygen outlets, two vacuum
outlets, one medical air, one medical air at 7 bar, and an optional nitrous oxide
outlet (In-scope of MGPS vendor) Additionally, there should be six main sockets, Rupees Two Lakh Eighty Four Thousand
each capable of supporting 5 to 15 amps, conforming to universal standards to and Zero Paisa Only
facilitate the operation of various medical and electronic devices. In terms of
materials and construction, the pendant should be crafted from high-strength
aluminum alloy with a sealed design to enhance durability and maintain sterile
conditions. The arm itself should be made from high-density aluminum alloy
extrusion, ensuring both strength and reliability. Installation of the pendant
should be ceiling-mounted to provide a reliable and firm setup, optimizing space
usage in the Operating Theatre or ICU while seamlessly integrating with existing
medical systems for managing medical gas, electrical services, data
communication, and equipment. Additionally, the pendant should include
practical features such as a stainless steel IV pole and a ward vacuum unit clamp
to further enhance its utility in a medical setting. With a net weight of
approximately 105 kg, accessible by the equipment carrier, the pendant should
be robust yet manageable, ensuring it meets the rigorous demands of modern
LED typeenvironments.
flat panel X-ray viewing panel should be supplied. This should comply
with relevant electrical safely codes. This should be a 2-panel viewing screen.
Mounting should be flush with the wall to avoid dust accumulation and growth
or organisms between wall and panel. Body should be of extruded aluminium
powder coated black with bacteria resistant and disinfectant resistant finish. The
diffuser on the front panel should be a uniformly lit screen. Dimming electronic Rupees Forty One Thousand Five
Hundred and Zero Paisa Only
control should be enclosed at the bottom of the cabinet. Proper spring-loaded
film clip with rollers should be provided to hold the films firmly and to remove
the film without scratches
Medical Gas Pipe Line Of Required dia for OT oxygen , Vaccum , Air.. Etc reuired
Point(from existing line ) as directed by engineer incharge from Outer Nearest
Rupees Three Lakh Forty Five Thousand
11 2 Passage to OT Pendant Rate Including , Alarm , Valve (for all line) , Point 345000 job
and Zero Paisa Only
,Flowmeter and Probe . if alredy then no payment given
Supply, Installation, Testing and Commissioning of Electrical
Wiring inside OT - Power distribution within each Operating
Theatre (OT) should be handled via distribution boards located
locally to each theatre using Fire Resistance Low Smoke
Wiring, layed in PVC conduits of reputed brand. The sub mains
power to these panels should be provided by the general
electrical contractor, and all distribution services within the Rupees Two Lakh Ninety Nine Thousand
departments should run from these panels. The power and Zero Paisa Only
distribution unit should hold certifications such as EN, CE, FDA,
IEC, and BIS to ensure compliance with international safety
and performance standards. Each wall of the MOT should have
a minimum of two hybrid switch sockets (6/16A) on each wall,
in compliance with IEC standards. Light fittings within the
clinical areas should be recessed LED types equipped with
controlInstallation,
Supply, gear andTesting
andinCommissioning
accordanceofwith the IP54 standard.
Membrane-Type Operation
Switch and Communication Controller - The Operation Switch and Comms
Controller should encompass all necessary controls to ensure the proper
operation and monitoring of equipment and services in the operating room
(OR). Positioned for optimal visibility in the surgeon's line of sight and the OT
staff, the wall-mounted membrane-buttons should be easily accessible to the
nurse for operation and assistance. In addition to hosting a digital clock and Rupees One Lakh Ninety Five Thousand
13 1 elapsed time indicator, the panel should feature a medical gas alarm, clearly
and Zero Paisa Only
indicating high and low gas pressures for each gas service, including vacuum,
supported by an audible alarm. The Operation Switch and Comms Controller
should also provide an alarm mute option for fault annunciation, with pressure
sensors strategically located near isolation valves. Controls for general lighting,
including ON/OFF and dimming, organized in groups for uniform illumination,
should be present. Furthermore, the panel should facilitate control over
operating lights (major and satellite) and camera functions (on/off and
In Words :- ( Rupees Fifty Six Lakhs Fourty Six Thousand Nine Hundred Fifty Only.)
I/we am/are willing to carry out the work at………………………………………………….% above/below percent (should be written in figures and words) of the estimated rates mentioned
Estimated amount put to tender
Add / deduct…………….% above / below
In words (Rupees………………………………..
Note -1 All works shall be carried out as per Public Work Department Handbook and other specification of Division or as directed.
Note -2 All the columns in Schedules should be filled in ink and the total of the entries ink last column should be struck by the contractor under his signature.
Note -3 Rates quoted include clearance of site ( prior commencement of work and at its close ). In all respect and hold good for work under all condition, site, moisture, weather etc.
Note -4 Serviceable material available ( if any ) after Demolishing / Dismentalling any item should be hand over to the concerned PIU Site Engineer In Charge as per instruction of
The Contractor shall exhibit a board with detailed specification and details of work as directed by the Engineer-In-Charge for which
no extra payment shall be made.
2 The labour cess will be deducted as per prevailing rules i.e. 1% of the work done.
3 GST and Income tax TDS will be deducted at a source while making payments of bills
In all R.C.C. Items in Rate Analysis Standard Cement Consumption has been taken as per Govt. G.R.: PRC-10/2017 Cement
4 Consumption/16/C Date:11/05/2017 as stated in S.O.R. therefore in R.C.C. items where there is a change as per actual mix design
the costof difference of cement consumption have been deducted from the rate of original item at the rate of input rate mentioned in
5 GST extra applicable in case of work based on SOR 2024-25 only.
Dy. Executive Engineer Dy. Executive Engineer (ele) Divisional Accountant Executive Engineer
PIU Zone-7 Tapi PIU Zone-7 Tapi PIU Zone-7 Surat PIU Zone-7 Surat
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Condition for cement.pdf
GR RnB Revise.pdf
GR-TMT-Lap Length.pdf
INSTRUCTIONS TO PERSON TENDERING.jpg
JPG
Performance Bond and SD-Paripatra-2023.pdf
PIU SPECIAL CONDITIONS.pdf
Inclusion of Insurance clause as per new SBD.pdf
6372 Make List HO 15.10.2025.pdf
Specification.pdf
Schedule B.pdf
SBD.pdf
Tender Document.pdf
PQ OT.pdf
Revised Tender Document.pdf
Revised PQ.pdf
Corrigendum For revised Point No.6.pdf
OT SDH Plan.pdf
Pre-Bid Meeting Clearification.pdf
Revised Specification.pdf
Re Revised PQ.pdf
Corrigendum for Certification.pdf
Corrigendum for submission of Certification.pdf
Download all tender documents and submit your bid