| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹67.2 LAccepted-AOC | ₹67.2 L Quoted ₹69.9 L | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹70.0 L+₹9,844 (0.14%)Rejected-Finance VIKRAM COACHING GALI SUDAMA NAGARI MADI NATH BAREILLY 243001 | BAREILLY | UTTAR PRADESH | 243001 | ₹70.0 L+₹9,844 (0.14%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹79.0 L+₹9.1 L (13.0%)Rejected-Finance | ₹79.0 L+₹9.1 L (13.0%) | L3 | Rejected-Finance Not Lowest |
| Sl No | Description | Qty | Unit | The Electrical Engineers L1 | Radhe Krishn Engineering L3 | M/s. S.S. Refrigeration, Bareilly L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply removing and fixing of AHU cooling coil 3200 CFM .The chilled water coil shall be of copper tube with Aluminum fins. The coil shall be made from seamless solid drawn copper tubes. The minimum thickness of the tube shall be 0.5mm for cooling/ heating. The coil shall be with 6 rows deep with 11 to 13 fins per inch spacing. The minimum thickness of the fins shall be 0.15mm nominal. The coil shall be designed and tested for a pressure of 10 Kg/ Sq.cm (g) and. U-bends shall be of copper, jointed to the tubes by brazing. | 1 | Each | 3,75,000 ₹3,75,000 | 2,01,000 ₹2,01,000 | 1,54,500 ₹1,54,500 Lowest |
| 2.00 | Supply removing of pluged copper tubing of chiller unit No 2 and fixing of size 6/8" Copper tube suitable for make Carrier Model No 30HXC155A 1x146 TR .complete all as specified and directed | 34 | Each | 32,000 ₹10,88,000 | 15,000 ₹5,10,000 | 5,150 ₹1,75,100 Lowest |
| 3.00 | Dehydration of Carrier make chiller unit with changing Compressor Oil, pressure testing with nitrogen vaccumizing and refilling of refrigerant in the system . | 1 | Each Job | 1,60,000 ₹1,60,000 Lowest | 8,10,000 ₹8,10,000 | 1,80,000 ₹1,80,000 |
| 4.00 | Supply and installation of chiller expansion PVC storage tank capacity 2000 Ltr insulated with thermal insulation with Class O closed cell nitrile rubber having thickness of 50 mm (Thermal conductivity is 0.035 w/m as per EN12667/ ISO 8497 and having μ value ≥ 6000) | 1 | Each | 40,006 ₹40,006 | 28,961 ₹28,961 Lowest | 95,600 ₹95,600 |
| 5.00 | Supply, installation and fabrication of thermal insulation with Class O closed cell nitrile rubber having thickness of 50 mm for Chiller unit (Thermal conductivity is 0.035 w/m as per EN12667/ ISO 8497 and having μ value ≥ 6000). | 3 | Each | 8,000 ₹24,000 Lowest | 25,000 ₹75,000 | 47,500 ₹1,42,500 |
| 6.00 | Supply installation and fabrication of 100 mm three way valve with actuator for chiller water line and fitted with flange and rubber gasket of the same . Size of pipe: 100 mm dia. | 5 | Each | 45,000 ₹2,25,000 Lowest | 75,000 ₹3,75,000 | 99,450 ₹4,97,250 |
| 7.00 | Supply installation and fabrication of 80 mm three way valve for the inlet and outlet chilled water line needs to be supplied and fitted with flange and rubber gasket of the same . Size of pipe: 80 mm dia. | 21 | Each | 17,500 ₹3,67,500 Lowest | 65,000 ₹13,65,000 | 55,400 ₹11,63,400 |
| 8.00 | Supply, fixing for Insulation of M S Pipe 100 mm with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete | 150 | RM | 1,400 ₹2,10,000 Lowest | 3,100 ₹4,65,000 | 4,000 ₹6,00,000 |
| 9.00 | Supply, fixing for Insulation of M S Pipe 150 mm with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete | 150 | RM | 2,000 ₹3,00,000 | 1,250 ₹1,87,500 Lowest | 6,000 ₹9,00,000 |
| 10.00 | Supply and fix thrmocol insuation section w chilled water piping of 150 mm bore with density not less than 20 Kg/cum covered with a layer of 120 gm / sqm polythene sheet (as vapour barrier) duly reinforced with 26 guage chicken wire mesh with buffing of all joints and tied town with GI lacing wire and finally finished rigid with26 guage aluminium foil cladding if laid inside the building , and with cement mortar of 1:3 of 12 mm thick if laid in ground or air outside the building complete including excavation, refiling making good the excavated surface wherever the pipes are required to be laid in ground. | 100 | RM | 3,000 ₹3,00,000 | 1,100 ₹1,10,000 Lowest | 5,500 ₹5,50,000 |
Tender Value
₹77.3 L
EMD Value
₹1.4 L
Closing Date
26 Jun 2026, 6:00 pmClosed
CWE Bareilly
HEADQUARTERS, COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, STATION ROAD, BAREILLY CANTT, PIN 243001
CA NO.CWE BLY/GE (W)/49 OF 2026-27SPECIAL REPAIR TO COOLING COIL, INSULATION OF CHILLER PIPE AND ITS CONNECTED ITEMS OF CENTRAL AC PLANT INSTALLED AT MH BAREILLY UNDER GE (WEST) BAREILLY
2026_MES_767658_1
8100/B/959/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE(West) Bareilly
As per NIT
6 documents required · 6 mandatory
₹1,000
GE(West) Bareilly
₹1.4 L
Yes
21 Aug 2026
25 May 2026
3 Jul 2026
25 May 2026
26 Jun 2026
19 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply removing and fixing of AHU cooling coil 3200 CFM .The chilled water coil shall be of copper tube with Aluminum fins. The coil shall be made from seamless solid drawn copper tubes. The minimum thickness of the tube shall be 0.5mm for cooling/ heating. The coil shall be with 6 rows deep with 11 to 13 fins per inch spacing. The minimum thickness of the fins shall be 0.15mm nominal. The coil shall be designed and tested for a pressure of 10 Kg/ Sq.cm (g) and. U-bends shall be of copper, jointed to the tubes by brazing. | 1 | Each | -1 | - |
| 2 | Supply removing of pluged copper tubing of chiller unit No 2 and fixing of size 6/8" Copper tube suitable for make Carrier Model No 30HXC155A 1x146 TR .complete all as specified and directed | 34 | Each | -1 | - |
| 3 | Dehydration of Carrier make chiller unit with changing Compressor Oil, pressure testing with nitrogen vaccumizing and refilling of refrigerant in the system . | 1 | Each Job | -1 | - |
| 4 | Supply and installation of chiller expansion PVC storage tank capacity 2000 Ltr insulated with thermal insulation with Class O closed cell nitrile rubber having thickness of 50 mm (Thermal conductivity is 0.035 w/m as per EN12667/ ISO 8497 and having μ value ≥ 6000) | 1 | Each | -1 | - |
| 5 | Supply, installation and fabrication of thermal insulation with Class O closed cell nitrile rubber having thickness of 50 mm for Chiller unit (Thermal conductivity is 0.035 w/m as per EN12667/ ISO 8497 and having μ value ≥ 6000). | 3 | Each | -1 | - |
| 6 | Supply installation and fabrication of 100 mm three way valve with actuator for chiller water line and fitted with flange and rubber gasket of the same . Size of pipe: 100 mm dia. | 5 | Each | -1 | - |
| 7 | Supply installation and fabrication of 80 mm three way valve for the inlet and outlet chilled water line needs to be supplied and fitted with flange and rubber gasket of the same . Size of pipe: 80 mm dia. | 21 | Each | -1 | - |
| 8 | Supply, fixing for Insulation of M S Pipe 100 mm with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete | 150 | RM | -1 | - |
| 9 | Supply, fixing for Insulation of M S Pipe 150 mm with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete | 150 | RM | -1 | - |
| 10 | Supply and fix thrmocol insuation section w chilled water piping of 150 mm bore with density not less than 20 Kg/cum covered with a layer of 120 gm / sqm polythene sheet (as vapour barrier) duly reinforced with 26 guage chicken wire mesh with buffing of all joints and tied town with GI lacing wire and finally finished rigid with26 guage aluminium foil cladding if laid inside the building , and with cement mortar of 1:3 of 12 mm thick if laid in ground or air outside the building complete including excavation, refiling making good the excavated surface wherever the pipes are required to be laid in ground. | 100 | RM | -1 | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQ_859711.xls
BOQ • 0.25 MB
PS49.pdf
Tender Documents • 2.59 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .